Adaptive busbar differential relaying scheme during saturation period of current transformers based on alienation concept
Open Access
- 1 November 2016
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 10 (15) , 3803-3815
Abstract
This study presents an advanced technique provided with adaptive differential relay characteristics for avoiding current transformer (CT) saturation effects. The proposed technique uses the alienation and differential protection principles to make adaptive logic; if no CT saturation is detected, the differential principle alone is capable of tripping the busbar. If CT saturation is detected, both the alienation and differential principles must pickup in order to trip. The alienation coefficient is useful in CT saturation detection, evaluation of CT saturation degree and adapting the differential relay characteristics during saturation period of CTs to avoid false operation in the event of external faults. The differential current and alienation coefficient are calculated from two terminal currents of the busbar. The proposed protective scheme has several attractive features, including the simplicity of on‐line implementation, not affected by the remanent flux in the CT core, and it is independent of the CT parameters/characteristics and secondary burden. A real 19.57 kV busbar is simulated using Alternate Transients Program/Electro‐Magnetic Transient Program and MATLAB packages to examine the suggested scheme under different types of faults. Under normal operating conditions and external faults, the scheme remains stable and it operates only for the case of internal faults. Moreover, it is unaffected by CT saturation.Keywords
This publication has 15 references indexed in Scilit:
- Experimental results and technique evaluation based on alienation coefficients for busbar protection schemeInternational Journal of Electrical Power & Energy Systems, 2015
- Performance evaluation of busbar protection schemes under different fault scenarios2015
- A new digital busbar protection technique based on frequency information during CT saturationInternational Journal of Electrical Power & Energy Systems, 2013
- A Traveling-Wave-Based Amplitude Integral Busbar Protection TechniqueIEEE Transactions on Power Delivery, 2012
- Protection scheme for transmission lines based on alienation coefficients for current signalsIET Generation, Transmission & Distribution, 2010
- Busbar protection – a review2010
- A Traveling-Wave-Based Protection Technique Using Wavelet/PCA AnalysisIEEE Transactions on Power Delivery, 2010
- A Busbar Differential Protection Relay Suitable for Use With Measurement Type Current TransformersIEEE Transactions on Power Delivery, 2005
- A busbar protection technique and its performance during CT saturation and CT ratio-mismatchIEEE Transactions on Power Delivery, 2000