Abstract
Electromagnetic Time Reversal (EMTR) has been shown as a promising technique for fault localization in distribution networks. However, its application to larger networks is constrained by the need for finely spaced guessed fault points required in the back-propagation stage of the EMTR process. The need to assess numerous guessed locations can make the fault location process computationally expensive, and missing the matched fault point can lead to significant localization errors. This article proposes a novel EMTR-based method that pre-identifies the fault zone before pinpointing the fault location, by strategically placing guessed fault points solely at the network’s leaf nodes. Extensive simulations across networks of varying scales demonstrate that this approach substantially reduces the network search area while enhancing localization accuracy when the matched point is missed.
Funding Information
  • Australian Research Council (ARC) Discovery Early Career Researcher Award (DE230100056)

This publication has 17 references indexed in Scilit: