Naris Chattranont
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Naris Chattranont has a total of 6 co-authors. Here are the top co-authors by number of shared publications:
Jutanon Kaewmanee
Metropolitan Electricity Authority,District Affair Department,Bangkok,Thailand
1 shared publicationNattachote Rugthaicharoencheep
Department of Electrical Engineering, Faculty of Engineering, Rajamangala University of Technology, Bangkok, THAILAND
1 shared publication- Nattachote Rugthaicharoencheep
Department of Electrical Engineering, Faculty of Engineering, Rajamangala University of Technology Phra Nakhon, Bangkok 10800, Thailand
1 shared publication Sakhon Woothipatanapan
Department of Electrical Engineering, Faculty of Engineering, Rajamangala University of Technology, Bangkok, THAILAND
1 shared publication- Sakhon Woothipatanapan
Department of Electrical Engineering, Faculty of Engineering, Rajamangala University of Technology Phra Nakhon, Bangkok 10800, Thailand
1 shared publication Tanit Menaneatra
Metropolitan Electricity Authority,Bettercare and Power Quality Department,Bangkok,Thailand
1 shared publication
Latest Publications
- Open Access
- 5 June 2025
- Published by MDPI AG in Applied Sciences
- Vol. 15 (11) , 6357
Assessment of Transformer Fault Severity from Online Dissolved Gas Analysis Using Positive CUSUM
Dissolved gas analysis (DGA) is one of the transformer testing methods that has been widely used for a long time because it does not require the transformer to be offline for testing. The inspection can be conducted while the transformer is operating normally, and it is cost-effective. In research on fault severity, thermodynamic theory has been applied to find the energy index of the hydrocarbon gases generated by faults, , , and , referred to as the Normalised Energy Intensity (NEI). This study examines the application of the Positive Cumulative Sum of Difference (CUSUM) method to hydrocarbon NEI and carbon dioxide NEI for fault severity assessment. The study demonstrates the effectiveness of this approach by means of case studies on the basis of DGA results from two steel plants. In the case of NEI from hydrocarbon gases (), the positive CUSUM is compared with the NEI, the NEI score, and the cumulative NEI. In the case of NEI from carbon oxide gases (), Positive CUSUM is compared with NEI and the ratio of to . It was found that Positive CUSUM for is a much better indicator of the severity of defects than the NEI, the NEI score, and the cumulative NEI. In contrast, Positive CUSUM for gave excessively high values. However, combining NEI with the / ratio gave better monitoring results. Therefore, from an online DGA perspective, Positive CUSUM can be used to effectively monitor fault severity.- 5 June 2025
- Published by MDPI AG in Applied Sciences
- Vol. 15 (11) , 6357
Open AccessAssessment of Transformer Fault Severity from Online Dissolved Gas Analysis Using Positive CUSUM
Dissolved gas analysis (DGA) is one of the transformer testing methods that has been widely used for a long time because it does not require the transformer to be offline for testing. The inspection can be conducted while the transformer is operating normally, and it is cost-effective. In research on fault severity, thermodynamic theory has been applied to find the energy index of the hydrocarbon gases generated by faults, , , and , referred to as the Normalised Energy Intensity (NEI). This study examines the application of the Positive Cumulative Sum of Difference (CUSUM) method to hydrocarbon NEI and carbon dioxide NEI for fault severity assessment. The study demonstrates the effectiveness of this approach by means of case studies on the basis of DGA results from two steel plants. In the case of NEI from hydrocarbon gases (), the positive CUSUM is compared with the NEI, the NEI score, and the cumulative NEI. In the case of NEI from carbon oxide gases (), Positive CUSUM is compared with NEI and the ratio of to . It was found that Positive CUSUM for is a much better indicator of the severity of defects than the NEI, the NEI score, and the cumulative NEI. In contrast, Positive CUSUM for gave excessively high values. However, combining NEI with the / ratio gave better monitoring results. Therefore, from an online DGA perspective, Positive CUSUM can be used to effectively monitor fault severity. - 6 December 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-4
Fault Classification from Dissolved Gas Analysis Results Using Machine Learning
Transformers are essential devices in the distribution system. If the transformer is damaged, It will cause a prolonged power outage and affect many customers. Therefore, inspecting and analyzing the transformer’s condition for maintenance planning is essential. Dissolved gas analysis is extensive use because sampling of transformer oil for analysis can be carried out without shutting down the transformer and at a low cost. This paper discusses the application of machine learning methods to classify fault types from the results of dissolved gas analysis. The significant gases dissolved in transformer oil are Hydrogen (H 2 ), Methane (CH 4 ), Ethane (C 2 H 6 ), Ethylene (C 2 H 4 ), and Acetylene (C 2 H 2 ). Fault type analysis using Classification Machine Learning Algorithms such as Decision Tree, Naive Bayes, k-nearest Neighbor, and Support Vector Machine compared to Ensemble Machine Learning Algorithms such as Bootstrap Aggregation (Bagging), Random Forest, and Adaboost. Ensemble Machine Learning Algorithms make prediction results more accurate than Classification Machine Learning algorithms.
- 6 December 2023
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-4
Fault Classification from Dissolved Gas Analysis Results Using Machine Learning
Transformers are essential devices in the distribution system. If the transformer is damaged, It will cause a prolonged power outage and affect many customers. Therefore, inspecting and analyzing the transformer’s condition for maintenance planning is essential. Dissolved gas analysis is extensive use because sampling of transformer oil for analysis can be carried out without shutting down the transformer and at a low cost. This paper discusses the application of machine learning methods to classify fault types from the results of dissolved gas analysis. The significant gases dissolved in transformer oil are Hydrogen (H 2 ), Methane (CH 4 ), Ethane (C 2 H 6 ), Ethylene (C 2 H 4 ), and Acetylene (C 2 H 2 ). Fault type analysis using Classification Machine Learning Algorithms such as Decision Tree, Naive Bayes, k-nearest Neighbor, and Support Vector Machine compared to Ensemble Machine Learning Algorithms such as Bootstrap Aggregation (Bagging), Random Forest, and Adaboost. Ensemble Machine Learning Algorithms make prediction results more accurate than Classification Machine Learning algorithms.
- 14 October 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 165-168
Case Study on Power Transformer using Dissolved Gas Analysis Technique
This paper discusses Dissolved Gas Analysis (DGA) in transformer oil from two 69/24 kV 24/32 MVA installed in urban areas. By detecting unusual increasing gas, then transformer oil samples were collected frequently according to Standards. First transformer was failed by inside short circuit. All loads were transfer to second transformer. The risk of failure on last transformer is very high. Standards used for DGA interpretation is IEEE C57.104. Evaluation of fault type used Key gas method, Doernenburg ratio, Rogers ratio and Duval Triangle.
- 14 October 2020
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 165-168
Case Study on Power Transformer using Dissolved Gas Analysis Technique
This paper discusses Dissolved Gas Analysis (DGA) in transformer oil from two 69/24 kV 24/32 MVA installed in urban areas. By detecting unusual increasing gas, then transformer oil samples were collected frequently according to Standards. First transformer was failed by inside short circuit. All loads were transfer to second transformer. The risk of failure on last transformer is very high. Standards used for DGA interpretation is IEEE C57.104. Evaluation of fault type used Key gas method, Doernenburg ratio, Rogers ratio and Duval Triangle.