Evaluation of ability to withstand short circuit and development of large capacity 500 kV autotransformer
Open Access
- 29 December 2022
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Electric Power Applications
- Vol. 17 (5) , 579-592
Abstract
Once the short circuit damage accident of a large capacity 500 kV transformer occurs suddenly, it will seriously affect the safe operation of the power grid. The article expounds on the calculation principle and evaluation method of the transformer's ability to withstand short circuit, then introduces the design structure of 400 MVA/500 kV short circuit autotransformer and calculates the electromagnetic force and evaluates the ability to withstand short circuit under high voltage ‐ medium voltage (HV‐MV) and medium voltage ‐ low voltage (MV‐LV) conditions. By comparing with typical 110 kV and 220 kV transformers, the short‐circuit characteristics are analysed, the control strategy is proposed, and the largest capacity short circuit prototype with 400 MVA/500 kV autotransformer is developed. Last, the sudden short circuit test is carried out in the large current test centre. The results show that the large capacity autotransformer passed the big current impulse under HV‐MV and MV‐LV short circuit conditions for the first time in the world, and all indicators are good, which confirms the accuracy of the strength check and the effectiveness of the short circuit evaluation method and also proves that the 500 kV autotransformer has strong strength to withstand short circuits.Keywords
Funding Information
- National Natural Science Foundation of China (51822702)
- Higher Education Discipline Innovation Project (B17016)
This publication has 21 references indexed in Scilit:
- Short Circuit Stress Analysis Using FEM in Power Transformer on H-V Winding Displaced Vertically & HorizontallyAlexandria Engineering Journal, 2018
- Short-Circuit Strength of Power Transformer Windings-Verification of Tests by a Finite Element Analysis-Based ModelIEEE Transactions on Power Delivery, 2016
- An Investigation of Winding Curvature Effect on the Mechanical Strength of Transformer WindingsIEEE Transactions on Power Delivery, 2015
- Short circuit tests to derive the buckling strength of Continuously Transposed Cable for power transformers under the influence of the paper insulation thickness2014
- Dynamic Deformation Analysis of Power Transformer Windings in Short-Circuit Fault by FEMIEEE Transactions on Applied Superconductivity, 2013
- Coupled Electromagnetic-Structural Analysis of the Spiraling Phenomenon in a Helical Winding of a Power TransformerIEEE Transactions on Power Delivery, 2013
- Analysis of Buckling Strength of Inner Windings in Transformers Under Radial Short-Circuit ForcesIEEE Transactions on Power Delivery, 2013
- Analysis of winding stability of short-circuit test model for extra-high voltage power transformer2011
- Eigenvalue Analysis for Investigation of Tilting of Transformer Winding Conductors Under Axial Short-Circuit ForcesIEEE Transactions on Power Delivery, 2011
- Instability of the continuously transposed cable under axial short-circuit forces in transformersIEEE Transactions on Power Delivery, 2002