High Frequency Current Transformer Modeling for Traveling Waves Detection
- 1 June 2007
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE) in 2007 IEEE Power Engineering Society General Meeting
- p. 1-6
Abstract
Current traveling waves are utilized to localize faults on transmission lines using conventional current transformers. This paper investigates high frequency characterization of the current transformer. The current transformer parameters at high frequencies are experimentally determined. They are obtained using frequency response measurements where the current transformer transfer function is calculated from measured impulse signals. Therefore its performance under transient conditions can be studied using different programs such as EMTP and MATLAB. The current transformer modeling and its experimental verifications show that there are good replicas of high frequency traveling waves over a suitable range for fault locators. The test results insure the CT applicability to traveling wave fault location.Keywords
This publication has 4 references indexed in Scilit:
- Comparison of simulated and recorded transients for travelling wave fault location2004
- Stray capacitances of two winding transformers: equivalent circuit, measurements, calculation and lowering2002
- Transmission level instrument transformers and transient event recorders characterization for harmonic measurementsIEEE Transactions on Power Delivery, 1993
- Current Transformer Accuracy with Asymmetric and High Frequency Fault CurrentsIEEE Transactions on Power Apparatus and Systems, 1981