Development of Second Order High Frequency Filter for Partial Discharge Measurement
Open Access
- 20 March 2024
- journal article
- research article
- Published by Akademia Baru Publishing in Journal of Advanced Research in Applied Sciences and Engineering Technology
- Vol. 41 (2) , 194-207
Abstract
Partial discharge (PD) can occur on any high-voltage equipment. This study is particularly concerned with the PD that occurs on underground cables. Researchers frequently struggle to isolate interference noise from the PD signal when doing PD measurements. Therefore, to reduce the interference noise during PD measurements, Sallen-Key high-pass filters with a 500 kHz, or a little bit higher cut-off frequency are designed. This filter is designed with a designated cut-off frequency value because the frequency range of the PD signal is between 1 MHz to 1 GHz. Based on the results of experimental testing for actual filters, the designed filter is a high-pass filter with a cut-off frequency of 500KHz. When the generator function's input frequency values are set between 500 kHz and 2.4 MHz, the signal will pass the filter and provide output values for both frequencies and amplitude. However, at frequencies lower than 500 kHz, the signal is beginning to be filtered and the output signal's amplitude is getting close to zero. Based on the PD testing results, there is interference on the PD signal shown on the oscilloscope when a 1kV supply is applied to an underground cable without using a filter. But, when the proposed filter is used in PD testing, the ripple voltage is reduced from 123 mV to 67 mV. This proves that when the designed filter is used in PD testing, it can reduce interference noise on the PD signal.Keywords
This publication has 23 references indexed in Scilit:
- Studies on the Characteristics of Partial Discharges in High-Voltage XLPE Cable Joints exposed to Lightning Impulse Voltages2023
- Research on Integrated Technology of PD Ultrasonic Signal and UHF Signal Detection2022
- Early Warning of XLPE Power Cable Breakdown by Using Partial Discharge Testing2021
- Development of Partial Discharge Detection Device for PD Detection on Medium Voltage XLPE Cable2021
- Performance Assessment for Bare Patch Antenna and Integrated Filter-antenna Microstrip Patch Resonator Based for Partial Discharge Application in HV Equipment2021
- Pattern Recognition of Partial Discharge Based on VMD-CWD Spectrum and Optimized CNN With Cross-Layer Feature FusionIEEE Access, 2020
- Challenges Associated with Implementation of HFCTs for Partial Discharge Measurements2020
- Automatic partial discharge recognition using the cross wavelet transform in high voltage cable joint measuring systems using two opposite polarity sensorsInternational Journal of Electrical Power & Energy Systems, 2020
- To the Issue of the Development of Partial Discharge Theory2019
- PD-source recognition in generator bars using a high-voltage coaxial-type high-pass filter2007