A Continuous Monitoring for Neutral Grounding Resistors and Reactors With Hardware Validation
- 23 January 2019
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 34 (4) , 1341-1349
Abstract
Neutral grounding devices are used to limit ground overcurrents, control transient overvoltages, and overcome the consequent issues. Intactness of these apparatuses is vital to prevent the risk of ungrounded or solidly grounded neutral. As such, they should be continuously monitored as targeted here. This paper proposes a continuous monitoring technique which supervises the NGD impedance obtained via full-range voltage and current measurement. It benefits from a new and cost-effective voltage metering mechanism specifically designed for the studied problem. Its performance has been validated using a fabricated prototype. In contrast to existing methods, the application of the proposed technique is not limited to a specific configuration, system operation mode, or neutral grounding device. Furthermore, monitoring is performed without signal injection. This monitoring technique shows reliable operation under various conditions of the system and grounding apparatuses based on the analysis performed using PSCAD in conjunction with MATLAB.Keywords
Funding Information
- Western University
- NSERC Collaborative Research and Development
This publication has 9 references indexed in Scilit:
- Online neutral grounding resistor monitoring for unit-connected generators with hardware validationInternational Journal of Electrical Power & Energy Systems, 2019
- Analysis of a Neutral Grounding Resistor Monitoring Method2018
- New methods for monitoring neutral grounding resistors2018
- Immunity Analysis and Experimental Investigation of a Low-Noise Amplifier Using a Transient Voltage Suppressor Diode Under Direct Current Injection of HPM PulsesIEEE Transactions on Electromagnetic Compatibility, 2014
- Neutral grounding resistor failure detection verification2013
- The Dangers of Grounding Resistor FailureIEEE Industry Applications Magazine, 2010
- Why neutral-grounding resistors need continuous monitoring2008
- Neutral ground resistor monitoring schemes2005
- Monitoring neutral-grounding resistors2003