On-Site Low Voltage Determination of Zero-Sequence Impedances for Power Transformers
- 3 March 2020
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 35 (2) , 1048-1057
Abstract
Accurate zero-sequence transformer data is important for correct fault analysis and protection settings. Utilities have been forced to approximate zero-sequence impedances for many three-legged core power transformers in service today that did not undergo testing for zero-sequence data at the factory before site installation. Where approximation of the zero-sequence impedances from positive sequence data is of insufficient accuracy, on-site tests have been proposed. However, these usually involve measurements from the high-voltage windings, which are either expensive with high test voltages or do not offer sufficient current resolution with low test voltages. This paper proposes new methods for carrying out on-site zero-sequence testing entirely from the lowest voltage winding. Affordable equipment can then be used for the test with minimal switchyard test preparations. Two test configurations are described; a One-Open-Phase test and a Two-Open-Phase test. To validate the method, three typical transformer types are considered; a station auxiliary transformer (SAT), a generation step-up transformer (GSU), and a transmission transformer. The proposed method was tested on actual SAT and GSU units, and simulated for a transmission transformer. All test results validated the method and offered high accuracy.Keywords
This publication has 11 references indexed in Scilit:
- Influence of zero sequence impedances of station auxiliary transformers on equipment performance under open-phase faults2017
- Analysis of open phase fault events using ETAP unbalanced load flow module2016
- On-site low voltage determination of zero sequence impedances for station auxiliary transformers2016
- Parameter Estimation of Three-Phase Transformer Models for Low-Frequency Transient Studies From Terminal MeasurementsIEEE Transactions on Magnetics, 2016
- The negative branch impedance in the transformer sequence circuit model2015
- Determination of Parameters of Zero-Sequence Equivalent Circuits for Three-Phase Three-Legged YNynd Transformers Based on Onsite Low-Voltage TestsIEEE Transactions on Power Delivery, 2013
- Numerical Methods for Least Squares Problems1996
- Zero phase sequence impedance and tank heating model for three phase three leg core type power transformers coupling magnetic field and electric circuit equations in a finite element softwareIEEE Transactions on Magnetics, 1995
- Calculation of zero phase sequence impedance for power transformers using numerical methodsIEEE Transactions on Magnetics, 1995
- Matrix Representation of Three-Phase N-Winding Transformers for Steady-State and Transient StudiesIEEE Power Engineering Review, 1982