The electrical power system is susceptible to several faults, which can cause the system to malfunction. Among these, the ones that occur in the busbars of substations stand out. The main bus of a substation can concentrate a large amount of power and many derivations to service electrical loads, making it an element of high importance for the reliability of the system. Although the buses have a low incidence of faults, they are considered critical elements of the electrical power system, as their operating output can cause a large number of forced outages. This situation makes the protection of this component of paramount importance. There are currently two widely used bus differential protection techniques: high-impedance and low-impedance bus differential protection. The second technique is more commonly used due to the possibility of sharing current transformers (CTs). However, the high cost and greater requirements for maintenance makes the differential protection of busbars in distribution or sub-transmission substations unfeasible. With the advent and implementation of the IEC 61850 standard, modern protection systems based on this standard offer significant advantages, such as lower expenses with installation, wiring, commissioning and maintenance; adaptable bus configuration; use of different CT ratios; considerably minimized susceptibility to CT saturation; lower risks of open secondary CT circuits and viability of implantation in distribution substations. The objective of this review is to present an overview of the works found in the literature on substation busbar differential protection, considering classical methods and those based on the IEC 61850 standard.Keywords
Funding Information
- CPFL Energia (PD-00063-3083/2021, Finance Code 001)
- Coordenação de Aperfeiçoamento de Pessoal de Nível Superior (PD-00063-3083/2021, Finance Code 001)
This publication has 26 references indexed in Scilit:
- Partial operating current characteristics to discriminate internal and external faults of differential protection zones during CT saturationIET Generation, Transmission & Distribution, 2017
- Intelligent busbar protection scheme based on combination of support vector machine and S‐transformIET Generation, Transmission & Distribution, 2017
- Development of a new fault zone identification scheme for busbar using logistic regression classifierIET Generation, Transmission & Distribution, 2017
- Adaptive busbar differential relaying scheme during saturation period of current transformers based on alienation conceptIET Generation, Transmission & Distribution, 2016
- Generalized Alpha Plane for Numerical Differential Protection ApplicationsIEEE Transactions on Power Delivery, 2016
- Development of a Substation-Area Backup Protective Relay for Smart SubstationIEEE Transactions on Smart Grid, 2016
- A Novel Busbar Protection Method Based on Polarity Comparison of Superimposed CurrentIEEE Transactions on Power Delivery, 2015
- New differential busbar characteristic based on high frequencies extracted from faulted signal during current transformer saturationIET Generation, Transmission & Distribution, 2014
- A new digital busbar protection technique based on frequency information during CT saturationInternational Journal of Electrical Power & Energy Systems, 2013
- A novel wavelet approach to busbar protection during CT saturation and ratio-mismatchElectric Power Systems Research, 2004