Efficient and Comprehensive Evaluation Method of Temporary Overvoltage in Distribution Systems with Inverter-Based Distributed Generations
Open Access
- 30 June 2021
- journal article
- research article
- Published by MDPI AG in Sustainability
- Vol. 13 (13) , 7335
Abstract
In general, a temporary overvoltage (TOV) on the healthy phases occurs because of the neutral-shift phenomenon during a single line-to-ground (SLG) fault. The TOV can destroy the insulation of electric devices and cause damage to other equipment and customer loads in just a few cycles. In practice, the TOV can be affected by numerous factors: the sequence reactance ratio of the interconnection transformer, the ratio of load to DG, and the distance to the fault. More importantly, inverter-based distributed generations (DGs) have different influences on the TOV from traditional synchronous-machine-based DGs. In this sense, this work performed an efficient and comprehensive investigation on the effect of these various parameter types and their extensive variations, based on steady-state analysis with sequence equivalent circuits and three-dimensional representations. The proposed methodology can facilitate judging the impact of multi-parameter conditions on the TOV readily and comparing the fault characteristics of synchronous-machine-based and inverter-based DGs. Finally, the results can be used for future studies on TOV mitigation techniques.Keywords
Funding Information
- Korea Electric Power Corporation (CX71-20-0007)
- Korea Institute of Energy Technology Evaluation and Planning(KETEP) grant funded by the Korea government(MOTIE) (20191210301890)
This publication has 20 references indexed in Scilit:
- Single Line to Ground Fault Detection in a Non-Effectively Grounded Distribution NetworkIEEE Transactions on Power Delivery, 2018
- IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems--Part I: Introduction2017
- Ground Fault Overvoltage With Inverter-Interfaced Distributed Energy ResourcesIEEE Transactions on Power Delivery, 2016
- A Review of Distributed Generation Resource Types and Their Mathematical Models for Power Flow AnalysisInternational Journal of Science, Technology and Society, 2015
- Solar PV inverter testing for model validation2011
- IEEE Standard for Insulation Coordination--Definitions, Principles, and Rules2011
- IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems2008
- Distributed generation interconnection transformer and grounding selection2008
- Distributed generation: challenges and possible solutions2006
- Overvoltage considerations in applying distributed resources on power systems2003