Abstract
As inverter-based resources (IBRs) are increasingly integrated into power systems, network resonance instability has become more common in recent years, primarily caused by the interaction between IBR power-electronic controllers and passive network elements. The existing s-domain nodal admittance matrix-based method provides a useful framework for large-scale resonance analysis and can deliver comprehensive modal information. However, when applied to power systems with a high proportion of renewable energy, the physical conditions associated with resonance instability driven by the negative-resistance effect of IBRs are not explicitly incorporated, and singular behavior in the nodal susceptance matrix may lead to misidentification of resonance points. To address these limitations, this paper proposes an improved s-domain nodal admittance matrix-based method. Specifically, the relationship between the negative-resistance effect of IBRs and modal impedance is analyzed to establish a modal-parameter criterion for unstable resonant modes, and the first-stage resonance screening is reformulated using the nodal reactance matrix to avoid singularity-induced misidentification. In addition, a method for establishing the s-domain impedance model of renewable energy stations is presented, and the theoretical basis and implementation procedure of the improved method are detailed. Finally, a modified IEEE 9-bus system is built in PSCAD/EMTDC. Comparing results with the existing method validates the improved method’s effectiveness.
Funding Information
  • National Natural Science Foundation of China (U24B2076)
  • National Natural Science Foundation of China (52507104)

This publication has 30 references indexed in Scilit: