Fast Transient Measurement at Transformer Terminal Based on Built-In Capacitive Sensor
- 25 March 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 73 (00189456) , 1-8
Abstract
It is important to determine the transient stresses at large power transformer winding terminals, because this transient stress may induce power transformer failure. When a transient sensor is mounted inside the transformer, there is a potential discharge from the high-voltage conductor to the sensor. Therefore, the transient voltages in transformers are usually measured indirectly. Such measurement results are not accurate because they are affected by the structure and impedance of the power equipment. Thus, a built-in capacitive fast transient sensor was developed in this paper. The developed sensor was installed inside the bushing mounting; thus, transient voltages are directly obtained. To eliminate potential discharge from a high-voltage conductor to a transient sensor, a dielectric window (DW) was developed. Then, the effects of the dielectric window and transformer oil on the amplitude-frequency response of the sensor were investigated. The results indicate that the bandwidth of the developed sensor spans 11 Hz~86.6 MHz (±1 dB). Afterward, switching and lightning impulse tests were conducted to demonstrate the accuracy of the sensor. Moreover, the proposed sensor was used to investigate the transient overvoltage in a 500 kV pumped storage power plant. The transformer winding exhibits increased stress due to the influence of frequent resonant transients with high amplitudes.Keywords
Funding Information
- National Natural Science Foundation of China (52222706)
- State Key Laboratory of Power Grid Environmental Protection (GYW51202201427)
This publication has 25 references indexed in Scilit:
- Frequency domain algorithm in the whole process simulation from VFTO to its conducted disturbance via voltage transformer in GIS substationsElectric Power Systems Research, 2022
- Configuration of suppression schemes against high-frequency transient reignition overvoltages caused by shunt reactor switching-off in offshore wind farmsInternational Journal of Electrical Power & Energy Systems, 2022
- Study of high frequency transient overvoltage caused by cable-transformer quarter-wave resonanceElectric Power Systems Research, 2021
- Transient overvoltage response performance of transformer windings with short‐circuit faultIET Generation, Transmission & Distribution, 2018
- Causes of transformer failures and diagnostic methods – A reviewRenewable and Sustainable Energy Reviews, 2018
- Performance evaluation of online transformer internal fault detection based on transient overvoltage signalsIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Non-contact measurement of lightning and switching transient overvoltage based on capacitive coupling and pockels effectsElectric Power Systems Research, 2016
- IEEE Guide to Describe the Occurrence and Mitigation of Switching Transients Induced by Transformers, Switching Device, and System Interaction2011
- Transformer Failure Due to Circuit-Breaker-Induced Switching TransientsIEEE Transactions on Industry Applications, 2010