During the past years, there has been an increase in the number of power transformer failures worldwide linked by the presence of corrosive sulfur compounds in mineral insulating oil, leading to the formation of deposits of highly conductive copper sulfide or silver sulfide. In oils in operation, a highly reactive elemental sulfur, in a form of eight atom molecule of sulfur, S8, with a strong affinity for silver can be detected which present a significant threat to the contacts of the on load tap changer (OLTC). The high-temperature reactivation process of adsorbents during or after the regeneration process of mineral insulating oils leads to the contamination of insulating oil with elemental sulfur. The paper presents an innovative low-temperature process for the efficient removal of S8 from mineral insulating oil, based on the application of a small amount of iron particles coated with copper on its surface as a key component of the reagent mixture which is dispersed in polyethylene glycol. Intensive mixing of the reagent mixture with mineral insulating oil at temperatures below 100°C enables the complete removal of S8 from the oil. High process efficiency, the removal of S8 from the initial 15 mg/kg to levels below the detection limit, is achieved by using a small amount of the reagent mixture relative to the oil mass (<0.2 wt.%), in laboratory conditions and on a pilot scale experiments. Applying this process and subsequent treatment with adsorbents, insulating oils with improved physical, chemical and electrical characteristics are obtained, suitable for further use in power transformers. This procedure reduces potential environmental and economic risks associated with power transformer failures. The next phase will involve further process optimization and industrial plant implementation.