Deriving a Novel Equivalent Circuit to Capture Current Transformer Behavior Under Partial Saturation Phenomena Caused by Stray Fluxes
- 17 February 2026
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 41 (3) , 1493-1503
Abstract
Presence of the external stray fluxes or eccentric installation of the primary conductor results in non-uniform flux distribution in the current transformer (CT) core. This causes saturation in some portions of the core, called partial saturation (PS) phenomenon. Moreover, the saturation of the entire core results in CT total saturation. In both cases, CT accuracy decreases, which can result in measurement and tariff meter inaccuracy as well as protective relay maloperation. In this article, a novel electrical equivalent circuit is derived to accurately model stray fluxes and eccentricity of the primary conductor effects on partial and total saturation phenomena. The method is based on dividing the CT iron core into some portions. Each portion is then modeled with a nonlinear inductance within the equivalent circuit. This approach accurately captures the behavior of the CT under the PS phenomenon. The method demonstrates remarkable accuracy, closely mirroring outcomes obtained through finite element method (FEM) simulations and practical experimentations, and shows a significant speedup by a factor of 100 compared to the FEM. The ability to model stray fluxes and PS phenomena, along with high efficiency, makes the new circuit model very useful and necessary for implementing in electromagnetic transient program simulation tools.Keywords
This publication has 33 references indexed in Scilit:
- Detailed Magnetic Equivalent Circuit Based Real-Time Nonlinear Power Transformer Model on FPGA for Electromagnetic Transient StudiesIEEE Transactions on Industrial Electronics, 2015
- A Real-Time Nonlinear Hysteretic Power Transformer Transient Model on FPGAIEEE Transactions on Industrial Electronics, 2013
- Active-clamp forward converter with asymmetric transformer turns for reducing transformer DC offset current2012
- Influence of stray flux on protection systems2008
- Experience on stray flux interference of CT: case study of a power plant in Thailand2008
- Addressing Window Type Transformer Proximity Errors2006
- Application of the surface‐current method to the analysis of saturated electromagnetic devicesCOMPEL - The international journal for computation and mathematics in electrical and electronic engineering, 2004
- An integral approach for 3D magnetostatic field calculationCOMPEL - The international journal for computation and mathematics in electrical and electronic engineering, 1998
- Operation of ground sensor relays under conditions of partial CT saturationIEEE Transactions on Industry Applications, 1997
- Relay performance considerations with low-ratio CTs and high-fault currentsIEEE Transactions on Industry Applications, 1995