Assessment of dehumidification performance of non-corrosive desiccant in hybrid liquid desiccant-vapour compression system
Authors:
- 7 August 2022
- journal article
- research article
- Published by Taylor & Francis in Energy Sources, Part A: Recovery, Utilization, and Environmental Effects
- Vol. 44 (3) , 6909-6926
Abstract
Air-conditioning (AC) systems, which operate on traditional vapor compression refrigeration (VCR) systems, consume a substantial proportion of the world’s electricity consumed by the building industry. In the scope of decreasing greenhouse gas emissions, energy consumption, heating, ventilation, and air conditioning industries have focused on finding alternatives to electrically operated VCR systems. A combination of a liquid desiccant dehumidification system (LDDS) with a VCR system has been recommended as a superior substitute in warm and moist climates. The focus of this research article is to design and fabricate a small-scale 5 kW hybrid LDDS system by integrating the distinct technologies mentioned above. Additionally, data collected on the vapor pressure of potassium formate (KCOOH) at various solution concentrations and temperatures is being collected to assist in encouraging research and determine the optimal concentration range. In this study, experimental analysis and comparison of dehumidification performance was conducted between two desiccants by analyzing the effects of input variables ( , , and ) on the output response ( , , and ). The results showed that the solution with a 69.92% KCOOH concentration had nearly the same vapor pressure as a solution with a 35% LiCl concentration. Moreover, it was revealed that the lowest values of and and the highest value of yield maximum values of the output responses. At the same combination of input variables, the KCOOH desiccant has a much higher hybrid system coefficient of performance than the LiCl desiccant.
Keywords
This publication has 22 references indexed in Scilit:
- Renewable energy for liquid desiccants air conditioning system: A reviewRenewable and Sustainable Energy Reviews, 2018
- Experimental measurement of equilibrium vapour pressure of H2O/KCOOH (potassium formate) solution at high concentrationInternational Journal of Refrigeration, 2018
- Liquid desiccant materials and dehumidifiers – A reviewRenewable and Sustainable Energy Reviews, 2016
- Three years experimental comparative analysis of a desiccant based air conditioning system for a flower greenhouse: Assessment of different desiccantsApplied Thermal Engineering, 2015
- Review of solar regeneration methods for liquid desiccant air-conditioning systemEnergy and Buildings, 2013
- Thermodynamic analysis of a counter flow adiabatic dehumidifier with different liquid desiccant materialsApplied Thermal Engineering, 2013
- Hybrid liquid desiccant air-conditioning system: Experiments and simulationsApplied Thermal Engineering, 2011
- Synergization of Clean Energy Utilization, Clean Technology Development and Controlled Clean Environment Through Thermally Activated Desiccant Cooling System2008
- Predictions of moisture removal rate and dehumidification effectiveness for structured liquid desiccant air dehumidifierEnergy, 2004
- ANOVA, Taguchi, and Other Design of Experiments Techniques2000