An improved test method for refrigerant flammability limits in a 12 L vessel
- 26 February 2018
- journal article
- research article
- Published by Taylor & Francis in Science and Technology for the Built Environment
- Vol. 24 (8) , 861-866
Abstract
The current study presents an improved test method for refrigerant flammability limit measurements. Such measurements are essential for determining refrigerant safety classifications. Predicated on expert interviews and experiments, several changes to ASTM E681 and related standards are recommended, as follows. The 12 L glass vessel should be replaced with transparent polycarbonate. The orientation of the electrode supports and the temperature probe should be changed from vertical to horizontal. All penetrations should be removed from the rubber stopper, it should be weighted for a total mass of 2.5 kg, and the initial pressure should be 90 kPa absolute. The flame angle should be plotted versus refrigerant concentration to obtain flammability limits. Finally, the vessel pressure should be measured during each test. These changes are relatively easy to implement and they will improve the test precision and reproducibility without significantly changing previously established flammability limits.Keywords
Funding Information
- American Society of Heating, Refrigerating and Air-Conditioning Engineers (1717RP)
This publication has 19 references indexed in Scilit:
- Experimental research on the concentration characteristics of R32 and R161′ combustion product HFEnergy, 2017
- Insights into the next generation HVAC&R refrigerant futureScience and Technology for the Built Environment, 2016
- Combustion inhibition and enhancement of premixed methane–air flames by halon replacementsCombustion and Flame, 2015
- Laminar burning speeds and flame structures of mixtures of difluoromethane (HFC-32) and 1,1-difluoroethane (HFC-152a) with air at elevated temperatures and pressuresHVAC&R Research, 2014
- Effects of temperature and humidity on the flammability limits of several 2L refrigerantsJournal of Fluorine Chemistry, 2012
- On the pressure dependence of flammability limits of CH2=CFCF3, CH2F2 and methaneFire Safety Journal, 2011
- Method of test for burning velocity measurement of flammable gases and resultsHVAC&R Research, 2011
- Lower Flammability Limit of Difluoromethane and Percolation TheoryInternational Journal of Thermophysics, 2004
- Comparison of two standard test methods for determining explosion limits of gases at atmospheric conditionsJournal of Hazardous Materials, 1999
- Reinvestigation of Flammability Limits Measurement of Methane by the Conventional Vessel Method with AC Discharge IgnitionCombustion Science and Technology, 1999