Lukasz Kocewiak
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Previous Organizations / Institutes
The organizations / institutes from the scholar's other articles in the past ten years
Research Subjects
Lukasz Kocewiak has a total of 70 co-authors. Here are the top co-authors by number of shared publications:
- Mohammad Kazem Bakhshizadeh
Rsted Wind Power A/S, Fredericia, Denmark
7 shared publications - Frede Blaabjerg
Aalborg University
6 shared publications Jesper Hjerrild
Electrical System Design and Grid Integration, Ørsted Fredericia Denmark
6 shared publicationsClaus Leth Bak
Department of Energy Aalborg University Aalborg Denmark
5 shared publications- Claus Leth Bak
Department of Energy, Aalborg University, Aalborg, Denmark
4 shared publications - Guangya Yang
Department of Wind and Energy Systems, Technical University of Denmark, Kongens Lyngby, Denmark
3 shared publications
Latest Publications
- 15 August 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 40 (2) , 1255-1268
Software-Defined Virtual Synchronous Condenser
Synchronous condensers (SCs) play important roles in integrating wind energy into relatively weak power grids. However, the design of SCs usually depends on specific application requirements and may not be adaptive enough to the frequently-changing grid conditions caused by the transition from conventional to renewable power generation. This paper devises a software-defined virtual synchronous condenser (SDViSC) method to address the challenges. Our contributions are fourfold: 1) design of a virtual synchronous condenser (ViSC) to enable full converter wind turbines to provide built-in SC functionalities; 2) engineering SDViSCs to transfer hardware-based ViSC controllers into software services, where a Tustin transformation-based software-defined control algorithm guarantees accurate tracking of fast dynamics under limited communication bandwidth; 3) a software-defined networking-enhanced SDViSC communication scheme to allow enhanced communication reliability and reduced communication bandwidth occupation; and 4) Prototype of SDViSC on our real-time, cyber-in-the-loop digital twin of large-wind-farm in an RTDS environment. Extensive test results validate the excellent performance of SDViSC to support reliable and resilient operations of wind farms under various physical and cyber conditions.
- 15 August 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 40 (2) , 1255-1268
Software-Defined Virtual Synchronous Condenser
Synchronous condensers (SCs) play important roles in integrating wind energy into relatively weak power grids. However, the design of SCs usually depends on specific application requirements and may not be adaptive enough to the frequently-changing grid conditions caused by the transition from conventional to renewable power generation. This paper devises a software-defined virtual synchronous condenser (SDViSC) method to address the challenges. Our contributions are fourfold: 1) design of a virtual synchronous condenser (ViSC) to enable full converter wind turbines to provide built-in SC functionalities; 2) engineering SDViSCs to transfer hardware-based ViSC controllers into software services, where a Tustin transformation-based software-defined control algorithm guarantees accurate tracking of fast dynamics under limited communication bandwidth; 3) a software-defined networking-enhanced SDViSC communication scheme to allow enhanced communication reliability and reduced communication bandwidth occupation; and 4) Prototype of SDViSC on our real-time, cyber-in-the-loop digital twin of large-wind-farm in an RTDS environment. Extensive test results validate the excellent performance of SDViSC to support reliable and resilient operations of wind farms under various physical and cyber conditions.
- Top Cited PapersOpen Access
- 18 April 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Open Journal of Power Electronics
- Vol. 5, 583-604
Grid Integration of Offshore Wind Power: Standards, Control, Power Quality and Transmission
Offshore wind is expected to be a major player in the global efforts toward decarbonization, leading to exceptional changes in modern power systems. Understanding the impacts and capabilities of the relatively new and uniquely positioned assets in grids with high integration levels of inverter-based resources, however, is lacking, raising concerns about grid reliability, stability, power quality, and resilience, with the absence of updated grid codes to guide the massive deployment of offshore wind. To help fill the gap, this paper presents an overview of the state-of-the-art technologies of offshore wind power grid integration. First, the paper investigates the most current grid requirements for wind power plant integration, based on a harmonized European Network of Transmission System Operators (ENTSO-E) framework and notable international standards, and it illuminates future directions. The paper discusses the wind turbine and wind power plant control strategies, and new control approaches, such as grid-forming control, are presented in detail. The paper reviews recent research on the ancillary services that offshore wind power plants can potentially provide, which, when harmonized, will not only comply with regulations but also improve the value of the asset. The paper explores topics of wind power plant harmonics, reviewing the latest standards in detail and outlining mitigation methods. The paper also presents stability analysis methods for wind power plants, with discussions centered on validity and computational efficiency. Finally, the paper discusses wind power plant transmission solutions, with a focus on high-voltage direct-current topologies and controls.
- 18 April 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Open Journal of Power Electronics
- Vol. 5, 583-604
Top Cited PapersOpen AccessGrid Integration of Offshore Wind Power: Standards, Control, Power Quality and Transmission
Offshore wind is expected to be a major player in the global efforts toward decarbonization, leading to exceptional changes in modern power systems. Understanding the impacts and capabilities of the relatively new and uniquely positioned assets in grids with high integration levels of inverter-based resources, however, is lacking, raising concerns about grid reliability, stability, power quality, and resilience, with the absence of updated grid codes to guide the massive deployment of offshore wind. To help fill the gap, this paper presents an overview of the state-of-the-art technologies of offshore wind power grid integration. First, the paper investigates the most current grid requirements for wind power plant integration, based on a harmonized European Network of Transmission System Operators (ENTSO-E) framework and notable international standards, and it illuminates future directions. The paper discusses the wind turbine and wind power plant control strategies, and new control approaches, such as grid-forming control, are presented in detail. The paper reviews recent research on the ancillary services that offshore wind power plants can potentially provide, which, when harmonized, will not only comply with regulations but also improve the value of the asset. The paper explores topics of wind power plant harmonics, reviewing the latest standards in detail and outlining mitigation methods. The paper also presents stability analysis methods for wind power plants, with discussions centered on validity and computational efficiency. Finally, the paper discusses wind power plant transmission solutions, with a focus on high-voltage direct-current topologies and controls.
- Open Access
Impact of Synchronous Condensers’ Ratings on Mitigating Subsynchronous Oscillations in Wind Farms
Subsynchronous oscillations have occurred in wind farms due to the high penetration of converter-based technology in power systems and may potentially lead to grid instability. As an effective solution, synchronous condensers, with their ability to control voltage and inject reactive power in the power system, are increasingly being adopted, as they can lead to the mitigation of such oscillations in weak grid conditions. However, the impact of synchronous condensers’ power ratings on system stability is a topic that requires further investigation. In fact, an improper selection of a synchronous condenser’s rating will not extinguish existing subsynchronous oscillations and may even cause the emergence of new oscillatory phenomena. This paper presents a novel examination of the impact that the synchronous condenser’s power rating has on the small-signal stability of a wind farm with existing subsynchronous oscillations while being connected to a weak grid. The wind farm’s model is developed using state-space modeling, centering on grid interconnection and incorporating the state-space submodel of a synchronous condenser to show its impact on subsynchronous oscillation mitigation. The stability analysis determines the optimal synchronous condenser’s power ratings for suppressing these oscillations in the wind farm model. The findings are corroborated through time domain simulations and fast-Fourier transformation (FFT) analysis, which further validate the stability effects of a synchronous condenser’s rating.
Open AccessImpact of Synchronous Condensers’ Ratings on Mitigating Subsynchronous Oscillations in Wind Farms
Subsynchronous oscillations have occurred in wind farms due to the high penetration of converter-based technology in power systems and may potentially lead to grid instability. As an effective solution, synchronous condensers, with their ability to control voltage and inject reactive power in the power system, are increasingly being adopted, as they can lead to the mitigation of such oscillations in weak grid conditions. However, the impact of synchronous condensers’ power ratings on system stability is a topic that requires further investigation. In fact, an improper selection of a synchronous condenser’s rating will not extinguish existing subsynchronous oscillations and may even cause the emergence of new oscillatory phenomena. This paper presents a novel examination of the impact that the synchronous condenser’s power rating has on the small-signal stability of a wind farm with existing subsynchronous oscillations while being connected to a weak grid. The wind farm’s model is developed using state-space modeling, centering on grid interconnection and incorporating the state-space submodel of a synchronous condenser to show its impact on subsynchronous oscillation mitigation. The stability analysis determines the optimal synchronous condenser’s power ratings for suppressing these oscillations in the wind farm model. The findings are corroborated through time domain simulations and fast-Fourier transformation (FFT) analysis, which further validate the stability effects of a synchronous condenser’s rating.
- Open Access
An Extended Nonlinear Stability Assessment Methodology For Type-4 Wind Turbines via Time Reversal Trajectory
As the integration of renewable energy generation increases and as conventional generation is phased out, there is a gradual decline in the grid's strength and resilience at the connection point of wind turbines (WTs). Previous studies have shown that traditional grid-following controlled converters exhibit deteriorating dynamic characteristics and may result in an unstable system when connected to a weak grid. Due to the limitations of linear analysis, transient stability investigations are necessary. However, existing methods, such as standalone time-domain simulations or analytical Lyapunov stability criteria, have drawbacks, including computational intensity or excessive conservatism. Our prior research proposed an innovative approach to estimate the system boundary - a time-limited region of attraction (TLRoA), using a hybrid linearised Lyapunov function-based method and the time-reversal technique to compensate for the known limitations. However, in that work, the accuracy of the estimated TLRoA was not investigated, i.e. the TLRoA was not compared against a forward simulated region of attraction, and the sensitivity of the system parameters on the TLRoA was not explored. Moreover, the framework did not consider nonlinear control elements such as PLL saturation. In this paper, we not only build upon our previous work and propose directions that address these gaps but also enhance its effectiveness by introducing optimal sampling to improve further the speed of estimating the TLRoA. Furthermore, the stability boundary is verified using time-domain simulation studies in PSCAD.
Open AccessAn Extended Nonlinear Stability Assessment Methodology For Type-4 Wind Turbines via Time Reversal Trajectory
As the integration of renewable energy generation increases and as conventional generation is phased out, there is a gradual decline in the grid's strength and resilience at the connection point of wind turbines (WTs). Previous studies have shown that traditional grid-following controlled converters exhibit deteriorating dynamic characteristics and may result in an unstable system when connected to a weak grid. Due to the limitations of linear analysis, transient stability investigations are necessary. However, existing methods, such as standalone time-domain simulations or analytical Lyapunov stability criteria, have drawbacks, including computational intensity or excessive conservatism. Our prior research proposed an innovative approach to estimate the system boundary - a time-limited region of attraction (TLRoA), using a hybrid linearised Lyapunov function-based method and the time-reversal technique to compensate for the known limitations. However, in that work, the accuracy of the estimated TLRoA was not investigated, i.e. the TLRoA was not compared against a forward simulated region of attraction, and the sensitivity of the system parameters on the TLRoA was not explored. Moreover, the framework did not consider nonlinear control elements such as PLL saturation. In this paper, we not only build upon our previous work and propose directions that address these gaps but also enhance its effectiveness by introducing optimal sampling to improve further the speed of estimating the TLRoA. Furthermore, the stability boundary is verified using time-domain simulation studies in PSCAD.
- Open Access
Nonlinear Stability Boundary Assessment of Multi-Converter Systems Based On Reverse Time Trajectory
As the integration of wind power accelerates, wind power plants (WPPs) are expected to play a crucial role in ensuring stability in future power grids. This paper examines the nonlinear stability boundary of a multi-converter system in a wind power plant (WPP) connected to an AC power grid via a long HVAC cable. Traditionally, for nonlinear analysis of WPPs, a simplification is adopted wherein the WPP is treated as an aggregation of individual wind turbines (WTs), with a simplified portrayal of the collector network. However, in the presence of different technologies, such as STATCOM, that are placed away from the WTs, the model aggregation will not hold. This paper presents a unified methodology to model and investigate the high-dimensional stability boundary of a WPP with a STATCOM. The stability region of the system, i.e. the region of attraction (RoA), is determined by the reverse time (backwards) trajectory technique. Furthermore, the estimated stability boundary is verified using time-domain simulation studies in PSCAD.
Open AccessNonlinear Stability Boundary Assessment of Multi-Converter Systems Based On Reverse Time Trajectory
As the integration of wind power accelerates, wind power plants (WPPs) are expected to play a crucial role in ensuring stability in future power grids. This paper examines the nonlinear stability boundary of a multi-converter system in a wind power plant (WPP) connected to an AC power grid via a long HVAC cable. Traditionally, for nonlinear analysis of WPPs, a simplification is adopted wherein the WPP is treated as an aggregation of individual wind turbines (WTs), with a simplified portrayal of the collector network. However, in the presence of different technologies, such as STATCOM, that are placed away from the WTs, the model aggregation will not hold. This paper presents a unified methodology to model and investigate the high-dimensional stability boundary of a WPP with a STATCOM. The stability region of the system, i.e. the region of attraction (RoA), is determined by the reverse time (backwards) trajectory technique. Furthermore, the estimated stability boundary is verified using time-domain simulation studies in PSCAD.
- Open Access
- 3 January 2023
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 17 (14) , 3523-3535
Integrating black start capabilities into offshore wind farms by grid‐forming batteries
Power systems are currently experiencing a transition towards decarbonisation through the large‐scale deployment of renewable energy sources. These are gradually replacing conventional thermal power plants which today are the main providers of black start services. Consequently, in case of a total/partial blackout, conventional black‐start resources may not be ready for operation. Offshore wind farms (OWFs), with their large capacity and fast controllers, have potential as innovative black‐start units, thus, the need for a new design for OWFs. Here, challenges and possible solutions in integrating black start services into offshore wind farms will be presented. The first challenge is represented by the self‐start capability. The self‐start unit should be capable of forming the wind farm power island and withstanding transient phenomena due to the equipment energisation. The investigated solution comprises grid‐forming (GFM) converters in the wind farm design, which could be battery energy storage systems (BESSs) to also increase the service availability. The challenges are analysed using simulations on a wind farm, and the proposed solutions are discussed. It can be concluded that a hybrid system comprised of a BESS and an OWF, with GFM control, applying soft‐charging, etc., represents a good proposal to provide black start services by OWFs.
- 3 January 2023
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 17 (14) , 3523-3535
Open AccessIntegrating black start capabilities into offshore wind farms by grid‐forming batteries
Power systems are currently experiencing a transition towards decarbonisation through the large‐scale deployment of renewable energy sources. These are gradually replacing conventional thermal power plants which today are the main providers of black start services. Consequently, in case of a total/partial blackout, conventional black‐start resources may not be ready for operation. Offshore wind farms (OWFs), with their large capacity and fast controllers, have potential as innovative black‐start units, thus, the need for a new design for OWFs. Here, challenges and possible solutions in integrating black start services into offshore wind farms will be presented. The first challenge is represented by the self‐start capability. The self‐start unit should be capable of forming the wind farm power island and withstanding transient phenomena due to the equipment energisation. The investigated solution comprises grid‐forming (GFM) converters in the wind farm design, which could be battery energy storage systems (BESSs) to also increase the service availability. The challenges are analysed using simulations on a wind farm, and the proposed solutions are discussed. It can be concluded that a hybrid system comprised of a BESS and an OWF, with GFM control, applying soft‐charging, etc., represents a good proposal to provide black start services by OWFs.
- Open Access
Modal Aggregation Technique to Check the Accuracy of the Model Reduction of Array Cable Systems in Offshore Wind Farms
The need for a verification method for aggregation techniques for passive electrical systems is necessary as power systems increase in complexity. Model reduction is crucial to increase the number of simulations necessary to ensure a stable and reliable design of power systems. This paper presents a novel modal domain-based technique to identify the best aggregation technique for a given system and to indicate the validity of the aggregation. This is done by benchmarking different aggregation techniques and using the dominant contribution factor ratio as a validity parameter. The different aggregation techniques are compared via time-domain simulations against the full detailed model. It is found that (1) the power loss aggregation technique is the most precise when it weighs the equivalent impedances of the parallel feeders, (2) unequal current generation does not impact the aggregation accuracy, (3) individual string aggregation provides the best results for dynamic simulations, and (4) the validity of aggregation decreases as frequency or cable length increases.
Open AccessModal Aggregation Technique to Check the Accuracy of the Model Reduction of Array Cable Systems in Offshore Wind Farms
The need for a verification method for aggregation techniques for passive electrical systems is necessary as power systems increase in complexity. Model reduction is crucial to increase the number of simulations necessary to ensure a stable and reliable design of power systems. This paper presents a novel modal domain-based technique to identify the best aggregation technique for a given system and to indicate the validity of the aggregation. This is done by benchmarking different aggregation techniques and using the dominant contribution factor ratio as a validity parameter. The different aggregation techniques are compared via time-domain simulations against the full detailed model. It is found that (1) the power loss aggregation technique is the most precise when it weighs the equivalent impedances of the parallel feeders, (2) unequal current generation does not impact the aggregation accuracy, (3) individual string aggregation provides the best results for dynamic simulations, and (4) the validity of aggregation decreases as frequency or cable length increases.
- 10 January 2022
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (5) , 3939-3946
Experimental Analysis of Root Causes for Rotor-Speed-Dependent Emissions From Type 3 Wind Turbines
Multi-frequency (or harmonic) emissions and interactions are ongoing challenges for converter-dominated power systems. Consequently, multi-frequency models are introduced for power quality and harmonic stability studies. Rotor-Speed-Dependent (RSD) emissions from Type 3 Wind Turbines (WT) can lead to unexpected interactions. However, there are only a few specific studies on Type 3 WTs’ emissions. Besides, the provided analyses have been only based on field measurements. In this paper, the uncertainties of the field measurements are demonstrated experimentally. This paper provides an experimental analysis of emissions in different parts of a Type 3 WT, including stator, rotor, grid-side converter, and DC-link. In this way, theoretical emission patterns are formulated in sequence domain and verified by experimental measurements from a 2.2 MVA Type 3 WT tested by a 15 MVA grid emulator. The tests include emission measurements in different rotor speeds with identical output power set-point. To the best of our knowledge, the provided experiments are unique presentations from different parts of a Type 3 WT using MVA-scale torque and grid emulators. The test results provide a good impression of the existence, patterns, and amplitudes of the RSD emissions. Addressing such emissions in multi-frequency models can be necessary for the improvement of harmonic studies.
- 10 January 2022
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (5) , 3939-3946
Experimental Analysis of Root Causes for Rotor-Speed-Dependent Emissions From Type 3 Wind Turbines
Multi-frequency (or harmonic) emissions and interactions are ongoing challenges for converter-dominated power systems. Consequently, multi-frequency models are introduced for power quality and harmonic stability studies. Rotor-Speed-Dependent (RSD) emissions from Type 3 Wind Turbines (WT) can lead to unexpected interactions. However, there are only a few specific studies on Type 3 WTs’ emissions. Besides, the provided analyses have been only based on field measurements. In this paper, the uncertainties of the field measurements are demonstrated experimentally. This paper provides an experimental analysis of emissions in different parts of a Type 3 WT, including stator, rotor, grid-side converter, and DC-link. In this way, theoretical emission patterns are formulated in sequence domain and verified by experimental measurements from a 2.2 MVA Type 3 WT tested by a 15 MVA grid emulator. The tests include emission measurements in different rotor speeds with identical output power set-point. To the best of our knowledge, the provided experiments are unique presentations from different parts of a Type 3 WT using MVA-scale torque and grid emulators. The test results provide a good impression of the existence, patterns, and amplitudes of the RSD emissions. Addressing such emissions in multi-frequency models can be necessary for the improvement of harmonic studies.
- Open Access
- 11 July 2021
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 15 (15) , 3564-3576
Test methodology for validation of multi‐frequency models of renewable energy generators using small‐signal perturbations
Providing trustworthy and accurate multi‐frequency (or harmonic) models for renewable energy generators (REG) is an ongoing challenge for harmonic studies. There have been effective attempts to propose and design a test device to validate the harmonic models, mainly based on shunt current perturbations. However, using additional devices for perturbations is costly for converter‐based test sites. This paper provides the test specifications to extend the application of the grid emulators for voltage perturbations and appropriate harmonic model validation. Besides, the effects of the sequence couplings, initial emissions, and power set‐points on the test results have been overlooked in the literature. Considering these effects, this paper proposes a generic test methodology to obtain more accurate models in the sequence domain. The experimental verification of the proposed methodology is demonstrated using a 7 MVA grid emulator for testing of a 2 MVA photo‐voltaic converter and a 2 MVA Type 3 wind turbine. This way, the test challenges, specifications, and recommendations are presented using the MW‐scale experiments on different REGs. Furthermore, the effects of sequence couplings and initial emissions on the calculation results are investigated and compared. The proposed methodology is applicable for harmonic model validation as well as empirical modelling.
- 11 July 2021
- Published by Institution of Engineering and Technology (IET) in IET Renewable Power Generation
- Vol. 15 (15) , 3564-3576
Open AccessTest methodology for validation of multi‐frequency models of renewable energy generators using small‐signal perturbations
Providing trustworthy and accurate multi‐frequency (or harmonic) models for renewable energy generators (REG) is an ongoing challenge for harmonic studies. There have been effective attempts to propose and design a test device to validate the harmonic models, mainly based on shunt current perturbations. However, using additional devices for perturbations is costly for converter‐based test sites. This paper provides the test specifications to extend the application of the grid emulators for voltage perturbations and appropriate harmonic model validation. Besides, the effects of the sequence couplings, initial emissions, and power set‐points on the test results have been overlooked in the literature. Considering these effects, this paper proposes a generic test methodology to obtain more accurate models in the sequence domain. The experimental verification of the proposed methodology is demonstrated using a 7 MVA grid emulator for testing of a 2 MVA photo‐voltaic converter and a 2 MVA Type 3 wind turbine. This way, the test challenges, specifications, and recommendations are presented using the MW‐scale experiments on different REGs. Furthermore, the effects of sequence couplings and initial emissions on the calculation results are investigated and compared. The proposed methodology is applicable for harmonic model validation as well as empirical modelling.
- Open Access
Offshore Wind Farm Black Start Service Integration: Review and Outlook of Ongoing Research
A review of the ongoing research on black start (BS) service integrated with offshore wind farms (OWFs) is presented in this paper. The overall goal is to firstly gain a better understanding of the BS capabilities required by modern power systems. Subsequently, the challenges faced by OWFs as novel BS service providers as well as an outlook on the ongoing research which may provide solutions to these are presented. OWFs have the potential to be a fast and environmentally friendly technology to provide BS services for power system restoration and, therefore, to ensure resiliency after blackouts. As a power electronic-based system, OWFs can be equipped with a self-starter in the system in order to perform BS. The self-start unit could be a synchronous generator (SG) or a power electronic unit such as a grid-forming (GFM) converter. Preliminary BS studies performed in PSCAD/EMTDC are presented in a simplified OWF system via an SG as the self-start unit. Consequently, technical challenges during the BS procedure in an OWF benchmark system are outlined via theoretical discussions and simulations results. This is useful to understand the threats to power electronics during BS. Finally, the most relevant GFM strategies in the state-of-the-art literature are presented and their application to OWF BS is discussed.
Open AccessOffshore Wind Farm Black Start Service Integration: Review and Outlook of Ongoing Research
A review of the ongoing research on black start (BS) service integrated with offshore wind farms (OWFs) is presented in this paper. The overall goal is to firstly gain a better understanding of the BS capabilities required by modern power systems. Subsequently, the challenges faced by OWFs as novel BS service providers as well as an outlook on the ongoing research which may provide solutions to these are presented. OWFs have the potential to be a fast and environmentally friendly technology to provide BS services for power system restoration and, therefore, to ensure resiliency after blackouts. As a power electronic-based system, OWFs can be equipped with a self-starter in the system in order to perform BS. The self-start unit could be a synchronous generator (SG) or a power electronic unit such as a grid-forming (GFM) converter. Preliminary BS studies performed in PSCAD/EMTDC are presented in a simplified OWF system via an SG as the self-start unit. Consequently, technical challenges during the BS procedure in an OWF benchmark system are outlined via theoretical discussions and simulations results. This is useful to understand the threats to power electronics during BS. Finally, the most relevant GFM strategies in the state-of-the-art literature are presented and their application to OWF BS is discussed.