Evaluation of Recommended Water Sample Collection Methods and the Impact of Holding Time on Legionella Recovery and Variability from Healthcare Building Water Systems
Open Access
- 11 November 2020
- journal article
- research article
- Published by MDPI AG in Microorganisms
- Vol. 8 (11) , 1770
Abstract
Water safety and management programs (WSMP) utilize field measurements to evaluate control limits and monitor water quality parameters including Legionella presence. This monitoring is important to verify that the plan is being implemented properly. However, once it has been determined when and how to sample for Legionella, it is important to choose appropriate collection and processing methods. We sought to compare processing immediate and flushed samples, filtration of different volumes collected, and sample hold times. Hot water samples were collected immediately and after a 2-min flush. These samples were plated directly and after filtration of either 100 mL, 200 mL, or 1 L. Additionally, unflushed samples were collected and processed immediately and after 1, 24, and 48 h of hold time. We found that flushed samples had significant reductions in Legionella counts compared to immediate samples. Processing 100 mL of that immediate sample both directly and after filter concentration yielded the highest concentration and percent sample positivity, respectively. We also show that there was no difference in culture values from time 0 compared to hold times of 1 h and 24 h. At 48 h, there were slightly fewer Legionella recovered than at time 0. However, Legionella counts were so variable based on sampling location and date that this hold time effect was minimal. The interpretation of Legionella culture results depends on the sample collection and processing methods used, as these can have a huge impact on the success of sampling and the validation of control measures.Keywords
This publication has 23 references indexed in Scilit:
- Parameters predictive of Legionella contamination in hot water systems: Association with trace elements and heterotrophic plate countsWater Research, 2011
- Role of Environmental Surveillance in Determining the Risk of Hospital-Acquired Legionellosis: A National Surveillance Study With Clinical CorrelationsInfection Control & Hospital Epidemiology, 2007
- Prospective 3-Year Surveillance for Nosocomial and EnvironmentalLegionella pneumophila: Implications for Infection ControlInfection Control & Hospital Epidemiology, 2006
- Reducing Legionella Colonization of Water Systems with MonochloramineEmerging Infectious Diseases, 2006
- Environmental Cultures and Hospital-Acquired Legionnaires' Disease: A 5-Year Prospective Study in 20 Hospitals in Catalonia, SpainInfection Control & Hospital Epidemiology, 2004
- Legionellain the Hospital Water Supply A Plea for Decision Making Based on Evidence-Based MedicineInfection Control & Hospital Epidemiology, 2001
- Hospital Characteristics Associated With Colonization of Water Systems byLegionellaand Risk of Nosocomial Legionnaires' Disease: A Cohort Study of 15 HospitalsInfection Control & Hospital Epidemiology, 1999
- LegionellosisNew England Journal of Medicine, 1997
- NOSOCOMIAL LEGIONELLOSIS IN SURGICAL PATIENTS WITH HEAD-AND-NECK CANCER: IMPLICATIONS FOR EPIDEMIOLOGICAL RESERVOIR AND MODE OF TRANSMISSIONThe Lancet, 1985
- LEGIONELLACEAE IN THE HOSPITAL WATER-SUPPLYThe Lancet, 1983