Influence of the Distribution of Lightning Strikes Along the Span of Transmission Lines On Their Backflashover Rate: The Span Factor
- 3 June 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (3) , 1403-1411
Abstract
The effect of the distribution of lightning strikes along the span on the performance of transmission lines was assessed following an advanced methodology, based on a Monte Carlo approach. First, considering typical features of 138-kV and 230-kV transmission lines, systematic simulations were performed, using an electromagnetic model to determine overvoltages and the disruptive effect method to assess backflashover occurrence. The influence of five variables was analyzed (tower-footing impedance, span length, waveform of the lightning return stroke current, insulation withstand and model of lightning attractiveness). The results indicated that a span factor is able to properly express the effect of the strikes distribution in the span and revealed trends: larger span factor with increasing tower-footing impedance and longer span length, smaller span factor with increasing critical flashover overvoltage and larger span factor for those models that assume larger attractiveness of the transmission line tower. Considering realistic distributions of tower-footing impedance along the line, a very narrow dispersion of the span factor was found. Assuming the same attractiveness for towers and shield wires, values of the span factor of about 0.8, 0.56, 0.53, and 0.37 were found, respectively for the 138-kV, 230-kV, 345-kV and 500-kV transmission lines.Keywords
This publication has 13 references indexed in Scilit:
- Lightning performance of transmission lines: Assessing the quality of traditional methodologies to determine backflashover rate of transmission lines taking as reference results provided by an advanced approachElectric Power Systems Research, 2017
- Lightning Performance of Transmission Lines: Requirements of Tower-Footing Electrodes Consisting of Long Counterpoise WiresIEEE Transactions on Power Delivery, 2015
- Lightning Performance of Transmission Lines: Methodology to Design Grounding Electrodes to Ensure an Expected Outage RateIEEE Transactions on Power Delivery, 2014
- FDTD Simulation of Insulator Voltages at a Lightning-Struck Tower Considering Ground-Wire CoronaIEEE Transactions on Power Delivery, 2013
- Analytical Representation of Single- and Double-Peaked Lightning Current WaveformsIEEE Transactions on Electromagnetic Compatibility, 2007
- Lightning Performance Analysis of Overhead Transmission Lines Using the EMTPIEEE Transactions on Power Delivery, 2005
- HEM: A Model for Simulation of Lightning-Related Engineering ProblemsIEEE Transactions on Power Delivery, 2005
- A representative curve for lightning current waveshape of first negative strokeGeophysical Research Letters, 2004
- The Incidence of Lightning Strikes to Power LinesIEEE Transactions on Power Delivery, 1987
- Monte Carlo Computer Calculation of Transmission-Line Lightning PerformanceTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1961