Side Effects of Air-Core Reactors in Bus Ties, Tackled by Pre-Saturated Core Fault Current Limiters
- 19 January 2022
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 16, 1-8
Abstract
In this paper, a pre-saturated fault current limiter (PS-FCL) is proposed to be employed instead of the series reactors in distribution network of Mobarakeh Steel Company (MSC). In recent years, several interruptions have been reported which refer to undesirable role of the series reactors in normal condition. Significant voltage dip during heavy loads start-up is one of the main problems of the series reactors in the system. The complaints regarding the series reactors are studied as some simulation scenarios. Using PS-FCL instead of the series reactors, the same scenarios are simulated and the results are compared. The simulations are carried out using ANSYS/Maxwell and MATLAB/Simulink.Keywords
This publication has 18 references indexed in Scilit:
- Three-Phase Saturated-Core Fault Current LimiterEnergies, 2018
- Design and Performance Analysis of Single-Phase Pre-Saturated Core Fault Current LimitersIEEE Transactions on Power Delivery, 2018
- Optimization of MV Distribution System DesignsIEEE Transactions on Industry Applications, 2017
- A Novel Hybrid Saturated Core Fault Current Limiter Topology Considering Permanent Magnet Stability and PerformanceIEEE Transactions on Magnetics, 2017
- Simulation Method for Current-Limiting Effect of Saturated-Core Superconducting Fault Current LimiterIEEE Transactions on Applied Superconductivity, 2016
- Saturated Core Fault Current Limiters in a Live GridIEEE Transactions on Applied Superconductivity, 2016
- Cognition on the Current-Limiting Effect of Saturated-Core Superconducting Fault Current LimiterIEEE Transactions on Magnetics, 2015
- A Methodology for Modeling and Simulation of Saturated Cores Fault Current LimitersIEEE Transactions on Applied Superconductivity, 2014
- Development and Testing of a Transmission Voltage SuperLimiter™ Fault Current Limiter2012
- Fault current limiters report on the activities of CIGRE WG A3.162006