  • Open Access

    Electrothermal Failure Mechanism of Multi-Finger Contacts in a Disconnector Under Foundation-Induced Displacement

    by Jia Zhang, Bodong Chen, Kang Liu, Tiancun Wu, Hailong Wang, Luyao Wang, Miao Wen

    To clarify the electrothermal failure of fixed contacts in a 363 kV three-phase five-column disconnector, field inspection, circuit-resistance tests, contact-mechanical modeling, finger-level resistance calculation, and electrothermal simulation were combined. The fault side had approximately 10 mm settlement and 51 mm horizontal displacement. Unserved contacts remained at 81–83 μΩ, whereas field-served contacts showed displacement-sensitive, non-monotonic resistance changes. A finite element model of 24 contact fingers with assembly-induced prestress was developed. Contact pressures were calculated under normal, settlement, and combined settlement—horizontal displacement conditions. Normal force was integrated over each contact area, and zero pressure denoted contact loss. The force, contact length, and equivalent contact width were used in a cylinder-on-flat model to calculate finger resistance. These resistances were connected in parallel and calibrated against the measured normal-state resistance of 83.57 μΩ. Settlement redistributed load from lower to upper fingers, while further horizontal displacement concentrated contact on one side; eastward displacement caused all bottom-row fingers to lose contact. Electrothermal simulation showed little temperature change while most fingers remained in contact, but temperatures exceeded 130 °C after bottom-row contact loss. Thus, total resistance can conceal local degradation, while load redistribution and current concentration increase Joule heating in remaining paths and explain burnout.

  • Open Access

    Collaborative Suppression Method Based on Current Preprocessing and Active Power Decoupling for Second-Order DC Voltage Ripple in PFC Converters

    by Wei Chen, Hang Zhang, Jia Zhang, Feng Wang, Dingjun Wen, Feixing Wang, Kang Liu, Yongliang Yao, Dibin Zhu, Yong Wang, et al.

    This paper presents a collaborative second-order voltage ripple suppression control method for single-phase power factor correction (PFC) converters. First, the causes of second-order DC output voltage ripples are analyzed. Then a modified current preprocessing mechanism is presented for the PFC in order to elevate valley power and suppress peak power, which is able to reduce the second-order power fluctuations. Parameter design and constraints are further provided to obtain a reasonable trade-off between current distortion and the suppressing effect. Meanwhile, an active power decoupling (APD) circuit reusing a capacitor half-bridge is also embedded into the PFC converter. For the APD circuit, this paper calculates and determines the capacitor voltage reference for the purpose of absorbing second-order power fluctuations. Moreover, a closed-loop control strategy for APD is presented to achieve tracking of the capacitor voltage. A coordinate control algorithm is introduced to monitor the cooperative relationship between PFC and APD control. Finally, a 400 W PFC prototype is constructed, and experimental tests are then carried out for verification. The results obtained based on the prototype can confirm the feasibility of the control strategy and the correctness of the theoretical analysis discussed in this paper.

  • Open Access

    Transient Stability Enhancement and Voltage Support for Grid-Forming Converters via Adaptive Improved Observer Control Under Grid Fault

    by Wei Chen, Hang Zhang, Jia Zhang, Feng Wang, Dingjun Wen, Feixing Wang, Kang Liu, Yuanzhen Xu, Zhenzhen Xie, Wei Lv, et al.

    With the large-scale integration of renewable energy sources, grid-forming (GFM) converters with inherent voltage and frequency support capabilities have attracted significant attention. However, due to the limited overcurrent withstand capability of power electronic devices, the stable operation of GFM converters under grid faults such as grid voltage sags remains a critical challenge. To address this issue, this paper systematically investigates the mechanisms of power angle instability and overcurrent generation during grid faults by a unified equivalent impedance model. Based on this analysis, a comprehensive control strategy that simultaneously considers power angle stability and overcurrent suppression is proposed. By introducing an adaptive improved observer control (AIOC), the active power reference is adaptively adjusted to enhance the power angle stability of the system. Meanwhile, the voltage reference is dynamically regulated to effectively limit the fault current while enhancing the voltage support capability. Finally, comprehensive theoretical analysis and experimental validation are provided. The experimental results demonstrate that the proposed strategy is capable of ensuring power angle stability and limits the overcurrent to within 1.5 p.u. Meanwhile, the voltage magnitude is increased by approximately 6%. The results demonstrate the robustness and adaptability of the proposed method under various conditions.

  • Open Access

    Influence of Conducting Particle on DC Flashover Characteristics and Tracking Property of GIS/GIL Insulator

    by Xiaolong Li, Chen Cao, Xin Lin

    Flashover at gas/insulator interface acts as a vital challenge to the safe and stable operation of gas-insulated system especially when involved with surface metallic particle. In this paper, flashover characteristics at SF6/epoxy insulator interface were investigated concerning on the tracking property based on image analysis. DC flashover experiments were operated for basin-type spacer with metallic particle at various locations. Flashover voltage was obtained and tracking on the surface after successive flashover was captured. Improved image analysis method based on fractal theory was carried out to evaluate tracking pattern quantitatively. The relation between the fractal dimension of tracking and field distribution at particle tip was revealed. Obtained results showed that flashover voltage decreased due to severe field distortion with moving particle from ground to HV electrode. Meanwhile, fractal dimension of tracking covering the area from particle to ground electrode indicated centralized tendency. Simulation result confirmed this variation as the consequence of centralized field distribution at the tip of particle. The quantitative relation between fractal dimension and field distribution suggests new sight to estimate the influence of metallic particle on insulation property in the gas-insulated system.


  • Dynamic Dielectric Strength of C3F7CN/CO2 and C3F7CN/N2 Gas Mixtures in High Voltage Circuit Breakers

    by Xin Lin, Jia Zhang, Jianyuan Xu, Jianying Zhong, Yu Song, Youpeng Zhang

    Searching for SF 6 -substitute gaseous dielectrics is currently an urgent task for high-voltage circuit breaker (HVCB) insulation and arc extinction applications. Once leaked, SF 6 will affect the Earth's climate on the order of decades to millennia. In this work, we developed a test method that supplies a series of extended pulse voltages to obtain the dynamic dielectric strength of C 3 F 7 CN/CO 2 and C 3 F 7 CN/N 2 gas mixtures that are potential SF 6 alternative gases in an HVCB during its no-load closing-opening processes, by measuring the dynamic breakdown voltage between the contacts. We also investigated the closing pre-strike and opening insulation characteristics of these gas mixture HVCBs at different voltage polarities, C 3 F 7 CN concentrations and pressures during the processes. We experimentally found an obvious “low-voltage-breakdown” phenomenon and much higher dispersion in the dynamic breakdown voltage of C 3 F 7 CN gas mixtures compared with pure SF 6 . Moreover, the dispersion in closing was significantly higher than that in opening, leading to the closing pre-strike characteristics of an HVCB filled with C 3 F 7 CN mixtures that are inferior to SF 6 . The results not only provide a criterion via data but also evaluate the interruption gap design and give insight into the expected performance of the interruption chamber during breaking capacity tests.