Abstract
Load Redistribution Attacks (LRAs) threaten the secure operation of power distribution networks by manipulating load distribution. This paper proposes a stealthy attack called Partition Load Redistribution Attacks (PLRAs). Instead of causing detectable power transfers like traditional LRAs, PLRAs exploit the inherent reactive power balance within a network partition. This allows PLRAs to remain undetected. To mitigate the adverse impacts of PLRAs, a tri-level defense optimization framework is proposed, using Static Var Generators (SVGs) to enhance the resilience of the system against attacks. The upper level minimizes the investment cost of SVGs. The middle level simulates worst-case PLRAs, where an attacker manipulates reactive power to maximize operating costs and voltage deviations. The lower level models the optimal post-attack response of the operator using installed SVGs. A nested column-and-constraint generation (NCCG) algorithm is employed to solve the complex tri-level problem. The effectiveness of the proposed framework is validated through case studies on the IEEE 33-bus and 69-bus systems.