Feature Extraction of High Impedance Arcing Faults in Compensated MV Networks. Part I: DWT-Based Analysis of Phase Quantities
- 1 July 2007
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Abstract
In this paper, the initial transients in the electrical network due to arc reignitions associated with high impedance faults caused by leaning trees are extracted from phase voltages and currents. The discrete wavelet transform (DWT) is used for the fault feature extraction corresponding to band frequency 12.5- 6.25 kHz and therefore localizing this fault occurrence. The detection security is enhanced because the DWT is responded to a periodicity of the initial transients. A novel technique for the selectivity term of the faulty feeder is introduced. It is based on the power polarity, in which, this power is computed by multiplying the DWT detail coefficient of the current and voltage for each feeder. The fault due to a leaning tree occurring at different locations in an unearthed 20 kV network is simulated by ATP/EMTP and the arc model is implemented using the universal arc representation.Keywords
This publication has 7 references indexed in Scilit:
- Modeling and experimental verification of high impedance arcing fault in medium voltage networksIEEE Transactions on Dielectrics and Electrical Insulation, 2007
- Universal Arc Representation Using EMTPIEEE Transactions on Power Delivery, 2005
- Artificial neural networks for single phase fault detection in resonant grounded power distribution systems2002
- Transient protection of transmission line using wavelet transform2001
- A new generation of materials for medium voltage, compensated neutral networks1997
- Detection of resistive single‐phase earth faults in a compensated power‐distribution systemEuropean Transactions on Electrical Power, 1997
- Digital simulation of fault arcs in power systemsEuropean Transactions on Electrical Power, 1991