On the Chemical Composition and Hygroscopicity of Aerosols Deposited on the Insulators of Italian Power Lines
Authors:
- Irene GiniIGIrene Gini
- Alessandra BalzariniABAlessandra Balzarini
- Guido PirovanoGPGuido Pirovano
- Anna Maria ToppettiATAnna Maria Toppetti
- Lucio FialdiniLFLucio Fialdini
- Paolo OmodeoPOPaolo Omodeo
- Giovanni PirovanoGPGiovanni Pirovano
- Massimo MarzinottoMassimo Marzinotto
- Alessandro ManciniAMAlessandro Mancini
- Niccolò LosiNLNiccolò Losi
- Amedeo Manuel CefalìACAmedeo Manuel Cefalì
- Andrea DoldiADAndrea Doldi
Open Access
- 29 November 2023
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 13 (23) , 12788
Abstract
The reliability of the national power grid is a key issue in modern society. Atmospheric aerosols are the main cause of the reduction in the performance of insulators and the increase in the possibility of flashovers, resulting in power line failures. Under high ambient humidity, the water-soluble compounds of atmospheric aerosols collected on the insulators’ surface can dissociate in ions and form a conductive layer, which may lead to flashover events. With a view to investigating the processes that drive these phenomena, the chemical composition of aerosol deposits on insulators in Italy was determined by ion chromatography analysis and thermos-optical and X-ray techniques. In addition, a synthetic aerosol with the same analyzed chemical composition was generated in a laboratory and deposited on PTFE filters and glass specimens allowing us to determine the deliquescence and crystallization relative humidity and the conductive effect in an aerosol exposure chamber. The results evidenced the presence of a hazardous inorganic ion layer, which generates a sharp phase transition of the aerosol deposit as a function of the ambient relative humidity; this layer poses a dangerous threat to the reliability of the power grid, increasing the probability of flashover events where the conductive layer facilitates the flow of electrical current across the insulator surface, potentially causing power outages or damage to the power lines.Keywords
Funding Information
- Research Fund for the Italian Electrical System
- GEMMA Center
- European Union—NextGenerationEU
This publication has 46 references indexed in Scilit:
- Water uptake of internally mixed ammonium sulfate and dicarboxylic acid particles probed by infrared spectroscopyAtmospheric Environment, 2013
- Quantification of PM2.5 organic carbon sampling artifacts in US networksAtmospheric Chemistry and Physics, 2010
- Effect of insulator shape on surface discharges and flashover under polluted conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2005
- Geochemistry of natural and anthropogenic fall-out (aerosol and precipitation) collected from the NW Mediterranean: two different multivariate statistical approachesApplied Geochemistry, 1999
- Heterogeneous nucleation of the efflorescence of (NH4)2SO4 particles internally mixed with Al2O3, TiO2, and ZrO2Journal of Geophysical Research: Atmospheres, 1999
- Saharan dust inputs to the western Mediterranean Sea: depositional patterns, geochemistry and sedimentological implicationsDeep Sea Research Part II: Topical Studies in Oceanography, 1997
- Role of non-soluble contaminants on the flashover voltage of porcelain insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 1996
- Identifying solid-aqueous-phase transitions in atmospheric aerosols. II. Acidic solutionsAtmospheric Environment, 1995
- Hygroscopic properties of pollutants on HV insulatorsIEEE Transactions on Electrical Insulation, 1989
- Natural contamination test of insulators with DC voltage energization at inland areasIEEE Transactions on Power Delivery, 1988