Dejan Kolarski
Current Organizations / Institutes
The organizations/institutes from the scholar's latest article
Previous Organizations / Institutes
The organizations / institutes from the scholar's other articles in the past ten years
Dejan Kolarski has a total of 19 co-authors. Here are the top co-authors by number of shared publications:
- Jelena Janković
Univerzitet u Beogradu Elektrotehnički institut Nikola Tesla Koste Glavinića 8a 11000 Beograd Srbija
8 shared publications - Jelena Lukić
Univerzitet u Beogradu Elektrotehnički institut Nikola Tesla Koste Glavinića 8a 11000 Beograd Srbija
4 shared publications - Draginja Mihajlović
Laboratory for Testing and Calibration, Electrical Engineering Institute Nikola Tesla, Koste Glavinica 8a, 11000 Belgrade, Serbia
3 shared publications - Valentina Vasović
Laboratory for Testing and Calibration, Electrical Engineering Institute Nikola Tesla, Koste Glavinica 8a, 11000 Belgrade, Serbia
3 shared publications - Sandra Glisic
Faculty of Technology and Metallurgy, University of Belgrade, 11000 Belgrade, Serbia
2 shared publications A. M. Orlović
Faculty of Technology and Metallurgy, University of Belgrade, Belgrade, Serbia
1 shared publication
Latest Publications
- Open Access
Kinetic Analysis of the Reaction of Silver with Elemental Sulfur in Mineral Insulating Oil
Elemental sulfur (S8) reacts readily with silver, forming highly conductive silver sulfide on silver-coated components of on-load tap changers (OLTCs), forming a highly conductive silver sulfide film at the surface of an OLTC, which can lead to the failure of critical components in power transformers. This study investigates the reaction between metallic silver and elemental sulfur dissolved in mineral insulating oil across temperatures from 60 °C to 180 °C. The process involves three stages: the diffusion of sulfur through oil, surface reaction, and product diffusion. For low-viscosity oil, diffusion is not the limiting factor, and sulfur does not react immediately on the silver’s surface, suggesting possible adsorption or intermediate formation. A kinetic analysis revealed that the reaction follows first-order kinetics, with a change in mechanism above 150 °C. The reaction follows the Arrhenius equation in two separate regions: 60–150 °C and 150–180 °C. Activation energy was calculated as 23.67 kJ mol−1, and it can be concluded that the reaction is controlled by the diffusion of sulfur through mineral oil, and at higher temperatures (150 °C to 180 °C), the calculated activation energy is 160.69 kJ mol−1, which leads to the conclusion that the combined chemisorption and diffusion through a silver sulfide–oil interface becomes the new limiting factor.
Open AccessKinetic Analysis of the Reaction of Silver with Elemental Sulfur in Mineral Insulating Oil
Elemental sulfur (S8) reacts readily with silver, forming highly conductive silver sulfide on silver-coated components of on-load tap changers (OLTCs), forming a highly conductive silver sulfide film at the surface of an OLTC, which can lead to the failure of critical components in power transformers. This study investigates the reaction between metallic silver and elemental sulfur dissolved in mineral insulating oil across temperatures from 60 °C to 180 °C. The process involves three stages: the diffusion of sulfur through oil, surface reaction, and product diffusion. For low-viscosity oil, diffusion is not the limiting factor, and sulfur does not react immediately on the silver’s surface, suggesting possible adsorption or intermediate formation. A kinetic analysis revealed that the reaction follows first-order kinetics, with a change in mechanism above 150 °C. The reaction follows the Arrhenius equation in two separate regions: 60–150 °C and 150–180 °C. Activation energy was calculated as 23.67 kJ mol−1, and it can be concluded that the reaction is controlled by the diffusion of sulfur through mineral oil, and at higher temperatures (150 °C to 180 °C), the calculated activation energy is 160.69 kJ mol−1, which leads to the conclusion that the combined chemisorption and diffusion through a silver sulfide–oil interface becomes the new limiting factor.
- Open Access
- 16 July 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
Process for Simultaneous Removal of S8, DBDS, and PCBs From Mineral Insulating Oils
The presence of corrosive sulfur and polychlorinated biphenyls (PCBs) in mineral insulating oils poses significant challenge to the reliability of power transformers and presents serious environmental risks. Elemental sulfur (S8) and dibenzyl disulfide (DBDS) are well-known for causing the formation of metal sulfides on transformer components, leading to equipment failures, while PCBs present in insulating oils are persistent environmental pollutants with long-term health hazards. Current insulating oil purification techniques, including adsorbents, metal passivators and reagents, exhibit limited effectiveness, particularly if elemental sulfur is present in oil. This study introduces a novel reagent-based desulfurization process which uses copper deposited on iron particles dispersed in polyethylene glycol, for the complete removal of S8 from mineral insulating oil. The integration of S8 removal process with the KOH/PEG complex enables the simultaneous removal of S8, DBDS, and PCBs, with no residual metal particles detected in the oil following the treatment. Laboratory-scale experiments have shown the high efficiency of the developed process resulting in the improved physical-chemical and electrical properties of the oil, which was further verified on pilot scale unit and finally on the industrial scale process unit.
- 16 July 2025
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
Open AccessProcess for Simultaneous Removal of S8, DBDS, and PCBs From Mineral Insulating Oils
The presence of corrosive sulfur and polychlorinated biphenyls (PCBs) in mineral insulating oils poses significant challenge to the reliability of power transformers and presents serious environmental risks. Elemental sulfur (S8) and dibenzyl disulfide (DBDS) are well-known for causing the formation of metal sulfides on transformer components, leading to equipment failures, while PCBs present in insulating oils are persistent environmental pollutants with long-term health hazards. Current insulating oil purification techniques, including adsorbents, metal passivators and reagents, exhibit limited effectiveness, particularly if elemental sulfur is present in oil. This study introduces a novel reagent-based desulfurization process which uses copper deposited on iron particles dispersed in polyethylene glycol, for the complete removal of S8 from mineral insulating oil. The integration of S8 removal process with the KOH/PEG complex enables the simultaneous removal of S8, DBDS, and PCBs, with no residual metal particles detected in the oil following the treatment. Laboratory-scale experiments have shown the high efficiency of the developed process resulting in the improved physical-chemical and electrical properties of the oil, which was further verified on pilot scale unit and finally on the industrial scale process unit.
- 1 January 2025
- Published by Centre for Evaluation in Education and Science (CEON/CEES)
- p. 57-61
3PINT innovative technologies as permanent solution to mitigate corrosive sulphur in power transformers
Focus of 3PINT project is to upgrade readiness level of the innovative technology for the removal of corrosive sulphur, PCB and aging product from transformer oils. Technology itself includes chemical conversion process to refine transformer oils in eco-friendly manner. Used technology is environmentally closed with no toxic emissions and waste released into environment. In addition, innovative solution for corroded silver-plated contacts cleaning, effectively removes silver sulphide deposits from OLTC contacts, ensuring long-term reliability and complete power transformer corrosive sulphur mitigation.
- 1 January 2025
- Published by Centre for Evaluation in Education and Science (CEON/CEES)
- p. 57-61
3PINT innovative technologies as permanent solution to mitigate corrosive sulphur in power transformers
Focus of 3PINT project is to upgrade readiness level of the innovative technology for the removal of corrosive sulphur, PCB and aging product from transformer oils. Technology itself includes chemical conversion process to refine transformer oils in eco-friendly manner. Used technology is environmentally closed with no toxic emissions and waste released into environment. In addition, innovative solution for corroded silver-plated contacts cleaning, effectively removes silver sulphide deposits from OLTC contacts, ensuring long-term reliability and complete power transformer corrosive sulphur mitigation.
- Open Access
- 1 January 2025
- Published by Centre for Evaluation in Education and Science (CEON/CEES) in Zbornik Radova, Elektrotehnicki Institut Nikola Tesla
- No. 35,p. 127-146
Kinetics of the reaction between elemental sulfur and silver in synthetic esters and comparison with mineral oils
For decades, the problem of corrosive sulfur was considered to be exclusively associated with mineral oils. However, recent cases from industry have disproved this assumption. The presence of elemental sulfur in insulating oil causes corrosion of silver contacts and consequently leads to power transformer failures. The aim of this study is to determine the kinetics of the reaction between elemental sulfur and silver in synthetic ester within the temperature range of 120–180 °C. The elemental sulfur content in the oil during the reaction is determined using gas chromatography with an electron capture detector (GC-ECD). The results show that the reaction between silver and elemental sulfur follows the first-order law. A comparative analysis of the examined reaction in synthetic ester and mineral oil shows that the reaction proceeds faster in synthetic ester.
- 1 January 2025
- Published by Centre for Evaluation in Education and Science (CEON/CEES) in Zbornik Radova, Elektrotehnicki Institut Nikola Tesla
- No. 35,p. 127-146
Open AccessKinetics of the reaction between elemental sulfur and silver in synthetic esters and comparison with mineral oils
For decades, the problem of corrosive sulfur was considered to be exclusively associated with mineral oils. However, recent cases from industry have disproved this assumption. The presence of elemental sulfur in insulating oil causes corrosion of silver contacts and consequently leads to power transformer failures. The aim of this study is to determine the kinetics of the reaction between elemental sulfur and silver in synthetic ester within the temperature range of 120–180 °C. The elemental sulfur content in the oil during the reaction is determined using gas chromatography with an electron capture detector (GC-ECD). The results show that the reaction between silver and elemental sulfur follows the first-order law. A comparative analysis of the examined reaction in synthetic ester and mineral oil shows that the reaction proceeds faster in synthetic ester.
- Open Access
- 1 January 2024
- Published by Centre for Evaluation in Education and Science (CEON/CEES) in Zbornik Radova, Elektrotehnicki Institut Nikola Tesla
- No. 34,p. 83-94
Results of the GreenCleanS Project funded by the Science Fund of the Republic of Serbia
The project funded by the Science Fund of the Republic of Serbia, Development of Green Technology to Mitigate Power Transformer Failures Induced by Elemental Sulphur and Change Current Hazardous Practice in Transformer Oil Regeneration, under the acronym GreenCleanS focuses on developing a new technology for removing elemental sulphur molecule (S₈) from mineral insulating oils used in power transformers (PT) utilization an innovative low-temperature desulfurization process. The technology development includes experimental work at the laboratory scale and pilot scale level (technology readiness level, TRL 4), as well as the demonstration of the technology in an operational environment, involving the treatment of 3 tons of oil in a mobile desulfurization unit to achieve TRL 7. The implementation of this innovative technology will contribute to reducing the number of transformer failures caused by mineral oils containing S₈, a highly corrosive compound.
- 1 January 2024
- Published by Centre for Evaluation in Education and Science (CEON/CEES) in Zbornik Radova, Elektrotehnicki Institut Nikola Tesla
- No. 34,p. 83-94
Open AccessResults of the GreenCleanS Project funded by the Science Fund of the Republic of Serbia
The project funded by the Science Fund of the Republic of Serbia, Development of Green Technology to Mitigate Power Transformer Failures Induced by Elemental Sulphur and Change Current Hazardous Practice in Transformer Oil Regeneration, under the acronym GreenCleanS focuses on developing a new technology for removing elemental sulphur molecule (S₈) from mineral insulating oils used in power transformers (PT) utilization an innovative low-temperature desulfurization process. The technology development includes experimental work at the laboratory scale and pilot scale level (technology readiness level, TRL 4), as well as the demonstration of the technology in an operational environment, involving the treatment of 3 tons of oil in a mobile desulfurization unit to achieve TRL 7. The implementation of this innovative technology will contribute to reducing the number of transformer failures caused by mineral oils containing S₈, a highly corrosive compound.
- 1 January 2024
- Published by University Library in Kragujevac
PROCEDURE FOR REMOVING ELEMENTAL SULFUR FROM THE OIL OF POWER TRANSFORMERS - REDUCING THE RISK OF POWER TRANSFORMERS FAILURES
During the past years, there has been an increase in the number of power transformer failures worldwide linked by the presence of corrosive sulfur compounds in mineral insulating oil, leading to the formation of deposits of highly conductive copper sulfide or silver sulfide. In oils in operation, a highly reactive elemental sulfur, in a form of eight atom molecule of sulfur, S8, with a strong affinity for silver can be detected which present a significant threat to the contacts of the on load tap changer (OLTC). The high-temperature reactivation process of adsorbents during or after the regeneration process of mineral insulating oils leads to the contamination of insulating oil with elemental sulfur. The paper presents an innovative low-temperature process for the efficient removal of S8 from mineral insulating oil, based on the application of a small amount of iron particles coated with copper on its surface as a key component of the reagent mixture which is dispersed in polyethylene glycol. Intensive mixing of the reagent mixture with mineral insulating oil at temperatures below 100°C enables the complete removal of S8 from the oil. High process efficiency, the removal of S8 from the initial 15 mg/kg to levels below the detection limit, is achieved by using a small amount of the reagent mixture relative to the oil mass (<0.2 wt.%), in laboratory conditions and on a pilot scale experiments. Applying this process and subsequent treatment with adsorbents, insulating oils with improved physical, chemical and electrical characteristics are obtained, suitable for further use in power transformers. This procedure reduces potential environmental and economic risks associated with power transformer failures. The next phase will involve further process optimization and industrial plant implementation.
- 1 January 2024
- Published by University Library in Kragujevac
PROCEDURE FOR REMOVING ELEMENTAL SULFUR FROM THE OIL OF POWER TRANSFORMERS - REDUCING THE RISK OF POWER TRANSFORMERS FAILURES
During the past years, there has been an increase in the number of power transformer failures worldwide linked by the presence of corrosive sulfur compounds in mineral insulating oil, leading to the formation of deposits of highly conductive copper sulfide or silver sulfide. In oils in operation, a highly reactive elemental sulfur, in a form of eight atom molecule of sulfur, S8, with a strong affinity for silver can be detected which present a significant threat to the contacts of the on load tap changer (OLTC). The high-temperature reactivation process of adsorbents during or after the regeneration process of mineral insulating oils leads to the contamination of insulating oil with elemental sulfur. The paper presents an innovative low-temperature process for the efficient removal of S8 from mineral insulating oil, based on the application of a small amount of iron particles coated with copper on its surface as a key component of the reagent mixture which is dispersed in polyethylene glycol. Intensive mixing of the reagent mixture with mineral insulating oil at temperatures below 100°C enables the complete removal of S8 from the oil. High process efficiency, the removal of S8 from the initial 15 mg/kg to levels below the detection limit, is achieved by using a small amount of the reagent mixture relative to the oil mass (<0.2 wt.%), in laboratory conditions and on a pilot scale experiments. Applying this process and subsequent treatment with adsorbents, insulating oils with improved physical, chemical and electrical characteristics are obtained, suitable for further use in power transformers. This procedure reduces potential environmental and economic risks associated with power transformer failures. The next phase will involve further process optimization and industrial plant implementation.
- Open Access
Isotherm, Thermodynamic and Kinetic Studies of Elemental Sulfur Removal from Mineral Insulating Oils Using Highly Selective Adsorbent
Elemental sulfur (S8) is a corrosive sulfur compound which was found to be extremely reactive to silver, causing intensive silver sulfide (Ag2S) deposition on on-load tap changer (OLTC) contacts in power transformers. A highly selective adsorbent (HSA), called Tesla’Ssorb, for the removal of S8 from mineral insulating oils was prepared from raw material (RM) using the novel procedure. In this study, the adsorption properties of HSA for the removal of S8 from the oil were determined. RM and HSA were characterized using various techniques, such as field-emission scanning electron microscopy (FESEM), energy-dispersive X-ray (EDX), and X-ray diffraction (XRD). The performance of HSA was determined by adsorption equilibrium, thermodynamic, and kinetic study through batch experiments, at various temperatures and initial concentrations of S8. The obtained results were analyzed by Langmuir and Freundlich adsorption isotherms and it was found that equilibrium data were fitted better with the Langmuir isotherm model. The maximum adsorption capacity was 4.84 mg of S8/g of HSA at 353 K. Thermodynamic parameters, such as enthalpy (ΔH°), Gibbs free energy (ΔG°), and entropy (ΔS°), were calculated and it was found that the sorption process was spontaneous (ΔG° < 0) and endothermic in nature (ΔH° > 0). It was found that the adsorption of S8 follows pseudo-second-order kinetic model, and the activation energy indicated the activated chemisorption process.
Open AccessIsotherm, Thermodynamic and Kinetic Studies of Elemental Sulfur Removal from Mineral Insulating Oils Using Highly Selective Adsorbent
Elemental sulfur (S8) is a corrosive sulfur compound which was found to be extremely reactive to silver, causing intensive silver sulfide (Ag2S) deposition on on-load tap changer (OLTC) contacts in power transformers. A highly selective adsorbent (HSA), called Tesla’Ssorb, for the removal of S8 from mineral insulating oils was prepared from raw material (RM) using the novel procedure. In this study, the adsorption properties of HSA for the removal of S8 from the oil were determined. RM and HSA were characterized using various techniques, such as field-emission scanning electron microscopy (FESEM), energy-dispersive X-ray (EDX), and X-ray diffraction (XRD). The performance of HSA was determined by adsorption equilibrium, thermodynamic, and kinetic study through batch experiments, at various temperatures and initial concentrations of S8. The obtained results were analyzed by Langmuir and Freundlich adsorption isotherms and it was found that equilibrium data were fitted better with the Langmuir isotherm model. The maximum adsorption capacity was 4.84 mg of S8/g of HSA at 353 K. Thermodynamic parameters, such as enthalpy (ΔH°), Gibbs free energy (ΔG°), and entropy (ΔS°), were calculated and it was found that the sorption process was spontaneous (ΔG° < 0) and endothermic in nature (ΔH° > 0). It was found that the adsorption of S8 follows pseudo-second-order kinetic model, and the activation energy indicated the activated chemisorption process.
- Open Access
- 1 January 2021
- Published by Centre for Evaluation in Education and Science (CEON/CEES) in Zbornik Radova, Elektrotehnicki Institut Nikola Tesla
- Vol. 31 (31) , 113-123
Solving the problem of exploitation of transformers with corrosive sulfur by oil desulfurization using a strong inorganic base and organic solvent
Most power transformer failures are associated with the presence of corrosive sulfur compounds in mineral insulating oil, of which dibenzyl disulfide (DBDS) is the best known and most widespread corrosive sulfur compound. The oil of failed transformers usually contained DBDS, a compound with a pronounced affinity for the formation of copper (I) sulfide (Cu2S). Copper (I) sulfide is a compound that does not dissolve in oil, conducts electricity, and can be deposited on the paper insulation or copper conductor of the transformer. Created conductive paths between the windings can initiate turn-to-turn breakdown and failure of the transformer. Several technological procedures have been developed as a solution to oil corrosivity. The application of desulfurization technology developed by the Electrical Engineering Institute "Nikola Tesla" enables the efficient removal of DBDS and aging products from mineral insulation oils.
- 1 January 2021
- Published by Centre for Evaluation in Education and Science (CEON/CEES) in Zbornik Radova, Elektrotehnicki Institut Nikola Tesla
- Vol. 31 (31) , 113-123
Open AccessSolving the problem of exploitation of transformers with corrosive sulfur by oil desulfurization using a strong inorganic base and organic solvent
Most power transformer failures are associated with the presence of corrosive sulfur compounds in mineral insulating oil, of which dibenzyl disulfide (DBDS) is the best known and most widespread corrosive sulfur compound. The oil of failed transformers usually contained DBDS, a compound with a pronounced affinity for the formation of copper (I) sulfide (Cu2S). Copper (I) sulfide is a compound that does not dissolve in oil, conducts electricity, and can be deposited on the paper insulation or copper conductor of the transformer. Created conductive paths between the windings can initiate turn-to-turn breakdown and failure of the transformer. Several technological procedures have been developed as a solution to oil corrosivity. The application of desulfurization technology developed by the Electrical Engineering Institute "Nikola Tesla" enables the efficient removal of DBDS and aging products from mineral insulation oils.