Comparative analysis of active filters, inductor-capacitor and inductor-capacitor-inductor passive filters in reducing harmonics
Open Access
- 1 June 2025
- journal article
- Published by Institute of Advanced Engineering and Science in International Journal of Electrical and Computer Engineering (IJECE)
- Vol. 15 (3) , 2567-2582
Abstract
Control equipment at substations requires a rectifier to convert alternative current (AC)-direct current (DC) electric current to provide DC power for relays, motors for disconnector switches and power breaker switches, and telecommunications equipment. Rectifiers have non-linear load characteristics, which can result in a waveform that is not pure sinusoidal due to the interaction of fundamental frequency sinusoidal waves with other waves known as harmonics. Therefore, to not interfere with the equipment's work, a filter is needed to reduce the harmonics produced by the rectifier. In this research, using MATLAB/Simulink, prevention was carried out using active filters, inductor-capacitor (LC), and inductor-capacitor-inductor (LCL) passive filters (Ta, Tc, and Td designs) separately. After the research was carried out, it was found that the amount of harmonics before installing the filter was 49.61%. Then, after installing the active filter, the harmonics were reduced to 0.29%, the installation of the passive LC filter was reduced to 9.29%, and the installation of the LCL filter (Ta, Tc, and Td) became 1.44%, 0.29%, and 1.44%.Keywords
This publication has 27 references indexed in Scilit:
- Directly power system harmonics estimation using Equilibrium OptimizerElectric Power Systems Research, 2024
- Fault-tolerant shunt active power filter with synchronous reference frame control and self-tuning filterMeasurement: Sensors, 2024
- Harmonic analysis and attenuation using LCL-filter in doubly fed induction generator based wind conversion system using real time simulation based OPAL-RTAlexandria Engineering Journal, 2022
- Reducing of total harmonic distortion using passive filter simulation to suppress harmonic currents with the case: General Hospital, Universitas Kristen Indonesia JakartaIOP Conference Series: Earth and Environmental Science, 2021
- A multi‐objective optimized design of LCL filters for grid‐connected voltage source inverters considering discrete componentsInternational Transactions on Electrical Energy Systems, 2021
- Power Quality Improvement using a Shunt Active Power Filter for Grid Connected Photovoltaic Generation System2020
- An integrated design approach of LCL filters based on nonlinear inductors for grid-connected inverter applicationsElectric Power Systems Research, 2020
- The Influence of LC Filter on the Current Control of PWM-Fed Induction Motor Considering the Effect of Back-EMFJournal of Physics: Conference Series, 2020
- Performance comparison of passive series R and shunt R‐C damped LCL filter for grid‐connected invertersThe Journal of Engineering, 2019
- Optimal design method of passive LCL filters for grid-connected inverters2016