A robust and accurate discrete Fourier transform‐based phasor estimation method for frequency domain fault location of power transmission lines
Open Access
- 2 February 2022
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 16 (10) , 1990-2002
Abstract
Frequency domain methods had been commonly used in power transmission line fault location. To improve the accuracy of frequency domain fault location methods, this paper studies a robust and accurate discrete Fourier transform (DFT)‐based phasor estimation method. First, this paper analyses the deviation characteristics of DFT output phasors caused by decaying DC components with data window sliding. Based on these characteristics, this paper employs rotation factor computation to construct linear equations for the purpose of estimating the accurate fundamental frequency phasor during fault transient process. In this way, the accurate fundamental frequency phasor can be calculated by a two‐step linear operation. Furthermore, to eliminate the effect of off‐nominal frequency, the proposed method adjusts frequency deviation by using interpolation method. To further enhance the robustness for frequency domain fault location, the PauTa criterion is used to exclude the anomalous equations in the phasor estimation process. Finally, electro‐magnetic fault simulation is used to evaluate the proposed method. The test results demonstrate that the proposed method improve the accuracy of fault location during the fault transient process.Keywords
This publication has 28 references indexed in Scilit:
- Modified DFT-Based Phasor Estimation Algorithms for Numerical Relaying ApplicationsIEEE Transactions on Power Delivery, 2017
- DC Offset Removal Algorithm for Improving Location Estimates of Momentary FaultsIEEE Transactions on Smart Grid, 2017
- A New DFT-Based Phasor Estimation Algorithm Using High-Frequency ModulationIEEE Transactions on Power Delivery, 2016
- A phasor filtering algorithm on eliminating the effect of fault transient components for the frequency domain fault location2011
- Phasor estimation considering DC component using UKF2011
- Estimation of transmission line parameters from measurementsInternational Journal of Electrical Power & Energy Systems, 2008
- Removal of dc offset and subsynchronous resonance in current signals for series compensated transmission lines using a novel Fourier filter algorithmElectric Power Systems Research, 2006
- The effect of DC offset on current operated relays2002
- An analytic method for measuring accurate fundamental frequency componentsIEEE Transactions on Power Delivery, 2002
- Removal of DC-offset in current waveforms using digital mimic filteringIEEE Transactions on Power Delivery, 1995