Determination of Parameters of Zero-Sequence Equivalent Circuits for Three-Phase Three-Legged YNynd Transformers Based on Onsite Low-Voltage Tests
- 13 May 2013
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 28 (3) , 1618-1625
Abstract
This paper proposes a new approach for obtaining parameters of the zero-sequence equivalent circuit of three-phase three-legged three-winding YNynd transformers (i.e., transformers with two wye windings and a third delta stabilizing winding). The methodology proposed in this paper includes a complete set of onsite field measurements using commercial equipment (traditionally used for onsite transformer leakage reactance tests). An easy-to-implement determination of the zero-sequence behavior of the YNynd transformer is achieved by means of separating the equivalent T-circuit into two different circuits, one of them to be used when the delta stabilizing winding is closed and the other when this is open. The effect of the resistive component of the zero-sequence impedances is also analyzed and quantified. Onsite measurements on a 45/16.05/10-kV 25-MVA power transformer and their comparison with high-voltage factory tests are presented to demonstrate and validate the proposed methodology.Keywords
This publication has 5 references indexed in Scilit:
- Transformer Model for Inrush Current Calculations: Simulations, Measurements and Sensitivity AnalysisIEEE Transactions on Power Delivery, 2010
- Parameter Determination for Modeling System Transients—Part I: Overhead Lines IEEE PES Task Force on Data for Modeling System Transients of IEEE PES Working Group on Modeling and Analysis of System Transients Using Digital Simulation (General Systems Subcommittee)IEEE Transactions on Power Delivery, 2005
- Transformer Engineering2004
- An Algorithm for Least-Squares Estimation of Nonlinear ParametersJournal of the Society for Industrial and Applied Mathematics, 1963
- Are Stabilizing Windings Necessary in All Y-Connected Transformers?Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1959