Abstract
When discharge faults occur inside transformers, hydrogen (H2) gas is generated and dissolves into the insulating oil. However, conventional dissolved gas analysis (DGA) techniques cannot achieve in situ detection, and existing fiber-optic sensors lack sufficient detection limits. To enable in situ detection of transformer oil-dissolved trace H2, this work proposes a fiber-optic Fabry-Pérot (F-P) probe based on a composite membrane. The F-P cavity is fabricated by microassembling a single-mode fiber and a ceramic insert, and an ultrathin graphene membrane is transferred onto the cavity end-face as a support layer, followed by deposition of a Pd-Ag alloy as the H2-sensitive layer and pure Pd as the protective layer. Gas-phase H2 detection and in situ oil-dissolved H2 detection experiments are conducted using the fabricated fiber-optic F-P sensor. Results demonstrate that, in gas-phase environments with H2 concentrations ranging from 0 to 167 ppm, the sensor exhibits a sensitivity of 18.5 pm/ppm and a detection limit of 0.14 ppm, with a response time of 6 minutes. When directly immersed in transformer oil, the sensor achieves a sensitivity of 89.7 pm/ppm and a detection limit of 0.08 ppm for oil-dissolved H2 concentrations between 0 and 79.1 ppm. Furthermore, excellent recovery and selectivity performance are verified. Therefore, the fiber-optic F-P H2 sensor proposed in this work enables high-performance in situ detection of oil-dissolved H2 at sub-100 ppb levels.
Funding Information
  • Excellent Young Scientists Fund of the National Natural Science Foundation of China (52222706)
  • National Natural Science Foundation of China (5500-202315525A-3-2-ZN)

This publication has 32 references indexed in Scilit: