Modeling and Stability Analysis of Inverter-Based Microgrid Under Harmonic Conditions
- 19 August 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 11 (2) , 1330-1342
Abstract
Microgrids (MGs) operate under harmonic conditions due to the integration of nonlinear loads. The autonomous harmonic compensation control of inverterinterfaced DG has been proposed to successfully mitigate the harmonics. However, the small-signal analysis of harmonic compensation controls has not been investigated in the microgrid with multiple inverters. This paper develops the modeling and analysis of the inverterbased MGs under harmonic conditions. The concept of dynamic phasor (DP) is used to describe the fundamental and harmonic components of an ac waveform via dc variables. The developed model consists of droop-controlled distributed generators (DGs), diodes rectifiers (working as nonlinear load) and resistance loads. Virtual impedance control is considered in the droop-controlled DGs for the autonomous harmonic compensation. Based on the developed DP model, the dynamic behavior of the microgrid is investigated via small-signal analysis. It is observed that the virtual impedance for harmonic compensation brings inter-inverter oscillations on harmonic domain. Participation and eigenlocus analysis are performed to investigate the influence of parameter tuning of harmonic compensation on microgrid stability. Numerical simulations are carried out to validate the effectiveness of the proposed modeling method and the analysis results.Keywords
Funding Information
- National Natural Science Foundation of China (51622702)
This publication has 34 references indexed in Scilit:
- Microgrid stability: Classification and a reviewRenewable and Sustainable Energy Reviews, 2016
- Mitigation of Harmonics in Grid-Connected and Islanded Microgrids Via Virtual Admittances and ImpedancesIEEE Transactions on Smart Grid, 2015
- Dynamic Phasor Modeling of Multi-Generator Variable Frequency Electrical Power SystemsIEEE Transactions on Power Systems, 2015
- Dynamic Phasor-Based Modeling of Unbalanced Radial Distribution SystemsIEEE Transactions on Power Systems, 2015
- Modeling and Analysis of Harmonic Stability in an AC Power-Electronics-Based Power SystemIEEE Transactions on Power Electronics, 2014
- On Dynamic Evaluation of Harmonics Using Generalized Averaging TechniquesIEEE Transactions on Power Systems, 2014
- Dynamic Phasors-Based Modeling and Stability Analysis of Droop-Controlled Inverters for Microgrid ApplicationsIEEE Transactions on Smart Grid, 2014
- An Enhanced Islanding Microgrid Reactive Power, Imbalance Power, and Harmonic Power Sharing SchemeIEEE Transactions on Power Electronics, 2014
- Hybrid-model transient stability simulation using dynamic phasors based HVDC system modelElectric Power Systems Research, 2006
- Dynamic phasors in modeling and analysis of unbalanced polyphase AC machinesIEEE Transactions on Energy Conversion, 2002