Iulian-Cristian Ene
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Iulian-Cristian Ene has a total of 8 co-authors. Here are the top co-authors by number of shared publications:
- Vlad Iordache
CAMBI Research Center, Doctoral School, Faculty of Building Services Engineering, Technical University of Civil Engineering of Bucharest, 020396 Bucharest, Romania
6 shared publications - Ion Anghel
Fire Officers Faculty, Police Academy, 022451 Bucharest, Romania
4 shared publications - Dan-Adrian Ionescu
CAMBI Research Center, Doctoral School, Faculty of Building Services Engineering, Technical University of Civil Engineering of Bucharest, 020396 Bucharest, Romania
3 shared publications - Florin Bode
AtFlow Research Centre, Mechanical Engineering Department, Technical University of Cluj-Napoca, 400641 Cluj-Napoca, Romania
2 shared publications - Ilinca Nastase
Building Services Faculty, Technical University of Civil Engineering Bucharest, 020396 Bucharest, Romania
1 shared publication - Ion Anghel
Fire Officers Faculty, Police Academy, 022451 Bucharest, Romania
1 shared publication
Latest Publications
- Open Access
Influence of Fire Source Elevation on Positive Pressure Ventilation Effectiveness in Multi-Story Building Stairwells
This work presents an evaluation of the effectiveness of active ventilation methods compared to passive ventilation methods in a typical B + GF + 9 building, focusing on the impact of burner height location on smoke control performance. The numerical model was validated using a full-scale room fire experiment involving a 4350 kJ/s wood crib load, where the HRR was calibrated via the mass loss method, achieving an RMSE of 210 kW and MRE of 5.04%. FDS simulations were conducted across six scenarios involving burners on the ground, fifth, and ninth floors. The findings demonstrate that, while natural ventilation allows the stairwell to reach lethal conditions with temperatures exceeding 180 °C and CO concentrations above 0.24%, the implementation of top-level mechanical pressurization maintains temperatures below the 60 °C tenability threshold. The mechanical ventilation system extended the Available Safe Egress Time (ASET) by 75% to 110%, with effectiveness increasing as the burner elevation approached the fan location. Overall, the study provides a validated approach for transforming stairwells into protected refuge zones in existing mid-rise buildings. Overall, merging empirical with computational methods is a proven basis for simulating scaled-up, complicated layouts. This guarantees accurate initial conditions when analyzing urban fire emergencies.
Open AccessInfluence of Fire Source Elevation on Positive Pressure Ventilation Effectiveness in Multi-Story Building Stairwells
This work presents an evaluation of the effectiveness of active ventilation methods compared to passive ventilation methods in a typical B + GF + 9 building, focusing on the impact of burner height location on smoke control performance. The numerical model was validated using a full-scale room fire experiment involving a 4350 kJ/s wood crib load, where the HRR was calibrated via the mass loss method, achieving an RMSE of 210 kW and MRE of 5.04%. FDS simulations were conducted across six scenarios involving burners on the ground, fifth, and ninth floors. The findings demonstrate that, while natural ventilation allows the stairwell to reach lethal conditions with temperatures exceeding 180 °C and CO concentrations above 0.24%, the implementation of top-level mechanical pressurization maintains temperatures below the 60 °C tenability threshold. The mechanical ventilation system extended the Available Safe Egress Time (ASET) by 75% to 110%, with effectiveness increasing as the burner elevation approached the fan location. Overall, the study provides a validated approach for transforming stairwells into protected refuge zones in existing mid-rise buildings. Overall, merging empirical with computational methods is a proven basis for simulating scaled-up, complicated layouts. This guarantees accurate initial conditions when analyzing urban fire emergencies.
- Open Access
Impact of Fire Source Locations and Ventilation Strategies on Indoor Environments: An FDS Simulation Study
This paper analyzes smoke control strategies in high-rise building stairwells, with particular focus on their application to existing buildings without smoke exhaust openings at the top of the stairwell. This study is necessary to support the optimization of fire safety in a wide range of existing high-rise buildings in Bucharest, Romania, where stairwells operate without upper smoke vents. The scientific challenge addressed is the comparative evaluation of natural ventilation and mechanical pressurization applied at the lower part of the stairwell in order to assess their influence on smoke and heat propagation. The motivation of this work is related to emergency response, as firefighters require a clear understanding of smoke movement and evacuation conditions depending on the fire location and ventilation mode. Three-dimensional CFD simulations were performed, using a fire source validated against experimental data, to analyze temperature, pressure, airflow velocity, visibility, and toxic gas concentration for different fire-floor locations. The results show that natural ventilation alone is ineffective, while single-point mechanical pressurization improves conditions only during the early fire stage. The findings contribute to better-informed firefighter decision-making by clarifying stairwell conditions during intervention in existing high-rise buildings.
Open AccessImpact of Fire Source Locations and Ventilation Strategies on Indoor Environments: An FDS Simulation Study
This paper analyzes smoke control strategies in high-rise building stairwells, with particular focus on their application to existing buildings without smoke exhaust openings at the top of the stairwell. This study is necessary to support the optimization of fire safety in a wide range of existing high-rise buildings in Bucharest, Romania, where stairwells operate without upper smoke vents. The scientific challenge addressed is the comparative evaluation of natural ventilation and mechanical pressurization applied at the lower part of the stairwell in order to assess their influence on smoke and heat propagation. The motivation of this work is related to emergency response, as firefighters require a clear understanding of smoke movement and evacuation conditions depending on the fire location and ventilation mode. Three-dimensional CFD simulations were performed, using a fire source validated against experimental data, to analyze temperature, pressure, airflow velocity, visibility, and toxic gas concentration for different fire-floor locations. The results show that natural ventilation alone is ineffective, while single-point mechanical pressurization improves conditions only during the early fire stage. The findings contribute to better-informed firefighter decision-making by clarifying stairwell conditions during intervention in existing high-rise buildings.
- Open Access
Full-Scale Experimental Stand Development with HRR Determination from Mass Loss and CFD Model Validation
Accurate prediction of urban air quality during fire events is frequently limited by the lack of experimentally validated source terms. Current pollution dispersion models often rely on idealized input parameters that fail to capture the complex thermal and chemical dynamics of real-world indoor fires. Addressing this gap, this study presents an experiment which reproduces an office-type fire using a wooden crib with a calibrated thermal load, enabling accurate determination of the HRR through the mass loss rate method. Temperature evolution was monitored with 27 thermocouples positioned across five vertical planes, while toxic gas concentrations were measured near the upper boundary of the exterior opening. The experimental data were used to calibrate and validate the numerical model, with HRR representing the primary parameter and temperature and toxic gas concentrations serving secondary validation metrics. Quantitative comparison showed good agreement between the experimental and simulated trends, with acceptable prediction errors and consistent reproduction of the dominant physical mechanisms governing fire development, ventilation-driven flow, and pollutant accumulation. Overall, the combined experimental–numerical approach provides a validated framework for future simulations on larger and more complex geometries, ensuring reliable input parameters for urban-scale fire scenarios.
Open AccessFull-Scale Experimental Stand Development with HRR Determination from Mass Loss and CFD Model Validation
Accurate prediction of urban air quality during fire events is frequently limited by the lack of experimentally validated source terms. Current pollution dispersion models often rely on idealized input parameters that fail to capture the complex thermal and chemical dynamics of real-world indoor fires. Addressing this gap, this study presents an experiment which reproduces an office-type fire using a wooden crib with a calibrated thermal load, enabling accurate determination of the HRR through the mass loss rate method. Temperature evolution was monitored with 27 thermocouples positioned across five vertical planes, while toxic gas concentrations were measured near the upper boundary of the exterior opening. The experimental data were used to calibrate and validate the numerical model, with HRR representing the primary parameter and temperature and toxic gas concentrations serving secondary validation metrics. Quantitative comparison showed good agreement between the experimental and simulated trends, with acceptable prediction errors and consistent reproduction of the dominant physical mechanisms governing fire development, ventilation-driven flow, and pollutant accumulation. Overall, the combined experimental–numerical approach provides a validated framework for future simulations on larger and more complex geometries, ensuring reliable input parameters for urban-scale fire scenarios.
- Open Access
- 19 June 2025
- Published by MDPI AG in Applied Sciences
- Vol. 15 (12) , 6934
Efficiency of Positive Pressure Ventilation Compared to Organized Natural Ventilation in Fire Scenarios of a Multi-Story Building
This paper presents a detailed analysis of the dynamics of indoor environmental parameters under three simulated fire scenarios in a multi-story building, using the PyroSim platform (based on the Fire Dynamics Simulator—FDS). The study compares two smoke control strategies, organized natural ventilation (a passive system) and mechanical pressurization (an active system), evaluating their influence on temperature, differential pressure, air velocity, heat release rate (HRR), and toxic gas distribution. The simulations revealed that passive systems, relying on the stack effect and vertical natural ventilation, do not ensure the effective control of smoke infiltration into evacuation routes, allowing significant heat accumulation and reduced visibility. The results highlight the superior effectiveness of unidirectional mechanical pressurization in maintaining a stable flow regime, functional visibility, and a safe evacuation environment. A key finding is the transition from static pressure control to velocity-based flow control at the moment of door opening toward the fire source. The results confirm that a dynamically adapted application of mechanical pressurization—synchronized with the opening of access pathways—not only reinforces existing principles for protecting egress routes, but also provides a precise operational approach for optimizing emergency responses in high-rise buildings.
- 19 June 2025
- Published by MDPI AG in Applied Sciences
- Vol. 15 (12) , 6934
Open AccessEfficiency of Positive Pressure Ventilation Compared to Organized Natural Ventilation in Fire Scenarios of a Multi-Story Building
This paper presents a detailed analysis of the dynamics of indoor environmental parameters under three simulated fire scenarios in a multi-story building, using the PyroSim platform (based on the Fire Dynamics Simulator—FDS). The study compares two smoke control strategies, organized natural ventilation (a passive system) and mechanical pressurization (an active system), evaluating their influence on temperature, differential pressure, air velocity, heat release rate (HRR), and toxic gas distribution. The simulations revealed that passive systems, relying on the stack effect and vertical natural ventilation, do not ensure the effective control of smoke infiltration into evacuation routes, allowing significant heat accumulation and reduced visibility. The results highlight the superior effectiveness of unidirectional mechanical pressurization in maintaining a stable flow regime, functional visibility, and a safe evacuation environment. A key finding is the transition from static pressure control to velocity-based flow control at the moment of door opening toward the fire source. The results confirm that a dynamically adapted application of mechanical pressurization—synchronized with the opening of access pathways—not only reinforces existing principles for protecting egress routes, but also provides a precise operational approach for optimizing emergency responses in high-rise buildings.
- Open Access
- 19 June 2025
- Published by MDPI AG in Applied Sciences
- Vol. 15 (12) , 6909
HRR-Based Calibration of an FDS Model for Office Fire Simulations Using Full-Scale Wood Crib Experiments
This study deals with the simulation of office fires by combining large-scale experiments with nine wooden cribs and a carefully calibrated computer model. It shows how real fire conditions, reaching up to 800–1000 °C, could be reproduced experimentally. The numerical model was validated by comparing HRR and temperature data with real measurements. Accuracy was assessed using error metrics to ensure that the simulation closely approximates real fire behavior. The method of determining HRR through mass loss has been used in prior studies, but those typically involved small-scale setups and limited fire loads. Unlike most approaches in the field, this research is based on a full-scale experiment involving nine wooden cribs, offering superior realism and thermal intensity. The experimental data—temperature evolution, HRR, and observed destructive effects—were used to calibrate the FDS model. The strength of the study lies in the repeatability and accuracy of the simulation, its practical relevance, and its potential to improve fire safety evaluations for office spaces.
- 19 June 2025
- Published by MDPI AG in Applied Sciences
- Vol. 15 (12) , 6909
Open AccessHRR-Based Calibration of an FDS Model for Office Fire Simulations Using Full-Scale Wood Crib Experiments
This study deals with the simulation of office fires by combining large-scale experiments with nine wooden cribs and a carefully calibrated computer model. It shows how real fire conditions, reaching up to 800–1000 °C, could be reproduced experimentally. The numerical model was validated by comparing HRR and temperature data with real measurements. Accuracy was assessed using error metrics to ensure that the simulation closely approximates real fire behavior. The method of determining HRR through mass loss has been used in prior studies, but those typically involved small-scale setups and limited fire loads. Unlike most approaches in the field, this research is based on a full-scale experiment involving nine wooden cribs, offering superior realism and thermal intensity. The experimental data—temperature evolution, HRR, and observed destructive effects—were used to calibrate the FDS model. The strength of the study lies in the repeatability and accuracy of the simulation, its practical relevance, and its potential to improve fire safety evaluations for office spaces.
- Open Access
- 13 December 2024
- Published by MDPI AG in Applied Sciences
- Vol. 14 (24) , 11659
The Impact of an Office Fire Combined with the Stack Effect in a Multi-Story Building
The current study was based on two simulations conducted in FDS that examined the influences of an office fire on the ground floor of a 10-story building (with 9 above-ground floors) and its impact on air and smoke flow. After reviewing the literature, we observe a significant gap in current research addressing the dynamic interdependence between fire development and the stack effect in multi-story residential buildings. It was found that the fire significantly intensified the stack effect, increasing the temperature in the stairwell, particularly on the ground floor. Gas velocities within the building increased but do not endanger the lives of the occupants. Visibility remained sufficient for evacuation from the apartments, except in critical areas such as the fire-affected apartment and the stairwell. Lethal concentrations of CO and CO2 were rapidly reached, severely impairing evacuation capability within the fire-affected apartment and the stairwell. Natural ventilation proved insufficient for controlling smoke and toxic gasses, highlighting the need for additional sealing measures and forced ventilation.
- 13 December 2024
- Published by MDPI AG in Applied Sciences
- Vol. 14 (24) , 11659
Open AccessThe Impact of an Office Fire Combined with the Stack Effect in a Multi-Story Building
The current study was based on two simulations conducted in FDS that examined the influences of an office fire on the ground floor of a 10-story building (with 9 above-ground floors) and its impact on air and smoke flow. After reviewing the literature, we observe a significant gap in current research addressing the dynamic interdependence between fire development and the stack effect in multi-story residential buildings. It was found that the fire significantly intensified the stack effect, increasing the temperature in the stairwell, particularly on the ground floor. Gas velocities within the building increased but do not endanger the lives of the occupants. Visibility remained sufficient for evacuation from the apartments, except in critical areas such as the fire-affected apartment and the stairwell. Lethal concentrations of CO and CO2 were rapidly reached, severely impairing evacuation capability within the fire-affected apartment and the stairwell. Natural ventilation proved insufficient for controlling smoke and toxic gasses, highlighting the need for additional sealing measures and forced ventilation.