Ancillary Service Provision by Heat Pumps Using Load Flexibility and Predictive Control

Authors:

Abstract
Heat pumps offer considerable potential for providing frequency-related ancillary services to the electrical grid. However, rapid power modulation can cause condensation in the suction line even when the refrigerant remains superheated, a risk not explicitly addressed by conventional superheat control. We propose a successive linearization-based model predictive control scheme that explicitly considers the suction-line droplet-formation margin during prescribed compressor-power modulation for Frequency Containment Reserve. To achieve this, the vapor compression cycle is represented by a moving-boundary model extended with the dynamics of the suction line, heat source, and heat sink. The compressor speed is derived from the prescribed power and treated as a measured disturbance, while the controller minimizes state and input deviations from the prescribed equilibrium subject to thermodynamic safety constraints. In a numerical case study with Frequency Containment Reserve prequalification activations of 40 %, 60 %, and 80 % relative to the equilibrium power, the proposed scheme maintains a positive suction-line droplet-formation marginin all cases, whereas the PI benchmark falls below the condensation limit for up to 30 s. The mean normalized state deviation from the reference equilibrium selected for efficient operation is reduced by 10.1–38.7 %. These numerical results indicate the potential of predictive control to support ancillary-service power modulation without additional suction-line heating.