Abstract
Power systems (including industrial and commercial power systems) widely utilize digital protective relays for component and system protection. These protective devices have shown numerous operational advantages over conventional electromagnetic protective devices. Such operational advantages include the accuracy, reliability, response speed, interoperability, weight, and size. Performance and operational advantages of digital protective relays are typically dependent on the resolution of their input data, as well as their algorithms for fault detection and identification. This paper assesses the performance of time-based, frequency-based, and time-frequency-based digital protective relays, when operated at different sampling rates. Tested sampling rates include low, medium, and high sampling rates that range from 16 to 288 samples per cycle. In this paper, the three digital protective relays are tested when deployed as the digital 87 T transformer digital protection. Performance of the time-based, frequency-based, and time-frequency-based digital protective relays is assessed in terms of their accuracy and response speed. Test results show that low sampling rates can deteriorate the accuracy and response speed of the three tested digital protective relays. Obtained performance results also reveal that medium and high sampling rates can effectively improve the accuracy and response speed of the time-based, frequency-based, and time-frequency-based digital protective relays.Keywords
This publication has 23 references indexed in Scilit:
- Comparing the Performance of Protection Coordination and Digital Modular Protection for Grid-Connected Battery Storage SystemsIEEE Transactions on Industry Applications, 2018
- Modernizing Substation Automation Systems: Adopting IEC Standard 61850 for Modeling and CommunicationIEEE Industry Applications Magazine, 2016
- IEC/IEEE International Standard - Communication networks and systems for power utility automation – Part 9-3: Precision time protocol profile for power utility automation2016
- On the Design and Capacity of a Grounding Configuration for Grid-Connected DGUsIEEE Transactions on Industry Applications, 2015
- Impacts of Grounding Configurations on Responses of Ground Protective Relays for DFIG-Based WECSs—Part I: Solid Ground FaultsIEEE Transactions on Industry Applications, 2015
- Impacts of grounding configurations on responses of ground protective relays for DFIG-based WECSs2014
- The Development of a $d$–$q$ Axis WPT-Based Digital Protection for Power TransformersIEEE Transactions on Power Delivery, 2012
- A New Implementation Method of Wavelet-Packet-Transform Differential Protection for Power TransformersIEEE Transactions on Industry Applications, 2011
- Ground-fault detection in multiple source solidly grounded systems via the single-processor concept for circuit protectionIEEE Transactions on Industry Applications, 2006
- The Single-Processor Concept for Protection and Control of Circuit Breakers in Low-Voltage SwitchgearIEEE Transactions on Industry Applications, 2004