Experimental Performance Evaluation of the $\alpha \beta 0$-Based Bus Differential Protection
- 22 February 2023
- journal article
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 59 (3) , 2919-2931
Abstract
This paper presents the experimental performance assessment of the $\alpha \beta 0$ -based bus differential protection (BDP). This protection is developed for buses that interconnect battery storage systems (BSSs). The tested BDP employs $\alpha \beta 0$ components of the apparent powers flowing in all branches that are connected to the protected bus. The $\alpha \beta 0$ components of apparent powers allow accommodating frequent changes in the direction of power flows due to the charging/discharging modes of the BSS operation. In each branch connected to the protected bus, the $3\phi$ apparent powers are determined using the measured branch currents and voltage (at the protected bus). The $\alpha \beta 0$ -based BDP is implemented using a digital processing board for experimental testing for a laboratory setup. The test setup is composed of a bus that interconnects a 4 kW BSS, and feeds $3\phi$ linear and dynamic loads. The performance of the $\alpha \beta 0$ -based BDP is assessed for responding to various internal and external faults occurring during the charging and discharging of the BSS. Experimental results reveal encouraging abilities of the tested BDP to initiate fast, accurate, and reliable responses to internal and external faults. Observed response features are complimented with a negligible sensitivity to the BSS mode of operation, fault type, and/or fault location.Keywords
Funding Information
- NSERC Discovery Grant
This publication has 29 references indexed in Scilit:
- Bus Differential Protection in Industrial Systems With Generators Connected Directly to the Main Distribution BusIEEE Transactions on Industry Applications, 2016
- Hilbert–Huang transform‐based transient busbar protection algorithmIET Generation, Transmission & Distribution, 2015
- A Novel Busbar Protection Method Based on Polarity Comparison of Superimposed CurrentIEEE Transactions on Power Delivery, 2015
- On the Design and Capacity of a Grounding Configuration for Grid-Connected DGUsIEEE Transactions on Industry Applications, 2015
- Impacts of Grounding Configurations on Responses of Ground Protective Relays for DFIG-Based WECSs—Part I: Solid Ground FaultsIEEE Transactions on Industry Applications, 2015
- Optimal Coordination of Directional Overcurrent Relays Using a New Time–Current–Voltage CharacteristicIEEE Transactions on Power Delivery, 2014
- Impacts of grounding configurations on responses of ground protective relays for DFIG-based WECSs2014
- Adaptive Agent-Based Wide-Area Current Differential Protection SystemIEEE Transactions on Industry Applications, 2010
- Busbar differential protection in conjunction with a current transformer compensating algorithmIET Generation, Transmission & Distribution, 2008
- A Busbar Differential Protection Relay Suitable for Use With Measurement Type Current TransformersIEEE Transactions on Power Delivery, 2005