Partial Discharge Progress and Breakdown Characteristics of Oil-Impregnated Paper Insulation System for Capacitor Voltage Transformers
- 18 November 2024
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 32 (4) , 2257-2264
Abstract
Capacitor voltage transformers (CVTs) with aluminum foil/oil-impregnated papers composite insulation system have been operated over 30 years in substations. An insulation diagnosis of CVT is expected to be based on detecting partial discharge (PD). However, PD characteristics from PD inception to breakdown (BD) have not been clarified yet. In an insulation diagnosis of CVT, it is necessary to diagnose a risk level of BD based on PD characteristics. In this paper, we investigated the PD characteristics using electrical and optical measurement on the fundamental insulation model of CVT and discussed the PD progress characteristics leading to BD. Experimental results revealed that PD, which was generated from the aluminum foil electrode periphery, progressed from the creeping direction to the penetrating direction of the oil-impregnated papers, and then BD occurred. When PD penetrated the oil-impregnated paper, PD charge increased, and hydrogen-based gas was generated. This PD progress can be an important factor to establish insulation diagnosis based on PD measurement of CVT.Keywords
This publication has 14 references indexed in Scilit:
- Study on Failure Mechanism of Oil Paper Insulation Under Partial Discharge of Interlayer BubbleIEEE Transactions on Industry Applications, 2022
- Partial Discharge Characteristics and Deterioration Mechanisms of Bubble-Containing Oil-Impregnated PaperIEEE Transactions on Dielectrics and Electrical Insulation, 2022
- Partial discharge progress and breakdown characteristics of aluminum foil/oil-impregnated paper insulation system2022
- Effect of Aging Degree on Partial Discharge Degradation of Oil-paper InsulationIEEE Transactions on Dielectrics and Electrical Insulation, 2021
- Analysis on partial discharges variability in mineral oil under long-term AC voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2018
- Partial discharge development in needle-plane configuration of oil-paper insulation under AC voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Partial discharges in a cavity embedded in oil-impregnated paper: effect of electrical and thermal agingIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers2009
- Techniques for diagnosing deterioration of oil-impregnated paper-film power capacitorsIEEE Transactions on Power Delivery, 1997
- Gas Evolution Characteristics of Silicone Liquid under Electrical Discharge ConditionsIEEJ Transactions on Fundamentals and Materials, 1977