The paper presents the results of field measurements of carbon dioxide (CO₂) concentration in classroom 107Ts of Poltava Polytechnic National University, equipped with a decentralized supply-and-exhaust heat recovery unit VUT300 with three fixed fan speeds. The study aimed to establish the dependence of indoor CO₂ concentration on the number of occupants and the fan speed of the recovery unit, and to determine the minimum required outdoor airflow rate per person that keeps the CO₂ increment within the commonly accepted limit of 800 ppm above the outdoor background level. Measurements were carried out using three multifunctional Xintest HT-501 sensors, recording CO₂ concentration, relative humidity and temperature every two minutes at three characteristic points of the room: in the breathing zone at the center of the classroom, near the supply air branch, and in the most remote 'dead zone' with respect to the supply airflow. Outdoor conditions were monitored with a Sencor SWS 12500 WIFI weather station installed on the roof, and the electric power consumption of the unit at each fan speed was measured with a Sonoff POWR316D WIFI energy meter. Duct airflow rates in the 160 mm supply and exhaust ducts were additionally verified with a testo 405 V1 hot-wire anemometer with a telescopic probe, yielding measured supply airflow rates of approximately 70, 206 and 275 m³/h for the first, second and third fan speeds, respectively. An initial series of measurements under freely varying occupancy (0 to 8 people) did not produce a conclusive relationship between occupancy and CO₂ concentration because of fluctuations in the number of people present during the class. Therefore, a second series with strictly fixed occupancy before and after a defined time interval was used to determine the per-person CO₂ generation rate by applying a CO₂ mass-balance (build-up) method. The resulting generation rate of approximately 0.0036 dm³/s (12.95 dm³/h) per person is consistent with physiologically based estimates reported in the literature. Based on this rate, the required outdoor airflow was calculated for 1 to 20 occupants, and the applicability ranges of the three fan speeds of the VUT300 unit were established: the first speed is sufficient for 1-4 people, the second for 5-12 people, and the third for 13-16 people; for 17 or more people the measured capacity of the unit is insufficient to keep the CO₂ increment within the target limit under real operating conditions. The calculated values were compared with the normative outdoor airflow rates prescribed by DBN V.2.2-3:2018 'Educational Institutions' (20 m³/(h·person)) and with the category-based approach of DSTU B EN 15251:2011, showing that normative values include a margin beyond pure metabolic CO₂ control, since they also account for other human bioeffluents and perceived air quality criteria. The obtained results provide a practical basis for scheduling the fan speed of classroom heat recovery units (for example, through the Vents Home application) according to the expected number of students in a group, allowing indoor air quality requirements to be reconciled with energy-efficient operation of ventilation equipment during the ongoing thermal modernization of university buildings. The proposed approach can be extended to other classrooms and recovery unit models, and combined with direct CO₂-based automatic fan speed control instead of schedule-only operation, as a direction for further research.