An Arc Furnace as a Source of Voltage Disturbances—A Statistical Evaluation of Propagation in the Supply Network
Open Access
Abstract
This article presents the results of measuring Pst indicators at three points of a power system supplying a large source of voltage disturbances—an arc furnace. Measurements were made at three voltage levels: 30, 110, and 400 kV. Recorded values of Pst at each point were subjected to statistical analysis, the probability distributions were adjusted to their histograms, and the nature of changes in the basic parameters of these distributions with the distance from the source of disturbances was indicated. The adjustments of the distributions were made using a modified firefly algorithm.Keywords
This publication has 35 references indexed in Scilit:
- Flicker Propagation Pricing in Power Systems Using a New Short-Circuit-Based Method for Determining the Flicker Transfer CoefficientIEEE Transactions on Instrumentation and Measurement, 2020
- Phaselet Transform Based Approach for Detecting Voltage Flickers Due to Distributed Generation UnitsIEEE Transactions on Industry Applications, 2017
- On the influence of network impedance on flicker measurements2017
- Simple Continuous Assessment of Transmission-Network Flicker Levels Caused by Multiple SourcesIEEE Transactions on Power Delivery, 2015
- Synthesis and Evaluation of Fast Onload Multitap Changers for Flicker Compensation in AC Arc FurnacesIEEE Transactions on Power Delivery, 2014
- Flicker summation factor in the slovenian transmission network2011
- Study of flicker propagation in electric grid by modeling and on-site flicker measurements2010
- An Algorithm for Determining the Direction to a Flicker SourceIEEE Transactions on Power Delivery, 2006
- A V-I slope-based method for flicker source detection2005
- A Method Based on Interharmonics for Flicker Propagation Applied to Arc FurnacesIEEE Transactions on Power Delivery, 2005