Dielectric properties of mixed mineral and synthetic ester oil
- 1 November 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Science, Measurement & Technology
- Vol. 14 (9) , 704-714
Abstract
The dielectric properties of 20% synthetic ester oil mixed with mineral oil were studied for its potential applications as an insulator in transformers. The corona inception voltage of mixed oil under AC and DC voltages was measured by the ultra-high frequency (UHF) technique. A statistical study of the breakdown voltage of mixed oil under AC, DC and standard lightning impulse voltages was carried out to obtain a database which would be useful for designing transformer insulation. Further, the mixture was subjected to continuous breakdown studies under AC voltage with lightning impulse voltages, at regular intervals and characterised through measurement of interfacial tension, flash point, ionic mobility as well as UV–vis spectroscopy and frequency-domain spectroscopy studies to understand the liquid's chemical stability. The results of the study have shown that the mixture was stable even after several breakdowns. The ionic mobility and polarisation current have increased, indicating higher losses in the oil. UHF signal energy analysis and phase-resolved partial discharge analysis have revealed a reduction in discharge activity with mixed oils.Keywords
Funding Information
- Department of Science and Technology, New Delhi (DST/NM/NT/2018/33(c))
This publication has 31 references indexed in Scilit:
- Stability of mineral oil and oil–ester mixtures under thermal ageing and electrical dischargesIET Generation, Transmission & Distribution, 2017
- Data Requisites for Transformer Statistical Lifetime Modelling—Part I: Aging-Related FailuresIEEE Transactions on Power Delivery, 2013
- Synthetic ester transformer fluid: A total solution to windpark transformer technologyRenewable Energy, 2013
- Investigations on streamers phenomena in mineral, synthetic and natural ester oils under lightning impulse voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Streamer characteristic and breakdown in synthetic and natural ester transformer liquids under standard lightning impulse voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Vegetable oils, an alternative to mineral oil for power transformers- experimental study of paper aging in vegetable oil versus mineral oilIEEE Electrical Insulation Magazine, 2010
- Aging Performance and Moisture Solubility of Vegetable Oils for Power TransformersIEEE Transactions on Power Delivery, 2010
- Improvement of power transformers by using mixtures of mineral oil with synthetic estersIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Challenge of mixed insulating liquids for use in high-voltage transformers.1. Investigation of mixed liquidsIEEE Electrical Insulation Magazine, 2002
- Practical life-assessment technique for aged transformer insulationIEE Proceedings A Science, Measurement and Technology, 1993