Danyl Yermolenko
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Research Subjects
Danyl Yermolenko has a total of 5 co-authors. Here are the top co-authors by number of shared publications:
- Dmytro Guzyk
National University “Yuri Kondratyuk Poltava Polytechnic
2 shared publications - Oleksandra Cherednikova
Національний університет «Полтавська політехніка імені Юрія Кондратюка
1 shared publication - Volodymyr Cherednikov
Kondratyuk Poltava State Technical University
1 shared publication В. М. Чередніков
National University “Yuri Kondratyuk Poltava Polytechnic
1 shared publicationО. В. Череднікова
National University “Yuri Kondratyuk Poltava Polytechnic
1 shared publication
Latest Publications
- 2 November 2026
- Published by Admiral Makarov National University of Shipbuilding
- No. 3 (506),p. 277-285
ЕКСПЕРИМЕНТАЛЬНЕ ДОСЛІДЖЕННЯ ЕФЕКТИВНОСТІ ПРИПЛИВНО-ВИТЯЖНОЇ ВЕНТИЛЯЦІЙНОЇ СИСТЕМИЗ РЕКУПЕРАЦІЄЮ ТЕПЛОТИ В НАВЧАЛЬНОМУ ПРИМІЩЕННІ
Purpose. To evaluate the actual efficiency of a supply and exhaust ventilation unit with heat recovery under real operating conditions of an educational room during the heating period, to obtain the dependencies of its performance indicators on the outdoor air temperature and to quantify the influence of the frost protection algorithm on the achievable level of heat utilization. Method. A full-scale experiment was carried out on a Vents VUT 300 PB EC P A21 DTV unit with a counter-flow polymer heat exchanger installed in a computer classroom of the National University “Yuri Kondratyuk Poltava Polytechnic”. A hardware and software monitoring complex was created, including the built-in temperature sensors of the unit read every 2 minutes by the specially developed ModbusReader application, a Sonoff POWR316D Wi-Fi electricity meter with the eWeLink application, a Sencor SWS12500WIFI weather station and three Xintest HT-501 indoor climate sensors. During the heating period, at outdoor temperatures from minus 9.7 to 12.7 degrees Celsius, an array of 5267 synchronized records was formed; after averaging over 10-minute intervals and sorting by outdoor temperature it contained 1059 points. The recovery effectiveness was determined by the temperature method, and third-degree polynomial regression was applied separately to the two operating modes of the unit. Results. It was established that the boundary between the two qualitatively different operating modes is about minus 2.7 degrees Celsius. Below this temperature the frost protection algorithm limited the full operation of the unit to 51.3 percent of the time: the average recovery effectiveness in this mode was about 52 percent, which corresponds to an effective heat utilization of about 27 percent, while in the normal mode the average effectiveness reached 86 percent with peaks up to 97 percent. The average recovered heat capacity was 0.85 kW in the frost protection mode and 1.26 kW in the normal mode, the ratio of the recovered heat capacity to the consumed electric power was on average 7.8 and 2.9 respectively, reaching 18. The recovered heat capacity over the whole period varied within 0.23–1.68 kW, and in the normal mode it naturally decreased with the increase of the outdoor air temperature. Scientific novelty. For the first time, on the basis of long-term automated monitoring of a serial small-capacity unit in the climatic conditions of Ukraine, the influence of the frost protection algorithm was quantified and polynomial regression dependencies of the performance indicators on the outdoor air temperature were obtained separately for the two operating modes. Practical importance. The obtained dependencies and indicators can be used in technical and economic feasibility calculations of heat recovery ventilation in educational buildings, in the selection of operating modes of such units, and the described monitoring approach can be reproduced for other objects.
- 2 November 2026
- Published by Admiral Makarov National University of Shipbuilding
- No. 3 (506),p. 277-285
ЕКСПЕРИМЕНТАЛЬНЕ ДОСЛІДЖЕННЯ ЕФЕКТИВНОСТІ ПРИПЛИВНО-ВИТЯЖНОЇ ВЕНТИЛЯЦІЙНОЇ СИСТЕМИЗ РЕКУПЕРАЦІЄЮ ТЕПЛОТИ В НАВЧАЛЬНОМУ ПРИМІЩЕННІ
Purpose. To evaluate the actual efficiency of a supply and exhaust ventilation unit with heat recovery under real operating conditions of an educational room during the heating period, to obtain the dependencies of its performance indicators on the outdoor air temperature and to quantify the influence of the frost protection algorithm on the achievable level of heat utilization. Method. A full-scale experiment was carried out on a Vents VUT 300 PB EC P A21 DTV unit with a counter-flow polymer heat exchanger installed in a computer classroom of the National University “Yuri Kondratyuk Poltava Polytechnic”. A hardware and software monitoring complex was created, including the built-in temperature sensors of the unit read every 2 minutes by the specially developed ModbusReader application, a Sonoff POWR316D Wi-Fi electricity meter with the eWeLink application, a Sencor SWS12500WIFI weather station and three Xintest HT-501 indoor climate sensors. During the heating period, at outdoor temperatures from minus 9.7 to 12.7 degrees Celsius, an array of 5267 synchronized records was formed; after averaging over 10-minute intervals and sorting by outdoor temperature it contained 1059 points. The recovery effectiveness was determined by the temperature method, and third-degree polynomial regression was applied separately to the two operating modes of the unit. Results. It was established that the boundary between the two qualitatively different operating modes is about minus 2.7 degrees Celsius. Below this temperature the frost protection algorithm limited the full operation of the unit to 51.3 percent of the time: the average recovery effectiveness in this mode was about 52 percent, which corresponds to an effective heat utilization of about 27 percent, while in the normal mode the average effectiveness reached 86 percent with peaks up to 97 percent. The average recovered heat capacity was 0.85 kW in the frost protection mode and 1.26 kW in the normal mode, the ratio of the recovered heat capacity to the consumed electric power was on average 7.8 and 2.9 respectively, reaching 18. The recovered heat capacity over the whole period varied within 0.23–1.68 kW, and in the normal mode it naturally decreased with the increase of the outdoor air temperature. Scientific novelty. For the first time, on the basis of long-term automated monitoring of a serial small-capacity unit in the climatic conditions of Ukraine, the influence of the frost protection algorithm was quantified and polynomial regression dependencies of the performance indicators on the outdoor air temperature were obtained separately for the two operating modes. Practical importance. The obtained dependencies and indicators can be used in technical and economic feasibility calculations of heat recovery ventilation in educational buildings, in the selection of operating modes of such units, and the described monitoring approach can be reproduced for other objects.
- Open Access
- 30 October 2026
- Published by Kyiv National University of Construction and Architecture in Ventilation, Illumination and Heat Gas Supply
- Vol. 58, 49-61
Determination of the required airflow rate and operating modes of the VUT300 heat recovery unit based on CO₂ concentration in a university classroom
The paper presents the results of field measurements of carbon dioxide (CO₂) concentration in classroom 107Ts of Poltava Polytechnic National University, equipped with a decentralized supply-and-exhaust heat recovery unit VUT300 with three fixed fan speeds. The study aimed to establish the dependence of indoor CO₂ concentration on the number of occupants and the fan speed of the recovery unit, and to determine the minimum required outdoor airflow rate per person that keeps the CO₂ increment within the commonly accepted limit of 800 ppm above the outdoor background level. Measurements were carried out using three multifunctional Xintest HT-501 sensors, recording CO₂ concentration, relative humidity and temperature every two minutes at three characteristic points of the room: in the breathing zone at the center of the classroom, near the supply air branch, and in the most remote 'dead zone' with respect to the supply airflow. Outdoor conditions were monitored with a Sencor SWS 12500 WIFI weather station installed on the roof, and the electric power consumption of the unit at each fan speed was measured with a Sonoff POWR316D WIFI energy meter. Duct airflow rates in the 160 mm supply and exhaust ducts were additionally verified with a testo 405 V1 hot-wire anemometer with a telescopic probe, yielding measured supply airflow rates of approximately 70, 206 and 275 m³/h for the first, second and third fan speeds, respectively. An initial series of measurements under freely varying occupancy (0 to 8 people) did not produce a conclusive relationship between occupancy and CO₂ concentration because of fluctuations in the number of people present during the class. Therefore, a second series with strictly fixed occupancy before and after a defined time interval was used to determine the per-person CO₂ generation rate by applying a CO₂ mass-balance (build-up) method. The resulting generation rate of approximately 0.0036 dm³/s (12.95 dm³/h) per person is consistent with physiologically based estimates reported in the literature. Based on this rate, the required outdoor airflow was calculated for 1 to 20 occupants, and the applicability ranges of the three fan speeds of the VUT300 unit were established: the first speed is sufficient for 1-4 people, the second for 5-12 people, and the third for 13-16 people; for 17 or more people the measured capacity of the unit is insufficient to keep the CO₂ increment within the target limit under real operating conditions. The calculated values were compared with the normative outdoor airflow rates prescribed by DBN V.2.2-3:2018 'Educational Institutions' (20 m³/(h·person)) and with the category-based approach of DSTU B EN 15251:2011, showing that normative values include a margin beyond pure metabolic CO₂ control, since they also account for other human bioeffluents and perceived air quality criteria. The obtained results provide a practical basis for scheduling the fan speed of classroom heat recovery units (for example, through the Vents Home application) according to the expected number of students in a group, allowing indoor air quality requirements to be reconciled with energy-efficient operation of ventilation equipment during the ongoing thermal modernization of university buildings. The proposed approach can be extended to other classrooms and recovery unit models, and combined with direct CO₂-based automatic fan speed control instead of schedule-only operation, as a direction for further research.
- 30 October 2026
- Published by Kyiv National University of Construction and Architecture in Ventilation, Illumination and Heat Gas Supply
- Vol. 58, 49-61
Open AccessDetermination of the required airflow rate and operating modes of the VUT300 heat recovery unit based on CO₂ concentration in a university classroom
The paper presents the results of field measurements of carbon dioxide (CO₂) concentration in classroom 107Ts of Poltava Polytechnic National University, equipped with a decentralized supply-and-exhaust heat recovery unit VUT300 with three fixed fan speeds. The study aimed to establish the dependence of indoor CO₂ concentration on the number of occupants and the fan speed of the recovery unit, and to determine the minimum required outdoor airflow rate per person that keeps the CO₂ increment within the commonly accepted limit of 800 ppm above the outdoor background level. Measurements were carried out using three multifunctional Xintest HT-501 sensors, recording CO₂ concentration, relative humidity and temperature every two minutes at three characteristic points of the room: in the breathing zone at the center of the classroom, near the supply air branch, and in the most remote 'dead zone' with respect to the supply airflow. Outdoor conditions were monitored with a Sencor SWS 12500 WIFI weather station installed on the roof, and the electric power consumption of the unit at each fan speed was measured with a Sonoff POWR316D WIFI energy meter. Duct airflow rates in the 160 mm supply and exhaust ducts were additionally verified with a testo 405 V1 hot-wire anemometer with a telescopic probe, yielding measured supply airflow rates of approximately 70, 206 and 275 m³/h for the first, second and third fan speeds, respectively. An initial series of measurements under freely varying occupancy (0 to 8 people) did not produce a conclusive relationship between occupancy and CO₂ concentration because of fluctuations in the number of people present during the class. Therefore, a second series with strictly fixed occupancy before and after a defined time interval was used to determine the per-person CO₂ generation rate by applying a CO₂ mass-balance (build-up) method. The resulting generation rate of approximately 0.0036 dm³/s (12.95 dm³/h) per person is consistent with physiologically based estimates reported in the literature. Based on this rate, the required outdoor airflow was calculated for 1 to 20 occupants, and the applicability ranges of the three fan speeds of the VUT300 unit were established: the first speed is sufficient for 1-4 people, the second for 5-12 people, and the third for 13-16 people; for 17 or more people the measured capacity of the unit is insufficient to keep the CO₂ increment within the target limit under real operating conditions. The calculated values were compared with the normative outdoor airflow rates prescribed by DBN V.2.2-3:2018 'Educational Institutions' (20 m³/(h·person)) and with the category-based approach of DSTU B EN 15251:2011, showing that normative values include a margin beyond pure metabolic CO₂ control, since they also account for other human bioeffluents and perceived air quality criteria. The obtained results provide a practical basis for scheduling the fan speed of classroom heat recovery units (for example, through the Vents Home application) according to the expected number of students in a group, allowing indoor air quality requirements to be reconciled with energy-efficient operation of ventilation equipment during the ongoing thermal modernization of university buildings. The proposed approach can be extended to other classrooms and recovery unit models, and combined with direct CO₂-based automatic fan speed control instead of schedule-only operation, as a direction for further research.