Abstract
The calibration system for conventional instrument transformers does not apply to the electronic transformers (ECT/EVT) that meet the requirements of the IEC61850-9-2 digital substation protocol. In this paper, a calibration system for both electronic transformers and conventional transformers based on sampling techniques using digital multimeters (DMMs) is reported. This calibration system uses conventional instrument transformers as references, non-inductance shunts for current to voltage (I/V) conversion, and an inductive voltage divider (IVD) for secondary attenuation. Having received the pulse-per-second (PPS) signal from the merging unit (MU), a function generator burst pulses to trigger the DMMs for synchronous sampling. An improved quasi-synchronization algorithm is adopted as windowed discrete Fourier transform (DFT) for ratio and phase displacement calculation. This paper analyses the uncertainty contributions and makes corrections to the calibration results. Uncertainty evaluation under power frequency proposed for the calibration of CT up to 10kA is estimated to be within 10ppm and 15μrad for ratio and phase displacement, 25ppm and 30μrad for voltage transformers up to 500kV/√3 with a coverage factor k =2.