Wet Snow Flashover Characteristics of 500-kV AC Insulator Strings with Different Arrangements
Open Access
- 5 March 2019
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 9 (5) , 930
Abstract
In order to study the wet snow flashover characteristics of 500-kV AC insulator strings under different arrangements, wet snow flashover tests were carried out in the large climate chamber of China Electric Power Research Institute (CEPRI). The wet snow flashover voltages were obtained by the even-rising method and the flashovers were filmed by a camera. The test results showed that the installation of an anti-icing shed of large diameter could increase the wet snow flashover voltage. The distance between the two insulators was a key parameter that influenced the discharge process and the flashover voltage. Under Λ-string arrangement, for common insulators, the flashover performance of iced insulators increased with the connection angle; for anti-icing insulators, the flashover performance increased at first and then decreased with the connection angle. In wet snow conditions, when the connection angle was at the commonly adopted angle of 60°, the flashover performance of the common insulators under the V-string and Λ-string arrangements was almost the same. For anti-icing insulators, however, the V-string arrangement was recommended according to the tests. The results obtained in this study can provide a reference for external insulation design in wet snow conditions.Keywords
Funding Information
- Electric Power Research Institute of State Grid Tianjin Electric Power Company (SGTYHT/15-JS-191)
This publication has 14 references indexed in Scilit:
- Influence of AC electric field on conductor icingIEEE Transactions on Dielectrics and Electrical Insulation, 2016
- DC Flashover Performance of Ice-Covered Composite Insulators with Parallel Air GapsEnergies, 2015
- Study on the DC Flashover Performance of Various Types of Insulators With Fan-Shaped Nonuniform PollutionIEEE Transactions on Power Delivery, 2015
- Electrical performance of composite insulators under icing conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Laboratory Tests and Web Based Surveillance to Determine the Ice- and Snow Performance of InsulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2007
- Selection of Line Insulators With Respect to Ice and Snow—Part II: Selection Methods and Mitigation OptionsIEEE Transactions on Power Delivery, 2007
- Three-Dimensional Modeling of Potential and Electric-Field Distributions Along an EHV Ceramic Post Insulator Covered With Ice—Part I: Simulations of a Melting PeriodIEEE Transactions on Power Delivery, 2005
- Selection of Station Insulators With Respect to Ice and Snow—Part I: Technical Context and Environmental ExposureIEEE Transactions on Power Delivery, 2005
- Selection of Station Insulators With Respect to Ice and Snow—Part II: Methods of Selection and Options for MitigationIEEE Transactions on Power Delivery, 2005
- Experimental study and mathematical modelling of flashover on extra‐high voltage insulators covered with iceHydrological Processes, 2004