Alexandros Y. Hadjicostas
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Research Interests
Alexandros Y. Hadjicostas has a total of 10 co-authors. Here are the top co-authors by number of shared publications:
- Georgios D. Peppas
School of Electrical and Computer Engineering, Technical University of Crete, Chania, Greece
7 shared publications - Thomas E. Tsovilis
High Voltage Laboratory, School of Electrical & Computer Engineering, Aristotle University of Thessaloniki, Thessaloniki, Greece
7 shared publications - Evangelos Theocharis Staikos
High Voltage Laboratory, School of Electrical and Computer Engineering, Aristotle University of Thessaloniki, Thessaloniki, Greece
4 shared publications - Zacharias G. Datsios
High Voltage Laboratory, School of Electrical and Computer Engineering, Aristotle University of Thessaloniki, Thessaloniki, Greece
3 shared publications Zafiris Politis
2 shared publications- Andreas. I. Chrysochos
R&D Department of Cablel, Hellenic Cables S.A., Viohalco Group, Sousaki Korinthias, Korinthos Greece
1 shared publication
Latest Publications
- Open Access
- 7 May 2026
- Published by Elsevier in Electric Power Systems Research
- Vol. 259
Residential EV charging stations: Surge protection against direct lightning strikes
- 7 May 2026
- Published by Elsevier in Electric Power Systems Research
- Vol. 259
Open AccessResidential EV charging stations: Surge protection against direct lightning strikes
- Open Access
- 26 June 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 61 (6) , 8832-8842
Dimensioning of Sheath Voltage Limiters for Single- Core Power Cables Connecting an Overhead Transmission Line to a 150 kV Substation
This case study evaluates the stresses of sheath voltage limiters installed at the open end of single-point bonding systems employed for two single-core power cable circuits (lengths: 120 m and 50 m). These cable circuits connect one circuit of a 150 kV double-circuit overhead transmission line to a 150/33 kV substation. Detailed simulations are performed using the ATP-EMTP software for four main scenarios: (i) steady-state operating conditions, (ii) single-phase and three-phase short circuits, (iii) lightning strikes to towers, and (iv) shielding failures at the incoming 150 kV overhead line. For the lightning-related scenarios (iii and iv), the residual voltage and the surge current through the sheath voltage limiters are computed, considering the effects of the instantaneous value of the AC operating voltage, the time to half value, and the amplitude of the lightning return-stroke current. Stress on the sheath voltage limiters is analyzed in terms of charge transfer and specific energy obtained through simulations. Finally, the minimum required characteristics of the sheath voltage limiters are determined and discussed in the context of appropriate dimensioning in engineering applications.
- 26 June 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 61 (6) , 8832-8842
Open AccessDimensioning of Sheath Voltage Limiters for Single- Core Power Cables Connecting an Overhead Transmission Line to a 150 kV Substation
This case study evaluates the stresses of sheath voltage limiters installed at the open end of single-point bonding systems employed for two single-core power cable circuits (lengths: 120 m and 50 m). These cable circuits connect one circuit of a 150 kV double-circuit overhead transmission line to a 150/33 kV substation. Detailed simulations are performed using the ATP-EMTP software for four main scenarios: (i) steady-state operating conditions, (ii) single-phase and three-phase short circuits, (iii) lightning strikes to towers, and (iv) shielding failures at the incoming 150 kV overhead line. For the lightning-related scenarios (iii and iv), the residual voltage and the surge current through the sheath voltage limiters are computed, considering the effects of the instantaneous value of the AC operating voltage, the time to half value, and the amplitude of the lightning return-stroke current. Stress on the sheath voltage limiters is analyzed in terms of charge transfer and specific energy obtained through simulations. Finally, the minimum required characteristics of the sheath voltage limiters are determined and discussed in the context of appropriate dimensioning in engineering applications.
- Open Access
- 17 April 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 74 (00189456) , 1-11
Determination of Parasitic Inductance of Surge Protective Devices
This work investigates the effectiveness of various state-of-the-art techniques for determining the parasitic inductance of surge protective devices across a wide frequency range. This is critical, as the intrinsic inductive characteristics of surge protective devices influence their maximum residual voltage, which directly affects their protection efficiency against fast-front transients with high current derivatives. To provide an innovative solution to the problem of parasitic inductance determination, the parasitic inductance of single-phase and three-phase DIN rail surge protective devices is estimated by replacing the voltage-limiting components with copper blocks. Three methods are employed to estimate the parasitic inductance: (i) Impedance spectroscopy measurements, (ii) impulse current tests, and (iii) finite element analysis simulations. The results are analyzed to evaluate the accuracy of the proposed methods and address key challenges encountered in determining the parasitic inductance. It is found that the parasitic inductance of the protection mode exhibiting the longer surge current path is up to 1.6 times greater than that of the shortest surge current path for the three-phase (3+1) surge protective device, and consequently the maximum residual voltage increases by ~10% when subjected to its nominal discharge current of 20 kA with an 8/20 μs waveform for the same protection modes.
- 17 April 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 74 (00189456) , 1-11
Open AccessDetermination of Parasitic Inductance of Surge Protective Devices
This work investigates the effectiveness of various state-of-the-art techniques for determining the parasitic inductance of surge protective devices across a wide frequency range. This is critical, as the intrinsic inductive characteristics of surge protective devices influence their maximum residual voltage, which directly affects their protection efficiency against fast-front transients with high current derivatives. To provide an innovative solution to the problem of parasitic inductance determination, the parasitic inductance of single-phase and three-phase DIN rail surge protective devices is estimated by replacing the voltage-limiting components with copper blocks. Three methods are employed to estimate the parasitic inductance: (i) Impedance spectroscopy measurements, (ii) impulse current tests, and (iii) finite element analysis simulations. The results are analyzed to evaluate the accuracy of the proposed methods and address key challenges encountered in determining the parasitic inductance. It is found that the parasitic inductance of the protection mode exhibiting the longer surge current path is up to 1.6 times greater than that of the shortest surge current path for the three-phase (3+1) surge protective device, and consequently the maximum residual voltage increases by ~10% when subjected to its nominal discharge current of 20 kA with an 8/20 μs waveform for the same protection modes.
- Open Access
- 3 January 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 61 (2) , 2324-2335
Surge Protection of Charging Stations Against Impinging Overvoltages Due to Lightning Strikes to Incoming Medium Voltage Overhead Line
A typical 1 MVA charging station for electric cars connected to the overhead distribution system through underground medium voltage cables is modeled in the ATP-EMTP environment. Fast-front overvoltages impinging on the AC and DC sides of charging station equipment due to a wide range of lightning strikes to the incoming overhead medium voltage line are computed; positive and negative recorded lightning stroke currents are also considered. The risk of failure is evaluated by considering the rated impulse withstand voltage level of the charging station equipment by assessing the effects of lightning polarity, peak current, and soil resistivity. A protection scheme involving the installation of surge protective devices is investigated to diminish the risk of failure of equipment and interconnected charging cars. The energy absorption capability of surge protective devices against remote lightning strikes is assessed and the necessity of integrating surge protective devices to electric vehicles offering dedicated surge protection is discussed.
- 3 January 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 61 (2) , 2324-2335
Open AccessSurge Protection of Charging Stations Against Impinging Overvoltages Due to Lightning Strikes to Incoming Medium Voltage Overhead Line
A typical 1 MVA charging station for electric cars connected to the overhead distribution system through underground medium voltage cables is modeled in the ATP-EMTP environment. Fast-front overvoltages impinging on the AC and DC sides of charging station equipment due to a wide range of lightning strikes to the incoming overhead medium voltage line are computed; positive and negative recorded lightning stroke currents are also considered. The risk of failure is evaluated by considering the rated impulse withstand voltage level of the charging station equipment by assessing the effects of lightning polarity, peak current, and soil resistivity. A protection scheme involving the installation of surge protective devices is investigated to diminish the risk of failure of equipment and interconnected charging cars. The energy absorption capability of surge protective devices against remote lightning strikes is assessed and the necessity of integrating surge protective devices to electric vehicles offering dedicated surge protection is discussed.
- 3 September 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 60 (6) , 8362-8370
Surge Current Withstand Capability of Natural Ester Oil: A Comparison to Gas-to-Liquid Transformer Oil
The basic electrical characteristics of a natural ester oil are experimentally investigated and compared to gas-to-liquid transformer oil with emphasis given to the endurance against surge events. An accelerated degradation test is conducted using a sequence of current impulses generated through a combination wave generator. This test is employed to investigate changes in the electrical conductivity of the oil, serving as a crucial performance indicator for assessing its surge current withstand capability. Experimental results on the surge degradation of the natural ester oil are compared to those of gas-to-liquid oil, which is commonly used in power transformers. A discussion is made on the possible use of natural ester oils as a liquid matrix for environmentally friendly surge-proof nanofluids to substitute transformer oils, which are commonly employed as insulating liquids and coolants in the power industry.
- 3 September 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 60 (6) , 8362-8370
Surge Current Withstand Capability of Natural Ester Oil: A Comparison to Gas-to-Liquid Transformer Oil
The basic electrical characteristics of a natural ester oil are experimentally investigated and compared to gas-to-liquid transformer oil with emphasis given to the endurance against surge events. An accelerated degradation test is conducted using a sequence of current impulses generated through a combination wave generator. This test is employed to investigate changes in the electrical conductivity of the oil, serving as a crucial performance indicator for assessing its surge current withstand capability. Experimental results on the surge degradation of the natural ester oil are compared to those of gas-to-liquid oil, which is commonly used in power transformers. A discussion is made on the possible use of natural ester oils as a liquid matrix for environmentally friendly surge-proof nanofluids to substitute transformer oils, which are commonly employed as insulating liquids and coolants in the power industry.
- Open Access
- 7 September 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 60 (1) , 1645-1655
An Experimental Methodology for Modeling Surge Protective Devices: An Application to DC SPDs for Electric Vehicle Charging Stations
This work introduces an experimental methodology for time-domain modeling of low-voltage surge protective devices (SPDs), accounting for their sparkover performance as well as their resistive, inductive, and capacitive behavior. The modeling procedure is demonstrated through an application to a combination type SPD connected to the DC side of electric vehicle charging stations. An equivalent circuit model is developed based on experimental records acquired from applied voltages and currents of a wide frequency range and energy content. The developed lumped-circuit model yields results in very good agreement with experimental data regarding sparkover voltage, residual voltage, and energy absorption of SPDs, as illustrated through ATP-EMTP simulations. The proposed methodology can be an effective tool for surge protection and insulation coordination studies.
- 7 September 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 60 (1) , 1645-1655
Open AccessAn Experimental Methodology for Modeling Surge Protective Devices: An Application to DC SPDs for Electric Vehicle Charging Stations
This work introduces an experimental methodology for time-domain modeling of low-voltage surge protective devices (SPDs), accounting for their sparkover performance as well as their resistive, inductive, and capacitive behavior. The modeling procedure is demonstrated through an application to a combination type SPD connected to the DC side of electric vehicle charging stations. An equivalent circuit model is developed based on experimental records acquired from applied voltages and currents of a wide frequency range and energy content. The developed lumped-circuit model yields results in very good agreement with experimental data regarding sparkover voltage, residual voltage, and energy absorption of SPDs, as illustrated through ATP-EMTP simulations. The proposed methodology can be an effective tool for surge protection and insulation coordination studies.
- Open Access
- 1 August 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Vehicular Technology
- Vol. 73 (1) , 450-462
Coordination of Varistors With Transient Voltage Suppression Diodes in Automotive DC Systems
The coordination of metal-oxide varistors with transient voltage suppression diodes commonly employed for the protection of sensitive electronic equipment in DC automotive systems is experimentally investigated. Double-exponential impulse currents adopted in relevant standards, concave and rectangular impulse currents resembling field records on lightning-related surge events, as well as temporary overvoltages, are employed to stress the surge protective components and evaluate their coordination. Experimental results and the subsequent analysis reveal that effective coordination of varistors with bidirectional diodes can be a challenging task, especially under long-duration and high-energy electromagnetic pulses. Under such conditions, the safety and uninterrupted operation of vehicles containing low-voltage electrical circuits with embedded sensitive electronic equipment is threatened.
- 1 August 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Vehicular Technology
- Vol. 73 (1) , 450-462
Open AccessCoordination of Varistors With Transient Voltage Suppression Diodes in Automotive DC Systems
The coordination of metal-oxide varistors with transient voltage suppression diodes commonly employed for the protection of sensitive electronic equipment in DC automotive systems is experimentally investigated. Double-exponential impulse currents adopted in relevant standards, concave and rectangular impulse currents resembling field records on lightning-related surge events, as well as temporary overvoltages, are employed to stress the surge protective components and evaluate their coordination. Experimental results and the subsequent analysis reveal that effective coordination of varistors with bidirectional diodes can be a challenging task, especially under long-duration and high-energy electromagnetic pulses. Under such conditions, the safety and uninterrupted operation of vehicles containing low-voltage electrical circuits with embedded sensitive electronic equipment is threatened.