Chromium vapor density measurement by optical absorption spectroscopy of diffuse vacuum arcs in vacuum interrupters
- 1 October 2017
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 90-93
Abstract
The metallic vapor density in vacuum arc in a vacuum interrupter is crucial for deeper understanding of the anodic activities and dielectric recovery process. In this work, the objective is to measure the Cr metallic vapor density and its axial distribution along the gap in the vacuum arc between chromium contacts. The method of the optical absorption spectroscopy (OAS) using a broadband light source is adopted. The result shows that when the vacuum arc operates in diffuse mode, the maxima of metallic vapor density distribution occurs in the vicinity of electrodes during arcing period, representing the cathodic vapor source and anodic vapor source. Following the decrease of arc current, the metallic vapor density decrease as well. At current zero, the metallic vapor has a nearly uniform distribution in the gap of about 3×10 17 m -3 .Keywords
This publication has 13 references indexed in Scilit:
- Fully kinetic model of breakdown during sheath expansion after interruption of vacuum arcsJournal of Applied Physics, 2016
- Observation of the Plasma Plume at the Anode of High-Current Vacuum ArcIEEE Transactions on Plasma Science, 2011
- Laser measurement of copper vapor density after a high-current vacuum arc discharge in an axial magnetic fieldIEEE Transactions on Plasma Science, 2005
- Secondary plasma in the gap of high-current vacuum arc: origin and resulting effectsIEEE Transactions on Plasma Science, 2003
- Recovery of breakdown strength of a vacuum interrupter after extinction of high currentsIEEE Transactions on Dielectrics and Electrical Insulation, 2002
- Measurement of high copper vapour densities by laser-induced fluorescenceJournal of Physics D: Applied Physics, 1988
- Measurement of Particles and Vapor Density after High-Current Vacuum Arcs by Laser TechniquesIEEE Transactions on Plasma Science, 1987
- Measurement of the Neutral Copper Vapor Density around Current Zero of a 500-A Vacuum Arc Using Laser-Induced FluorescenceIEEE Transactions on Plasma Science, 1985
- Cathode spots and vacuum arcsPhysica B+C, 1981
- Measurement of the neutral vapour density decay following the extinction of a high-current vacuum arc between copper electrodesJournal of Physics D: Applied Physics, 1975