Numerical and experimental investigation of a novel liquid upper-feeding micro-channel flat loop thermosyphon cooling and heat recovery system

Authors:

Abstract
A novel liquid upper-feeding micro-channel flat loop thermosyphon (LUF-MCFLTS) system was developed, to eliminate the drying phenomenon of the upper surface in the traditional LTS and provide a highly efficient solution for DC cooling and heat recovery. The effects of cooling capacity (cooling water flow rate and temperature), heat load, and filling ratio on the heat transfer performance of the LUF-MCFLTS system are investigated experimentally. The results indicated that with the increase in cooling water flow, the decrease in cooling water temperature, and the increase in heat load, the heat transfer performance of the LUF-MCFLTS system was better. Under a heat load of 500 W, a cooling water flow rate of 600 L/h, and a cooling water temperature of 15°C, the heat recovery efficiency could reach 86.28%. Compared with the MCFTS and MCFLTS systems in literature, the recovery efficiency of the LUF-MCFLTS system could be increased by 31.6% and 2.64%, respectively. In addition, an effective numerical model to predict the heat recovery efficiency of the LUF-MCFLTS system with the experimental data in the 2.07% error band has been established. This work provides a new idea and theoretical basis for the design of DC cooling and heat recovery system.
Funding Information
  • European Commission (835778-LHP-C-H-PLATE-4-D)
  • Guangdong Provincial Department of Science and Technology (2019A050509008)

This publication has 33 references indexed in Scilit: