Vitaliy Vevenko
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Vitaliy Vevenko has a total of 7 co-authors. Here are the top co-authors by number of shared publications:
- Borys Gorkunov
National Technical University “Kharkiv Polytechnic Institute
2 shared publications - Serhii Lvov
National Technical University “Kharkiv Polytechnic Institute
2 shared publications - Anna Tyshchenko
National Technical University “Kharkiv Polytechnic Institute
1 shared publication - Denys G. Koliushko
Національний технічний університет «Харківський політехнічний інститут», м. Харків, Україна
1 shared publication - Serhii S. Rudenko
Національний технічний університет «Харківський політехнічний інститут», м. Харків, Україна
1 shared publication - Shaiban Tamer
Africell Angola
1 shared publication
Latest Publications
- Open Access
- 23 December 2025
- Published by Private Company Technology Center in Eastern-European Journal of Enterprise Technologies
- Vol. 6 (5 (138)) , 16-23
Expanding the functional capabilities of an electromagnetic converter with a spatially periodic magnetic field structure
This study investigates the process of interaction between the non-uniform electromagnetic field of a primary transducer and a metallic cylindrical article in order to obtain multiparametric information. The study tackles the scientific and technical task of expanding the functional capabilities of an electromagnetic transducer by increasing the number of controllable parameters for an article at a single excitation frequency using the same transducer. The method is based on extracting the amplitude and phase of the spatial harmonics of the non-uniform probing field. The advantage of such transducers is in the fact that, while operating at a single fixed excitation frequency, they enable multiparametric inspection of metal articles. The results have practical significance for the instrumentation industry when designing and manufacturing primary transducers with a spatially periodic structure of the excitation magnetic field. This makes it possible to perform contactless monitoring of the electrical, magnetic, and geometric parameters of cylindrical articles of various sizes and types. For a transducer having two poles with currents in opposite directions, at γ = 36° and d/а = 0.5, the influence of the 5th spatial harmonic on the extracted 1st and 3rd harmonics is zero, while the influence of the 7th harmonic on the 1st and 3rd harmonics amounts to 0.36% and 2.7%, respectively. The influence of the 7th harmonic on the 3rd can be reduced to 1% by choosing d/a = 0.4. An algorithm for monitoring three parameters of a cylindrical article has been developed, based on the normalized amplitudes of the 1st and 3rd harmonics and the phase of the 1st harmonic, thereby expanding the functional capabilities of the method. It has been established that the influence of higher spatial harmonics on the measurement results is insignificant, and the total error does not exceed 1.5% without higher harmonics, in contrast to single-frequency methods where the error exceeds 5%
- 23 December 2025
- Published by Private Company Technology Center in Eastern-European Journal of Enterprise Technologies
- Vol. 6 (5 (138)) , 16-23
Open AccessExpanding the functional capabilities of an electromagnetic converter with a spatially periodic magnetic field structure
This study investigates the process of interaction between the non-uniform electromagnetic field of a primary transducer and a metallic cylindrical article in order to obtain multiparametric information. The study tackles the scientific and technical task of expanding the functional capabilities of an electromagnetic transducer by increasing the number of controllable parameters for an article at a single excitation frequency using the same transducer. The method is based on extracting the amplitude and phase of the spatial harmonics of the non-uniform probing field. The advantage of such transducers is in the fact that, while operating at a single fixed excitation frequency, they enable multiparametric inspection of metal articles. The results have practical significance for the instrumentation industry when designing and manufacturing primary transducers with a spatially periodic structure of the excitation magnetic field. This makes it possible to perform contactless monitoring of the electrical, magnetic, and geometric parameters of cylindrical articles of various sizes and types. For a transducer having two poles with currents in opposite directions, at γ = 36° and d/а = 0.5, the influence of the 5th spatial harmonic on the extracted 1st and 3rd harmonics is zero, while the influence of the 7th harmonic on the 1st and 3rd harmonics amounts to 0.36% and 2.7%, respectively. The influence of the 7th harmonic on the 3rd can be reduced to 1% by choosing d/a = 0.4. An algorithm for monitoring three parameters of a cylindrical article has been developed, based on the normalized amplitudes of the 1st and 3rd harmonics and the phase of the 1st harmonic, thereby expanding the functional capabilities of the method. It has been established that the influence of higher spatial harmonics on the measurement results is insignificant, and the total error does not exceed 1.5% without higher harmonics, in contrast to single-frequency methods where the error exceeds 5%
- Open Access
- 2 July 2025
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 4,p. 80-85
Application of the multilayer soil equivalence method in determining the normalized parameters of the grounding system
Introduction. Normalized parameters of the grounding system, such as touch voltage and resistance, are critically important for ensuring electrical safety and reliability of power plants and substations. The complexity of the multi-layered soil structure makes it difficult to determine mentioned parameters. This is due to the fact that real soils on the territory of energy facilities of Ukraine have three or more layers, and the specified parameters are determined by software with two-layer calculation models. Therefore, the need to provide multilayer geoelectric structures into equivalence two-layer models for practical application is an urgent task. Goal. Determination of the application limits of the multilayer soils equivalence method based on the calculating results analysis of the grounding system normalized parameters. Methodology. The study considered a three-layer model for four soil types (A, H, Q, K) common in Ukraine. The calculations were performed using the LiGro software package, which is based on the method of integro-differential equations, applied to the analytical solution of the problem of the electric field potential of a point current source in a three-layer conducting half-space. As a criterion for the possibility of applying the equivalence method, a relative error value of 10 % was chosen when determining the normalized parameters of a grounding system of the given topology and soil type. When determining the error, the calculation results in the original three-layer soil structure for the given topology of the grounding system were taken as the true value. The results show that the effectiveness of equivalent technique significantly depends on the type of soil and the area of the grounding system. In particular, for soil type A, replacing the upper and middle layers with the equivalent first layer (the lower layer with the second) provides a smaller error in the calculations of the grounding resistance than representing the upper layer as the first, and the middle and lower layers as the second equivalent layer. At the same time, there is a tendency for the error to decrease with increasing area of the object: from 225 m2 to 14400 m2, for the first case, the error decreased from –14.6 % to –2.6 %, and for the second case, it changed from –9.3 % to 14.6 %, respectively. Originality. For the first time, the results of the methodical error evaluation of the equivalence techniques of multilayered soils of different types when calculating the normalized parameters of grounding system are presented. Practical value. Determination of the conditions and limits of the use of the equivalence method when calculating the normalized parameters of grounding system by software complexes can be used in the design of new or reconstruction of existing energy facilities of Ukraine. References 20, tables 5, figures 4.
- 2 July 2025
- Published by National Technical University Kharkiv Polytechnic Institute in Electrical Engineering & Electromechanics
- No. 4,p. 80-85
Open AccessApplication of the multilayer soil equivalence method in determining the normalized parameters of the grounding system
Introduction. Normalized parameters of the grounding system, such as touch voltage and resistance, are critically important for ensuring electrical safety and reliability of power plants and substations. The complexity of the multi-layered soil structure makes it difficult to determine mentioned parameters. This is due to the fact that real soils on the territory of energy facilities of Ukraine have three or more layers, and the specified parameters are determined by software with two-layer calculation models. Therefore, the need to provide multilayer geoelectric structures into equivalence two-layer models for practical application is an urgent task. Goal. Determination of the application limits of the multilayer soils equivalence method based on the calculating results analysis of the grounding system normalized parameters. Methodology. The study considered a three-layer model for four soil types (A, H, Q, K) common in Ukraine. The calculations were performed using the LiGro software package, which is based on the method of integro-differential equations, applied to the analytical solution of the problem of the electric field potential of a point current source in a three-layer conducting half-space. As a criterion for the possibility of applying the equivalence method, a relative error value of 10 % was chosen when determining the normalized parameters of a grounding system of the given topology and soil type. When determining the error, the calculation results in the original three-layer soil structure for the given topology of the grounding system were taken as the true value. The results show that the effectiveness of equivalent technique significantly depends on the type of soil and the area of the grounding system. In particular, for soil type A, replacing the upper and middle layers with the equivalent first layer (the lower layer with the second) provides a smaller error in the calculations of the grounding resistance than representing the upper layer as the first, and the middle and lower layers as the second equivalent layer. At the same time, there is a tendency for the error to decrease with increasing area of the object: from 225 m2 to 14400 m2, for the first case, the error decreased from –14.6 % to –2.6 %, and for the second case, it changed from –9.3 % to 14.6 %, respectively. Originality. For the first time, the results of the methodical error evaluation of the equivalence techniques of multilayered soils of different types when calculating the normalized parameters of grounding system are presented. Practical value. Determination of the conditions and limits of the use of the equivalence method when calculating the normalized parameters of grounding system by software complexes can be used in the design of new or reconstruction of existing energy facilities of Ukraine. References 20, tables 5, figures 4.
- 29 November 2024
- Published by Kharkiv National University of Radioelectronics in Metrology and instruments
- No. 1
EXPANSION OF THE FUNCTIONAL CAPABILITIES OF ELECTROMAGNETIC METHODS AND DEVICES FOR CONTROLLING MECHANICAL STRESSES IN CYLINDRICAL METAL PRODUCTS
This study addresses the theoretical foundations and the implementation algorithm of a differential transformer electromagnetic overlay transducer designed for monitoring variations in the electromagnetic parameters of a ferromagnetic shaft subjected to torque. An experimental setup was created, and the transducer's characteristics for amplitude, phase, and variable-frequency control methods were obtained. The obtained dependencies show that using the differential method, magnetic permeability and magnetizing current frequency serve as informative parameters, being the most sensitive to changes in mechanical loads on the cylindrical product. It has been established that such a system has high resolution and expanded functional capabilities.
- 29 November 2024
- Published by Kharkiv National University of Radioelectronics in Metrology and instruments
- No. 1
EXPANSION OF THE FUNCTIONAL CAPABILITIES OF ELECTROMAGNETIC METHODS AND DEVICES FOR CONTROLLING MECHANICAL STRESSES IN CYLINDRICAL METAL PRODUCTS
This study addresses the theoretical foundations and the implementation algorithm of a differential transformer electromagnetic overlay transducer designed for monitoring variations in the electromagnetic parameters of a ferromagnetic shaft subjected to torque. An experimental setup was created, and the transducer's characteristics for amplitude, phase, and variable-frequency control methods were obtained. The obtained dependencies show that using the differential method, magnetic permeability and magnetizing current frequency serve as informative parameters, being the most sensitive to changes in mechanical loads on the cylindrical product. It has been established that such a system has high resolution and expanded functional capabilities.