Influence of Arc Size on the Ignition and Flame Propagation of Cable Fire
Open Access
Abstract
Cable fire caused by arc faults is one of the essential factors threatening the safe operation of a power system. The ignition and flame propagation of cable fire dependent on the characteristics of the arc discharge is lackingin in-depth understanding at present. In this work, with the constant electric power deposited into the arc discharge, the effects of arc size on the ignition and flame propagation of 110 kV XLPE cable fire are investigated for the first time. The arc size is changed by varying the gap distance of electrodes from 1.5 cm to 2.5 cm. It is interesting to find that the larger the arc size is, the faster the cable fire is ignited and propagates, and the larger the damaged area of the sheath of the cable is. Therein, when the gap distance increases from 1.3 cm to 3.1 cm, the equivalent impedance and the length of the arc discharge increase nearly seven times and three times, respectively. However, the gas temperature of the arc decreases slightly from 2280 K to 2100 K. In addition, a 3D model of the cable fire ignited by arc discharge is computed by Pyrosim software with fire dynamic simulation (FDS) module. Simulated results show that as the arc size increases, the cable fire is ignited faster, the flame propagates both vertically and horizontally increasing significantly, which is agreed well with the experimental results. This study deepens the understanding of the cable fire ignited by arc discharge and therefore it is useful for the evaluation and prevention of cable fire.Keywords
Funding Information
- National Natural Science Foundation of China (51977110)
This publication has 22 references indexed in Scilit:
- Fire behavior of halogen-free flame retardant electrical cables with the cone calorimeterJournal of Hazardous Materials, 2018
- Use of thermocouples and argon line broadening for gas temperature measurement in a radio frequency atmospheric microplasma jetReview of Scientific Instruments, 2017
- External heating of electrical cables and auto-ignition investigationJournal of Hazardous Materials, 2017
- An enhanced fire hazard assessment model and validation experiments for vertical cable traysNuclear Engineering and Design, 2016
- Development of an anaerobic pyrolysis model for fire retardant cable sheathing materialsPolymer Degradation and Stability, 2015
- Burning Characteristics of Power Cables in a CompartmentProcedia Earth and Planetary Science, 2015
- Cable tunnel fire experiment study based on linear optical fiber fire detectors2013
- Experimental Study of Fire Characteristics of a Tray Flame Retardant CableJournal of the Korean Society of Safety, 2013
- Cone calorimeter analysis of UL‐94 V‐rated plasticsFire and Materials, 2006
- Some comments on the use of cone calorimeter dataPolymer Degradation and Stability, 2005