Air filtration mitigates aerosol levels both during and after OGD procedures
Preprint
Abstract
Objectives Upper GI endoscopies are aerosol generating procedures (AGPs), increasing risk of spreading airborne pathogens. We aim to quantify mitigation of airborne particles via improved ventilation, specifically laminar flow theatres and portable HEPA filters, during and after upper GI endoscopies. Methods This observational study included patients undergoing routine oral gastroscopy in a standard endoscopy room with 15-17 air changes per hour, a standard endoscopy room with portable HEPA filtration unit, and a laminar flow theatre with 300 air changes per hour. A particle counter (diameter range 0.3μm-25μm) took measurements 10cm from the mouth. Three analyses were performed: whole procedure particle counts, event-based counts and air clearance estimation using post-procedure counts. Results Compared to a standard endoscopy room, for whole procedures we observe a 28.5x reduction in particle counts in laminar flow (p5μm for oral extubation (12.2x,pConclusions Laminar flow theatres are highly effective at dispersing aerosols immediately after production and should be considered for high-risk cases where patients are actively infectious or supply of PPE is limited. Portable HEPA filers can safely reduce fallow time between procedures by 40%.Keywords
This publication has 16 references indexed in Scilit:
- Use of portable partitions with high-efficiency particulate air filters in the endoscopy unitEndoscopy International Open, 2021
- A Proof of Concept Study: Esophagogastroduodenoscopy Is an Aerosol-Generating Procedure and Continuous Oral Suction During the Procedure Reduces the Amount of Aerosol GeneratedGastroenterology, 2020
- Aerosols Produced by Upper Gastrointestinal Endoscopy: A Quantitative EvaluationAmerican Journal of Gastroenterology, 2020
- Use of a modified ventilation mask to avoid aerosolizing spread of droplets for short endoscopic procedures during coronavirus COVID-19 outbreakGastrointestinal Endoscopy, 2020
- Commercially available endoscopy facemasks to prevent aerosolizing spread of droplets during COVID-19 outbreakEndoscopy International Open, 2020
- Operating Room Traffic Increases Aerosolized Particles and Compromises the Air Quality: A Simulated StudyThe Journal of Arthroplasty, 2018
- Characterizations of particle size distribution of the droplets exhaled by sneezeJournal of The Royal Society Interface, 2013
- Airflow Dynamics of Human Jets: Sneezing and Breathing - Potential Sources of Infectious AerosolsPLOS ONE, 2013
- Size distribution and sites of origin of droplets expelled from the human respiratory tract during expiratory activitiesJournal of Aerosol Science, 2009
- Ventilation performance in the operating theatre against airborne infection: numerical study on an ultra-clean systemJournal of Hospital Infection, 2005