Tianyi Xu
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Tianyi Xu has a total of 4 co-authors. Here are the top co-authors by number of shared publications:
- Georgios Konstantinou
UNSW Sydney
4 shared publications - Shan Jiang
School of Electrical Engineering and Telecommunications, UNSW Sydney, Sydney, NSW, Australia
4 shared publications - Ye Zhu
School of Information Science and Technology, ShanghaiTech University, Shanghai, China
3 shared publications - Xiongfei Wang
Tsinghua University
1 shared publication
Latest Publications
- 10 September 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 41 (1) , 214-220
Current Saturation Ratio-Based Hybrid Synchronization Control of Grid-Forming Converters
Grid-forming (GFM) converters utilizing hybrid synchronization control (HSC) incorporate both power-synchronization loop (PSL)- and phase-locked loop (PLL)-based frequency components in the synchronization loop. However, existing implementations of HSC do not consider the physical current limits of GFM converters, are designed to only cater to specific types of grid disturbances, and exhibit inaccurate power setpoint tracking. In this letter, a current limit-informed HSC method is proposed to overcome these issues. The PSL and PLL components are weighted according to the current saturation ratio of the current limiter, as a proxy measure for the severity of a disturbance. In this way, the proposed method not only synergizes with current limiting control of GFM converters, but also works generally for any disturbance, which activates the current limiter. In addition, it tracks the active power setpoint accurately during unfaulted steady states, which also implies that a larger proportional gain can be used in the PLL, improving the design flexibility and dynamic performance. Experimental results demonstrate the enhanced performance of the proposed method over the PSL and existing HSC methods during grid frequency drops and voltage sags. The stability of the proposed method under weak grid conditions is also experimentally verified.
- 10 September 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 41 (1) , 214-220
Current Saturation Ratio-Based Hybrid Synchronization Control of Grid-Forming Converters
Grid-forming (GFM) converters utilizing hybrid synchronization control (HSC) incorporate both power-synchronization loop (PSL)- and phase-locked loop (PLL)-based frequency components in the synchronization loop. However, existing implementations of HSC do not consider the physical current limits of GFM converters, are designed to only cater to specific types of grid disturbances, and exhibit inaccurate power setpoint tracking. In this letter, a current limit-informed HSC method is proposed to overcome these issues. The PSL and PLL components are weighted according to the current saturation ratio of the current limiter, as a proxy measure for the severity of a disturbance. In this way, the proposed method not only synergizes with current limiting control of GFM converters, but also works generally for any disturbance, which activates the current limiter. In addition, it tracks the active power setpoint accurately during unfaulted steady states, which also implies that a larger proportional gain can be used in the PLL, improving the design flexibility and dynamic performance. Experimental results demonstrate the enhanced performance of the proposed method over the PSL and existing HSC methods during grid frequency drops and voltage sags. The stability of the proposed method under weak grid conditions is also experimentally verified.
- 14 February 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 40 (7) , 8886-8898
Frequency Domain Inertia Design of Grid-Forming Converters
Synthetic inertia plays a pivotal role in the frequency response of grid-forming (GFM) converters. A small inertia factor provides insufficient inertia power to resist frequency variations during grid contingencies. By contrast, a large inertia factor allows GFM converters to mimic the dynamic response of synchronous generators but could compromise grid synchronization during extreme frequency events, e.g., frequency disturbances from 47 to 52 Hz or phase jumps up to $60^\circ$. This happens when a current-limiting GFM converter fails to track a output power reference governed by the power synchronization loop (PSL). Unlike conventional inertia designs that use fixed inertia factors, this article proposes a frequency domain inertia design method for GFM converters based on a modified bandwise PSL. The equivalent inertia factor of GFM converters can be defined as a transfer function by leveraging the equivalence between the high-frequency droop power component and the low-frequency inertia power component, such that the inertia factor is frequency-dependent and varies across different frequency ranges. The proposed inertia design solution combines the advantages of conventional low- and high-inertia design, providing large inertia factor in low-frequency range to mitigate frequency disturbances and small inertia factor in high-frequency range to facilitate power and frequency recovery. The dynamic response of GFM converters adopting the proposed design is experimentally verified and also demonstrated in an accompanied video file under different scenarios including network transients, such as grid phase jumps, grid voltage sags and frequency excursions, as well as operational events of power step change and load reduction.
- 14 February 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 40 (7) , 8886-8898
Frequency Domain Inertia Design of Grid-Forming Converters
Synthetic inertia plays a pivotal role in the frequency response of grid-forming (GFM) converters. A small inertia factor provides insufficient inertia power to resist frequency variations during grid contingencies. By contrast, a large inertia factor allows GFM converters to mimic the dynamic response of synchronous generators but could compromise grid synchronization during extreme frequency events, e.g., frequency disturbances from 47 to 52 Hz or phase jumps up to $60^\circ$. This happens when a current-limiting GFM converter fails to track a output power reference governed by the power synchronization loop (PSL). Unlike conventional inertia designs that use fixed inertia factors, this article proposes a frequency domain inertia design method for GFM converters based on a modified bandwise PSL. The equivalent inertia factor of GFM converters can be defined as a transfer function by leveraging the equivalence between the high-frequency droop power component and the low-frequency inertia power component, such that the inertia factor is frequency-dependent and varies across different frequency ranges. The proposed inertia design solution combines the advantages of conventional low- and high-inertia design, providing large inertia factor in low-frequency range to mitigate frequency disturbances and small inertia factor in high-frequency range to facilitate power and frequency recovery. The dynamic response of GFM converters adopting the proposed design is experimentally verified and also demonstrated in an accompanied video file under different scenarios including network transients, such as grid phase jumps, grid voltage sags and frequency excursions, as well as operational events of power step change and load reduction.
- 9 December 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 40 (4) , 4969-4983
Composite Power-Frequency Synchronization Loop for Enhanced Frequency Response Considering Current and Power Limits of Grid-Forming Converters
Grid-forming (GFM) control is a promising solution to provide damping and frequency support services in low-inertia power systems with an increasing share of inverter-based resources. This article investigates the available frequency response services from GFM converters during frequency disturbances, considering the impact of physical limitations of the converter and underlying power source (i.e., current and power ratings). Specifically, current limiters that are used for protection of power semiconductors restrict the achievable output power range of GFM converters and make them susceptible to loss of grid synchronization during large frequency disturbances. The inclusion of power limiters guarantees a stable equilibrium point without exceeding the current limit during disturbances, but negatively impacts frequency stability by reducing the effective damping factor. To address these problems, a composite power-frequency synchronization loop (CPFSL) is proposed as an alternative to the widely adopted power-synchronization loop (PSL). The proposed CPFSL can coordinate with current and power limiters, and enhances the damping factor of GFM converters by incorporating a phase-locked loop-based droop term into the conventional PSL. GFM converters with the CPFSL are capable of providing adaptive frequency response, which fully utilizes the available power headroom of dc-side energy sources, while maintaining grid synchronization during extreme grid events. A comparison with other GFM control methods demonstrates the improved synchronization stability of the CPFSL during severe frequency events. Furthermore, the response of CPFSL-based GFM converters during frequency disturbances, voltage disturbances, and under weak grid and islanded conditions is verified experimentally using a hardware setup of a grid-connected GFM converter.
- 9 December 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 40 (4) , 4969-4983
Composite Power-Frequency Synchronization Loop for Enhanced Frequency Response Considering Current and Power Limits of Grid-Forming Converters
Grid-forming (GFM) control is a promising solution to provide damping and frequency support services in low-inertia power systems with an increasing share of inverter-based resources. This article investigates the available frequency response services from GFM converters during frequency disturbances, considering the impact of physical limitations of the converter and underlying power source (i.e., current and power ratings). Specifically, current limiters that are used for protection of power semiconductors restrict the achievable output power range of GFM converters and make them susceptible to loss of grid synchronization during large frequency disturbances. The inclusion of power limiters guarantees a stable equilibrium point without exceeding the current limit during disturbances, but negatively impacts frequency stability by reducing the effective damping factor. To address these problems, a composite power-frequency synchronization loop (CPFSL) is proposed as an alternative to the widely adopted power-synchronization loop (PSL). The proposed CPFSL can coordinate with current and power limiters, and enhances the damping factor of GFM converters by incorporating a phase-locked loop-based droop term into the conventional PSL. GFM converters with the CPFSL are capable of providing adaptive frequency response, which fully utilizes the available power headroom of dc-side energy sources, while maintaining grid synchronization during extreme grid events. A comparison with other GFM control methods demonstrates the improved synchronization stability of the CPFSL during severe frequency events. Furthermore, the response of CPFSL-based GFM converters during frequency disturbances, voltage disturbances, and under weak grid and islanded conditions is verified experimentally using a hardware setup of a grid-connected GFM converter.
- 5 February 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 39 (5) , 5271-5285
Current-Synchronization Control of Grid-Forming Converters for Fault Current Limiting and Enhanced Synchronization Stability
Grid-forming (GFM) converters with the widely adopted power-synchronization controller (PSC) are exposed to the risk of losing synchronization, due to their limited power transfer capability under severe symmetrical faults. The output of the PSC, i.e., internal angular frequency, is forced to deviate from its reference, leading to an uncontrollable power angle during the fault. Hence, GFM converters become sensitive to fault depth and duration, suffering from long recovery time. This article proposes a current-limiting GFM control that is capable of limiting fault current and maintaining grid synchronization during severe faults. A current-synchronization controller (CSC) is developed to replace the PSC. The proposed CSC works compatibly with a current limiter and behaves as a PSC during normal conditions to provide synthetic inertia and a phase-locked loop during severe faults with enhanced synchronization stability. Based on the developed steady-state model, it shows that GFM converters under the proposed control directly transition to a faulted steady state when a fault occurs and maintain a constant power angle until the fault is cleared. This helps converters to regain the prefault steady state within a shorter recovery period. The proposed method is validated by a comprehensive comparison with existing current-limiting methods, as well as experimental results under different control parameters, power settings, and system strength.
- 5 February 2024
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 39 (5) , 5271-5285
Current-Synchronization Control of Grid-Forming Converters for Fault Current Limiting and Enhanced Synchronization Stability
Grid-forming (GFM) converters with the widely adopted power-synchronization controller (PSC) are exposed to the risk of losing synchronization, due to their limited power transfer capability under severe symmetrical faults. The output of the PSC, i.e., internal angular frequency, is forced to deviate from its reference, leading to an uncontrollable power angle during the fault. Hence, GFM converters become sensitive to fault depth and duration, suffering from long recovery time. This article proposes a current-limiting GFM control that is capable of limiting fault current and maintaining grid synchronization during severe faults. A current-synchronization controller (CSC) is developed to replace the PSC. The proposed CSC works compatibly with a current limiter and behaves as a PSC during normal conditions to provide synthetic inertia and a phase-locked loop during severe faults with enhanced synchronization stability. Based on the developed steady-state model, it shows that GFM converters under the proposed control directly transition to a faulted steady state when a fault occurs and maintain a constant power angle until the fault is cleared. This helps converters to regain the prefault steady state within a shorter recovery period. The proposed method is validated by a comprehensive comparison with existing current-limiting methods, as well as experimental results under different control parameters, power settings, and system strength.