Research on infrared spectroscopy detection of furfural content in transformer oil based on acetonitrile extraction
- 7 June 2024
- journal article
- research article
- Published by IOP Publishing in Measurement Science and Technology
- Vol. 35 (9) , 095004
Abstract
The stable operation of power transformers depends on the oil-paper insulation system, in which the aging degree of insulating paper is the key to evaluate the remaining life of the transformer. Currently, methanol extraction is widely used to detect the furfural content in oil to evaluate the aging state of insulating paper, but it ignores the influence of methanol produced during the operation of the transformer on the extraction results. To address this issue, this paper proposes a new method that can replace methanol extraction for detecting furfural in oil through simulation and experiment. Firstly, through simulation and experiment, it is proved that the strong vibration absorption peaks at 1677 cm−1 for furfural carbonyl and 2240 cm−1 for acetonitrile cyano can be used to establish a new method for extracting furfural content in oil using acetonitrile. A quantitative model between the concentration x of furfural in the furfural-acetonitrile mixed solution and the area y of the infrared absorption peak at 1677 cm−1 is established, with a goodness of fit of 0.9974. Secondly, a comparison between direct detection and acetonitrile extraction methods is conducted. The results show that direct detection is simple to operate, but the minimum detection concentration is 40 mg l−1, which is difficult to meet practical requirements. Acetonitrile extraction can reduce the minimum detection concentration to 0.1 mg l−1. At the same time, the extraction conditions are analyzed to determine the extraction ratio of 30, extraction times of 5, and extraction rate of 60%. Finally, the proposed detection method is applied to thermal aging tests on insulating paper of different types. The experimental results show that the proposed method has good repeatability and improves the detection resolution of furfural content. This paper combines infrared spectroscopy with acetonitrile extraction technology to open up a more efficient and practical new method for detecting furfural content in transformer oil.Keywords
Funding Information
- National Key Research and Development Plan of China Project (2017YFB0902705)
- Opening Foundation of State Key Laboratory of Metal Extrusion and Forging Equipment Technology (S2208100.W03)
- Xi’an Science and Technology Project (22GXFW0039 and 22GXFW0038)
- China Postdoctoral Science Foundation Project (2019M653631)
- Key R&D plan of Shaanxi Project (2020ZDLGY09-10)
This publication has 32 references indexed in Scilit:
- Atomic mechanisms of long-term pyrolysis and gas production in cellulose-oil composite for transformer insulationApplied Energy, 2023
- Aging state assessment of transformer cellulosic paper insulation using multivariate chemical indicatorsCellulose, 2021
- Aging assessment of transformer solid insulation: A reviewMaterials Today: Proceedings, 2021
- The application research of solid‐phase extraction and headspace gas chromatography in the detection of methanol in transformer oilIEEJ Transactions on Electrical and Electronic Engineering, 2020
- Preparation of furfural by catalytic pyrolysis of cellulose based on nano Na/Fe-solid acidFuel, 2019
- Analysis of fault of insulation aging of oiled paper of a large‐scale power transformer and the prediction of its service lifeIEEJ Transactions on Electrical and Electronic Engineering, 2019
- The production of furfural directly from hemicellulose in lignocellulosic biomass: A reviewCatalysis Today, 2019
- Near infrared spectroscopy: A mature analytical technique with new perspectives – A reviewAnalytica Chimica Acta, 2018
- The van Deemter equation: Assumptions, limits, and adjustment to modern high performance liquid chromatographyJournal of Chromatography A, 2013
- Furfural as a marker of cellulose degradation. A quantitative approachApplied Physics A, 2010