Abstract
Accurate spatial position measurement of overhead power lines is essential for ensuring the reliability of power systems, especially in smart grid scenarios that require real-time monitoring. However, existing methods face significant challenges: contact-based techniques, such as tension or differential GPS (DGPS) sensors, are costly and cumbersome, while image-based methods are vulnerable to weather conditions. Magnetic sensors, offering a non-contact measurement approach, present a promising alternative. However, current technology often suffers from non-linearity and high uncertainty in alternating current (AC) environments, limiting their accuracy. This paper introduces a Frequency-Aided Extended Kalman Filter (FA-EKF) algorithm that integrates frequency information into the prediction model, thereby enhancing stability and efficiency in AC signal measurements. The proposed algorithm significantly reduces convergence time and measurement uncertainty. Experimental validation in laboratory-scale models demonstrates the method’s effectiveness, with a relative error of less than 2%. Further simulations show that the method achieves 97.5% relative accuracy at a 2.5-meter distance in one-dimensional measurements and maintains over 90% relative accuracy in two-dimensional measurements within a 1.5-meter radius around the target line in realistic scenarios. This paper also explores the impact of factors such as sensor spacing, angular deviation, and interference from other current sources.
Funding Information
  • National Natural Science Foundation of China (U23A20651)

This publication has 45 references indexed in Scilit: